Skip to content
Permalink
main
Switch branches/tags
Go to file
 
 
Cannot retrieve contributors at this time
<?xml version="1.0" encoding="UTF-8"?>
<zabbix_export>
<version>5.0</version>
<date>2021-06-01T16:56:11Z</date>
<groups>
<group>
<name>Retificadores</name>
</group>
</groups>
<templates>
<template>
<template>Template-Vertiv</template>
<name>Template-Vertiv</name>
<groups>
<group>
<name>Retificadores</name>
</group>
</groups>
<applications>
<application>
<name>Inform</name>
</application>
<application>
<name>Operational</name>
</application>
</applications>
<items>
<item>
<name>Battery 2 Capacity</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.5.8.0</snmp_oid>
<key>fBattery2Capacity</key>
<units>%</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<triggers>
<trigger>
<expression>{last(#2)}&lt;99</expression>
<name>Battery 2 Capacity on {HOST.NAME}</name>
<priority>HIGH</priority>
</trigger>
</triggers>
</item>
<item>
<name>Battery 1 Capacity</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.5.3.0</snmp_oid>
<key>ifBattery1Capacity</key>
<units>%</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<triggers>
<trigger>
<expression>{last(#1)}&lt;90</expression>
<name>Battery 1 Capacity on {HOST.NAME}</name>
<priority>HIGH</priority>
</trigger>
<trigger>
<expression>{last(#1)}&lt;50</expression>
<name>Battery 1 on Half {HOST.NAME}</name>
<priority>HIGH</priority>
</trigger>
</triggers>
</item>
<item>
<name>Battery 1 Current</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.5.2.0</snmp_oid>
<key>ifBattery1Current</key>
<value_type>FLOAT</value_type>
<units>A</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<preprocessing>
<step>
<type>MULTIPLIER</type>
<params>0.001</params>
</step>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>6h</params>
</step>
</preprocessing>
</item>
<item>
<name>Battery 2 Current</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.5.7.0</snmp_oid>
<key>ifBattery2Current</key>
<value_type>FLOAT</value_type>
<units>A</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<preprocessing>
<step>
<type>MULTIPLIER</type>
<params>0.001</params>
</step>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>6h</params>
</step>
</preprocessing>
</item>
<item>
<name>Battery Voltage</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.5.1.0</snmp_oid>
<key>ifBatteryVoltage</key>
<value_type>FLOAT</value_type>
<units>V</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<preprocessing>
<step>
<type>MULTIPLIER</type>
<params>0.001</params>
</step>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>6h</params>
</step>
</preprocessing>
</item>
<item>
<name>Capacidade da Bateria (%)</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.5.13.0</snmp_oid>
<key>ifCapacidadeBateria</key>
<value_type>FLOAT</value_type>
<units>%</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<preprocessing>
<step>
<type>MULTIPLIER</type>
<params>0.001</params>
</step>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>6h</params>
</step>
</preprocessing>
<triggers>
<trigger>
<expression>{last(#1)}&lt;90</expression>
<name>Bateria Descarregando {HOST.NAME}</name>
<status>DISABLED</status>
<priority>HIGH</priority>
<manual_close>YES</manual_close>
</trigger>
<trigger>
<expression>{last(#1)}&lt;50</expression>
<name>Bateria Na Metade {HOST.NAME}</name>
<status>DISABLED</status>
<priority>DISASTER</priority>
<manual_close>YES</manual_close>
</trigger>
</triggers>
</item>
<item>
<name>System Current</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.3.0</snmp_oid>
<key>ifSystemCurrent</key>
<value_type>FLOAT</value_type>
<units>A</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<preprocessing>
<step>
<type>MULTIPLIER</type>
<params>0.001</params>
</step>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>6h</params>
</step>
</preprocessing>
</item>
<item>
<name>System Status</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.1.0</snmp_oid>
<key>ifSystemStatus</key>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
</item>
<item>
<name>System Used Capacity</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.4.0</snmp_oid>
<key>ifSystemUsedCapacity</key>
