PLCnext Engineer Component that allows automatic configuration and startup of the local I/O bus (Axioline or Inline).
Branch: master
Clone or download
martinboers Merge branch 'patch-1' into 'master'
Update README.md

See merge request TCS_SupportService/PLCnext_Controls/Project_Collection/BusConductor!2
Latest commit a75bc2c Jul 15, 2019
Permalink
Type Name Latest commit message Commit time
Failed to load latest commit information.
design Merge branch 'master' of git-ima.europe.phoenixcontact.com:TCS_Suppor… Jul 10, 2019
generic_axioline Merge branch 'master' of git-ima.europe.phoenixcontact.com:TCS_Suppor… Jul 10, 2019
generic_inline Merge branch 'master' of git-ima.europe.phoenixcontact.com:TCS_Suppor… Jul 10, 2019
images Merge branch 'master' of git-ima.europe.phoenixcontact.com:TCS_Suppor… Jul 10, 2019
src Merge branch 'master' of git-ima.europe.phoenixcontact.com:TCS_Suppor… Jul 10, 2019
.gitignore Merge branch 'master' of git-ima.europe.phoenixcontact.com:TCS_Suppor… Jul 10, 2019
BusConductor.acf.config Merge branch 'master' of git-ima.europe.phoenixcontact.com:TCS_Suppor… Jul 10, 2019
CMakeLists.txt Merge branch 'master' of git-ima.europe.phoenixcontact.com:TCS_Suppor… Jul 10, 2019
CONTRIBUTING.md Merge branch 'master' of git-ima.europe.phoenixcontact.com:TCS_Suppor… Jul 10, 2019
CONTRIBUTORS.md Merge branch 'master' of git-ima.europe.phoenixcontact.com:TCS_Suppor… Jul 10, 2019
CodeOfConduct.md Merge branch 'master' of git-ima.europe.phoenixcontact.com:TCS_Suppor… Jul 10, 2019
LICENSE Merge branch 'master' of git-ima.europe.phoenixcontact.com:TCS_Suppor… Jul 10, 2019
MAINTAINERS.md Merge branch 'master' of git-ima.europe.phoenixcontact.com:TCS_Suppor… Jul 10, 2019
PLCnext_Store_Icons_1024x1024_Library_NoFrame-20190611083342.png Merge branch 'master' of git-ima.europe.phoenixcontact.com:TCS_Suppor… Jul 10, 2019
README.md Update README.md Jul 15, 2019
SECURITY.md Merge branch 'master' of git-ima.europe.phoenixcontact.com:TCS_Suppor… Jul 10, 2019
plcnext.proj Merge branch 'master' of git-ima.europe.phoenixcontact.com:TCS_Suppor… Jul 10, 2019

README.md

PLCnext Technology - Bus Conductor

Feature Requests Bugs License Web Community

Date Version Authors
02.07.2019 1.0 Martin Boers

Description

This app can be used to configure a local PLCnext Control I/O bus, containing either Axioline or Inline I/O modules, without the need to hard-code the specific I/O configuration either directly in .tic files, or indirectly using PLCnext Engineer.

This app can be used in any application where the precise I/O configuration is not known at design-time, or must be changed dynamically at run-time. Examples include:

  1. A machine builder who uses a single PLCnext Engineer project for multiple machine configurations, where the PLC program dynamically adapts itself based on the arrangement of local I/O modules detected.

  2. A PLCnext Control used as a general-purpose RTU, data logger, or multiplexer, where the I/O arrangement must be flexible.

  3. A custom PLCnext Control run-time written in any language (e.g. C/C++, rust, node.js, python) which requires flexible local I/O, but which does not want to manipulate .tic files. This can be used by applications like Sample Runtime so that PLCnext Engineer is no longer required for I/O configuration.

The source code for this app is freely available. Software developers who want to build this type of functionality into their own projects are free to use this app as a reference.

Note: The terms "Inline" and "Interbus" are used interchangeably in this document, since the Inline I/O system uses the Interbus communication protocol.

Background

On a PLCnext Control, local I/O can only be accessed through system components that are started as part of the plcnext process. The system components that handle local I/O - either Axioline or Inline - must be configured using TIC ("Technology Independent Configuration") files, which are XML files in a format defined by Phoenix Contact.

Currently the only practical method of generating a valid set of TIC files is by using PLCnext Engineer software, where the arrangement of local I/O modules must be configured manually. In the background, PLCnext Engineer generates TIC files for the specified hardware configuration, which are sent to the PLC with the PLCnext Engineer project.

Once on the PLC, TIC files are read during startup of the plcnext process. TIC files cannot be reloaded while the plcnext process is running.

This application demonstrates how to use a single set of TIC files to configure and re-configure the arrangement of local I/O modules that are connected to a PLC - without the need to manually create different I/O module arrangements in PLCnext Engineer.

Installation

Download the app from the PLCnext Store and install the "BusConductor" library on the host machine.

Building from source

The project can be built using the PLCnext CLI tool, either from the command-line or from Eclipse (with the PLCnext add-in). The SDK for AXC F 2152 firmware version 2019.3 is required.

When building from the command line, the following commands should be called in sequence from the project root directory:

plcncli generate code
plcncli generate config
plcncli build
plcncli generate library

Operation

The BusConductor library contains one component, called BcComponent. One instance of this component must be created by the user. The component includes one GDS port named "BusConductor", which is a structure containing the following fields:

Field name C++ Type Direction Description
CONFIG_REQ boolean input Requst to (re-)configure the local bus
CONFIG_MUST_MATCH boolean input Local bus configuration must match the user-specified configuration
START_IO_REQ boolean input Request to start local I/O exchange
CONFIGURED boolean output Local bus has been (re-)configured
NUM_MODULES uint16 output Total number of local I/O modules detected

The two REQ commands are processed on a rising edge. They both be set in sequence, and START_IO_REQ will not be processed if CONFIGURED is not TRUE.

If CONFIG_MUST_MATCH is TRUE, then the user must place a file named config.txt in the PLC directory /opt/plcnext/projects/BusConductor. This file contains the expected local I/O module arrangement, and is checked (if necessary) during the processing of the CONFIG_REQ command. If there is any mis-match detected between the contents of this file and the actual local I/O configuration, then CONFIGURED will remain FALSE, and the bus cannot be started. In this case, check the Output.log file on the PLC for error messages.

If CONFIG_MUST_MATCH is FALSE, then no configuration checking is done, and a config.txt file does not need to be provided.

The CONFIGURED output variable from the BusConductor component is latched, and is only reset on a rising edge of the CONFIG_REQ input. Once running, the real-time status of the local I/O bus should be monitored using the diagnostics variables provided by the PLCnext Control (refer to the "Local bus diagnostics" section below).

Once the local bus is running, process data can be exchanged with all local I/O modules using the GDS ports "Arp.Io.AxlC/0.DI4096" (inputs) and "Arp.Io.AxlC/0.DO4096" (outputs). Process data from each I/O module will appear in these two arrays in the same order that the modules appear on the local bus. The amount of process data for each I/O module can be obtained from the data sheet for that module.

Note that this app starts all I/O modules using the configuration that is stored in the module. Any changes to module-specific configuration (e.g. analog output channel configuration) must be done separately, using (for example) the PDI_WRITE function block in the PLCnext Controller library, or the Acyclic Communication RSC service, or the Startup+ configuration tool.

Quick start

This app is packaged as a PLCnext Engineer Library, but can be used without PLCnext Engineer. This quick-start covers both cases. Use of this app without PLCnext Engineer requires advanced knowledge of file-based configuration and operation of PLCnext Control components.

Quick Start using PLCnext Engineer

  • Create a new PLCnext Engineer project.

  • Keep the default local bus type (Axioline), or switch the local bus type to InLine.

  • Create a generic I/O configuration. In the PLCnext Engineer Components Search box, enter "AXL F physcial" (sic) for Axioline, or "IB IL 256" for Inline. Drag the generic I/O module from the Component library to the Axioline or Inline controller in the Project tree.

  • Create the following user-defined data types

    For Axioline I/O:

    TYPE
      ARR_LOCAL_IO : ARRAY [1..512] OF BYTE;
    END_TYPE
    

    For Inline I/O:

    TYPE
      ARR_LOCAL_IO : ARRAY [1..256] OF BYTE;
    END_TYPE
    
    

    For both Axioline and Inline I/O:

    TYPE
      BUS_CONDUCTOR       : STRUCT
        CONFIG_REQ        : BOOL;
        CONFIG_MUST_MATCH : BOOL;
        START_IO_REQ      : BOOL;
        CONFIGURED        : BOOL;
        NUM_MODULES       : UINT;
      END_STRUCT
    END_TYPE
    
  • Create a local IEC program in any language. In the variable table for that program, declare the following variables:

    Name Type Usage
    Field_Inputs ARR_LOCAL_IO IN Port
    Field_Outputs ARR_LOCAL_IO OUT Port
    BusConfig_Inputs BUS_CONDUCTOR IN Port
    BusConfig_Outputs BUS_CONDUCTOR OUT Port
  • In a Code sheet for the local IEC program, add the following logic:

    BusConfig_Outputs.CONFIGURED := BusConfig_Inputs.CONFIGURED;
    BusConfig_Outputs.NUM_MODULES := BusConfig_Inputs.NUM_MODULES;
    

    (This is a work-around for a current limitiation on Component Ports in PLCnext Engineer)

  • Create one instance of the local IEC program in a PLCnext Task.

  • In the PLCnext Port List, connect the Field_Inputs and Field_Outputs to the DO4096 and DI4096 ports on the generic I/O module.

  • Add the BusConductor user library to the PLCnext Engineer project.

  • Create one instance of the BcProgram program (from the BusConductor library) in a PLCnext Task.

  • In the PLCnext Port List, connect the ports BusConfig_Inputs and BusConfig_Outputs to the BusConductor port on BcComponent1.

  • Download the PLCnext Engineer project to the PLC and enter Debug mode.