<value_type>FLOAT</value_type>
<units>%</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
</item>
<item>
<name>System Voltage</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.2.0</snmp_oid>
<key>ifSystemVoltage</key>
<value_type>FLOAT</value_type>
<units>V</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<preprocessing>
<step>
<type>MULTIPLIER</type>
<params>0.001</params>
</step>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>6h</params>
</step>
</preprocessing>
</item>
<item>
<name>psTemperature1</name>
<type>SNMP_AGENT</type>
<snmp_oid>1.3.6.1.4.1.6302.2.1.2.7.1.0</snmp_oid>
<key>ps1.temperature[upsHighPrecBatteryTemperature]</key>
<history>7d</history>
<value_type>FLOAT</value_type>
<units>℃</units>
<description>MIB: PowerNet-MIB&#13;
The current internal UPS temperature in Celsius.&#13;
Temperatures below zero read as 0.</description>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<preprocessing>
<step>
<type>MULTIPLIER</type>
<params>0.001</params>
</step>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>6h</params>
</step>
</preprocessing>
</item>
<item>
<name>psTemperature2</name>
<type>SNMP_AGENT</type>
<snmp_oid>1.3.6.1.4.1.6302.2.1.2.7.2.0</snmp_oid>
<key>ps2.temperature[upsHighPrecBatteryTemperature]</key>
<history>7d</history>
<value_type>FLOAT</value_type>
<units>℃</units>
<description>MIB: PowerNet-MIB&#13;
The current internal UPS temperature in Celsius.&#13;
Temperatures below zero read as 0.</description>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<preprocessing>
<step>
<type>MULTIPLIER</type>
<params>0.001</params>
</step>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>6h</params>
</step>
</preprocessing>
</item>
<item>
<name>psStatusBatteryMode</name>
<type>SNMP_AGENT</type>
<snmp_oid>1.3.6.1.4.1.6302.2.1.2.9.0</snmp_oid>
<key>psbattery.status[upsBasicBatteryStatus]</key>
<history>7d</history>
<description>MIB: PowerNet-MIB&#13;
The status of the UPS batteries. A batteryLow(3) value&#13;
indicates the UPS will be unable to sustain the current&#13;
load, and its services will be lost if power is not restored.&#13;
The amount of run time in reserve at the time of low battery&#13;
can be configured by the upsAdvConfigLowBatteryRunTime.&#13;
A batteryInFaultCondition(4)value indicates that a battery&#13;
installed has an internal error condition.</description>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<valuemap>
<name>PowerNet-MIB::upsBasicBatteryStatus</name>
</valuemap>
<preprocessing>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>6h</params>
</step>
</preprocessing>
<triggers>
<trigger>
<expression>{last(0)}=3</expression>
<name>The battery power is too low to support the load on {HOST.NAME}</name>
<priority>DISASTER</priority>
</trigger>
</triggers>
</item>
<item>
<name>Input Line A Current</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.6.4.0</snmp_oid>
<key>psInputLineACurrent</key>
<value_type>FLOAT</value_type>
<units>A</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<preprocessing>
<step>
<type>MULTIPLIER</type>
<params>0.001</params>
</step>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>6h</params>
</step>
</preprocessing>
</item>
<item>
<name>Input Line A Voltage</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.6.1.0</snmp_oid>
<key>psInputLineAVoltage</key>
<value_type>FLOAT</value_type>
<units>V</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<preprocessing>
<step>
<type>MULTIPLIER</type>
<params>0.001</params>
</step>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>6h</params>
</step>
</preprocessing>
</item>
<item>
<name>Input Line B Current</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.6.5.0</snmp_oid>
<key>psInputLineBCurrent</key>
<value_type>FLOAT</value_type>
<units>A</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<preprocessing>
<step>
<type>MULTIPLIER</type>
<params>0.001</params>
</step>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>6h</params>
</step>
</preprocessing>
</item>
<item>
<name>Input Line B Voltage</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.6.2.0</snmp_oid>
<key>psInputLineBVoltage</key>
<value_type>FLOAT</value_type>
<units>V</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<preprocessing>
<step>
<type>MULTIPLIER</type>
<params>0.001</params>
</step>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>6h</params>
</step>
</preprocessing>
</item>
<item>
<name>Input Line C Current</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.6.6.0</snmp_oid>
<key>psInputLineCCurrent</key>
<value_type>FLOAT</value_type>
<units>A</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<preprocessing>
<step>
<type>MULTIPLIER</type>
<params>0.001</params>
</step>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>6h</params>
</step>
</preprocessing>
</item>
<item>
<name>Input Line C Voltage</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.6.3.0</snmp_oid>
<key>psInputLineCVoltage</key>
<value_type>FLOAT</value_type>
<units>V</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<preprocessing>
<step>
<type>MULTIPLIER</type>
<params>0.001</params>
</step>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>6h</params>
</step>
</preprocessing>
</item>
<item>
<name>psSystemTotalACEnergy</name>
<type>SNMP_AGENT</type>
<snmp_oid>1.3.6.1.4.1.6302.2.1.2.11.11.0</snmp_oid>
<key>psSystemTotalACEnergy</key>
<value_type>FLOAT</value_type>
<units>kWh</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<preprocessing>
<step>
<type>MULTIPLIER</type>
<params>0.001</params>
</step>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>6h</params>
</step>
</preprocessing>
</item>
<item>
<name>psSystemTotalDCEnergy</name>
<type>SNMP_AGENT</type>
<snmp_oid>1.3.6.1.4.1.6302.2.1.2.11.12.0</snmp_oid>
<key>psSystemTotalDCEnergy</key>
<value_type>FLOAT</value_type>
<units>kWh</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<preprocessing>
<step>
<type>MULTIPLIER</type>
<params>0.001</params>
</step>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>6h</params>
</step>
</preprocessing>
</item>
<item>
<name>Total Load Current</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.12.1.0</snmp_oid>
<key>psTotalLoadCurrent</key>
<value_type>FLOAT</value_type>
<units>A</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<preprocessing>
<step>
<type>MULTIPLIER</type>
<params>0.001</params>
</step>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>6h</params>
</step>
</preprocessing>
</item>
<item>
<name>Capacidade Usada dos Retificadores</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.11.3.0</snmp_oid>
<key>rectifiersUsedCapacity</key>
<units>%</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
</item>
</items>
<discovery_rules>
<discovery_rule>
<name>Alarms Description</name>
<type>SNMP_AGENT</type>
<snmp_oid>discover[{#DESCR},SNMPv2-SMI::enterprises.6302.2.1.4.1.5]</snmp_oid>
<key>ifAlarmDescription</key>
<lifetime>0</lifetime>
<item_prototypes>
<item_prototype>
<name>{#DESCR}</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.4.1.4.{#SNMPINDEX}</snmp_oid>
<key>if[{#DESCR}]</key>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<valuemap>
<name>AlarmVertiv</name>
</valuemap>
<preprocessing>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>1m</params>
</step>
</preprocessing>
<trigger_prototypes>
<trigger_prototype>
<expression>{last()}=6</expression>
<name>{#DESCR} - CRITICAL</name>
<priority>HIGH</priority>
<manual_close>YES</manual_close>
</trigger_prototype>
<trigger_prototype>
<expression>{last()}=3</expression>
<name>{#DESCR} - WARNING</name>
<priority>AVERAGE</priority>
<manual_close>YES</manual_close>
</trigger_prototype>
</trigger_prototypes>
</item_prototype>
</item_prototypes>
</discovery_rule>
<discovery_rule>
<name>Battery</name>
<type>SNMP_AGENT</type>
<snmp_oid>discover[{#IFBATTERY},SNMPv2-SMI::enterprises.6302.2.1.2.5.5.1.3]</snmp_oid>
<key>ifBattery</key>
<lifetime>1h</lifetime>
<item_prototypes>
<item_prototype>
<name>{#IFBATTERY} - Capacidade</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.5.5.1.4.{#SNMPINDEX}</snmp_oid>
<key>ifBatteryRating[{#IFBATTERY}]</key>
<units>Ah</units>
<description>Tipo de Bateria Utilizada</description>
<applications>
<application>
<name>Inform</name>
</application>
</applications>
<preprocessing>
<step>
<type>MULTIPLIER</type>
<params>0.001</params>
</step>
</preprocessing>
</item_prototype>
</item_prototypes>
</discovery_rule>
<discovery_rule>
<name>Retificadores</name>
<type>SNMP_AGENT</type>
<snmp_oid>discover[{#IFDESCR},SNMPv2-SMI::enterprises.6302.2.1.2.11.4.1.7]</snmp_oid>
<key>ifRetificadores</key>
<lifetime>1h</lifetime>
<item_prototypes>
<item_prototype>
<name>{#IFDESCR} - Capacidade da Corrente</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.11.4.1.6.{#SNMPINDEX}</snmp_oid>
<key>ifCurrentCapacity[{#IFDESCR}]</key>
<delay>1h</delay>
<value_type>FLOAT</value_type>
<units>A</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<preprocessing>
<step>
<type>MULTIPLIER</type>
<params>0.001</params>
</step>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>6h</params>
</step>
</preprocessing>
</item_prototype>
<item_prototype>
<name>{#IFDESCR} - Falha no Retificador</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.11.4.1.8.{#SNMPINDEX}</snmp_oid>
<key>ifFailRectifyer[{#IFDESCR}]</key>
<delay>1h</delay>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<valuemap>
<name>PostgreSQL recovery role</name>
</valuemap>
<trigger_prototypes>
<trigger_prototype>
<expression>{last()}&lt;&gt;2</expression>
<name>Falha no Retificador</name>
<priority>HIGH</priority>
</trigger_prototype>
</trigger_prototypes>
</item_prototype>
<item_prototype>
<name>Hardware Version {#IFDESCR}</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.11.4.1.3.{#SNMPINDEX}</snmp_oid>
<key>ifHardwareVersion[{#IFDESCR}]</key>
<delay>1h</delay>
<trends>0</trends>
<value_type>CHAR</value_type>
<applications>
<application>
<name>Inform</name>
</application>
</applications>
</item_prototype>
<item_prototype>
<name>Product Model {#IFDESCR}</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.11.4.1.2.{#SNMPINDEX}</snmp_oid>
<key>ifProducModel[{#IFDESCR}]</key>
<delay>1h</delay>
<trends>0</trends>
<value_type>CHAR</value_type>
<applications>
<application>
<name>Inform</name>
</application>
</applications>
</item_prototype>
<item_prototype>
<name>Software Revision {#IFDESCR}</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.11.4.1.4.{#SNMPINDEX}</snmp_oid>
<key>ifSoftwareRevision[{#IFDESCR}]</key>
<delay>1h</delay>
<trends>0</trends>
<value_type>CHAR</value_type>
<applications>
<application>
<name>Inform</name>
</application>
</applications>
</item_prototype>
<item_prototype>
<name>{#IFDESCR} - Temperature</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.11.4.1.9.{#SNMPINDEX}</snmp_oid>
<key>ifTemperatura[{#IFDESCR}]</key>
<delay>1h</delay>
<value_type>FLOAT</value_type>
<units>℃</units>
<applications>
<application>
<name>Operational</name>
</application>
</applications>
<preprocessing>
<step>
<type>MULTIPLIER</type>
<params>0.001</params>
</step>
<step>
<type>DISCARD_UNCHANGED_HEARTBEAT</type>
<params>6h</params>
</step>
</preprocessing>
</item_prototype>
<item_prototype>
<name>Serial {#IFDESCR}</name>
<type>SNMP_AGENT</type>
<snmp_oid>SNMPv2-SMI::enterprises.6302.2.1.2.11.4.1.5.{#SNMPINDEX}</snmp_oid>
<key>serial[{#IFDESCR}]</key>
<delay>1h</delay>
<trends>0</trends>
<value_type>CHAR</value_type>
<applications>
<application>
<name>Inform</name>
</application>
</applications>
</item_prototype>
</item_prototypes>
</discovery_rule>
</discovery_rules>
<macros>
<macro>
<macro>{$HOSTNAME}</macro>
<value>{#IFHOSTNAME}</value>
<description>HOSTNAME</description>
</macro>
</macros>
</template>
</templates>
<value_maps>
<value_map>
<name>AlarmVertiv</name>
<mappings>
<mapping>
<value>3</value>
<newvalue>Warning</newvalue>
</mapping>
<mapping>
<value>6</value>
<newvalue>Critical</newvalue>
</mapping>
</mappings>
</value_map>
<value_map>
<name>PostgreSQL recovery role</name>
<mappings>
<mapping>
<value>0</value>
<newvalue>Master</newvalue>
</mapping>
<mapping>
<value>1</value>
<newvalue>Standby</newvalue>
</mapping>
</mappings>
</value_map>
<value_map>
<name>PowerNet-MIB::upsBasicBatteryStatus</name>
<mappings>
<mapping>
<value>1</value>
<newvalue>Unknown</newvalue>
</mapping>
<mapping>
<value>2</value>
<newvalue>Normal</newvalue>
</mapping>
<mapping>
<value>3</value>
<newvalue>Low</newvalue>
</mapping>
<mapping>
<value>4</value>
<newvalue>In Fault Condition</newvalue>
</mapping>
</mappings>
</value_map>
</value_maps>
</zabbix_export>