  • Set the variable BusConfig_Outputs.CONFIG_MUST_MATCH to FALSE.

  • Set the variable BusConfig_Outputs.CONFIG_REQ to TRUE.

  • Check that the variable BusConfig_Inputs.CONFIGURED goes TRUE, and BusConfig_Inputs.NUM_MODULES is set to the total number of I/O modules on the local bus. The local bus is now configured and ready to exchange I/O data.

  • Set the variable BusConfig_Outputs.START_IO_REQ to TRUE.

  • Check that the local bus is running, using the standard diagnostics variables (described below). The local bus is now exchanging I/O data with the Field_Inputs and Field_Outputs variables.

Process Data from each I/O module is mapped to the Field_Inputs and Field_Outputs byte arrays. Check the documentation for each I/O module to see how many bytes of process data are provided by that module.

Quick Start without PLCnext Engineer

This example describes the use of Axioline I/O. A similar procedure is used to configure Inline I/O.

  • Using PuTTY on the host machine, log in to the PLC as admin.

  • On the PLC, create a new directory for this project, e.g.

    mkdir /opt/plcnext/projects/BusConductor
    
  • On the host machine, locate the file BusConductor.pcwlx that was installed with the app.

  • Unzip BusConductor.pcwlx using a tool like 7-Zip.

  • Locate the file libBusConductor.so in the sub-directory PROJECT\Logical%20Elements\AXCF2152_19.3.0. This is the shared object library containing the PLCnext Component that must be instantiated by the Automation Component Framework (ACF).

  • Using WinCSP, copy the shared object library libBusConductor.so from the host to the PLC directory /opt/plcnext/projects/BusConductor

  • Clone the Github repository and copy the file BusConductor.acf.config from the host to the PLC directory /opt/plcnext/projects/BusConductor The acf.config file instructs the ACF to load the shared object library and create one instance of the BusConductor component.

  • Check that the contents of the acf.config file are correct. For example, the path to the shared object library may need to be updated for your installation.

  • Copy the directory generic_axioline and all its contents from the host to the PLC directory /opt/plcnext/projects/BusConductor This directory contains the generic Axioline bus configuration, including a valid set of TIC files.

  • On the PLC, change the 'current' symlink to point to the new project directory.

    cd /opt/plcnext/projects
    rm current 
    ln -s BusConductor current
    

    This tells the PLCnext Control to use this as the default project, which will load the acf.config file and generic I/O configuration from this directory.

  • Restart the PLCnext runtime to create the BusConductor component.

  • If using the acf.config file in this example, the name of the BusConductor port in the Global Data Space will be "BcComponent1/BusConductor"

You must now send commands to the BcComponent instance from your own application via the Global Data Space. How this is done will be specific to each user application. For example, you can use a gds.config file to connect the BusConductor port to a GDS port in your own C++ project, or you can read and write GDS data by subscribing to the Data Access RSC Service in the PLC. In any case, be sure to include the following logic in your application:

BusConfig_Outputs.CONFIGURED = BusConfig_Inputs.CONFIGURED;
BusConfig_Outputs.NUM_MODULES = BusConfig_Inputs.NUM_MODULES;

(This is a work-around for a current limitiation on Component Ports in PLCnext Engineer)

Once the local bus is running, I/O data can be exchanged with a user application in a number of ways. Entries in a gds.config file can be used to connect I/O data to GDS ports in the user application, or the ANSI-C interface can be used to read and write I/O data.

An example of how to use the Data Access RSC Service (for GDS access) and the ANSI-C libraries (for I/O access) are given in the Sample Runtime example. This sample could be modified to use the BusConductor component to start the Axioline bus, which would eliminate the need to use PLCnext Engineer to generate a different I/O configuration for each specific arrangement of I/O modules.

Format of user confguration file - /opt/plcnext/projects/BusConductor/config.txt

If provided, this file must contain at least one line. Each line must contain a single integer in base 10 format. There must be no blank lines.

If the format of the config.txt file is not correct, or if there are differences between the expected and actual local I/O configurations, then these will be reported in the Output.log file in the PLC directory /opt/plcnext/logs

The numbers in the configuration file will be interpreted as follows:

Axioline

Line number(s) Meaning
1 Total number of I/O modules expected
2-5 Device Type for first I/O module
6-9 Device Type for second I/O module
10-13 Device Type for third I/O module
: :
: Device Type for last I/O module

Device Type is specified as a series of 8 bytes, unique for each type of local I/O module. These 8 bytes are represented in the config.txt file as 4 x 16 bit integers (in base 10 format) as follows:

Line number Device Type bytes
x MSB = byte 7, LSB = byte 6
x+1 MSB = byte 5, LSB = byte 4
x+2 MSB = byte 3, LSB = byte 2
x+3 MSB = byte 1, LSB = byte 0

The Device Type for each type of I/O module can be found in the data sheet for that module - search for the text "Device Type" or "DeviceType". For example, the data sheet for the Axioline module AXL F DI8/3 DO8/3 2H (part number 2702071) shows the device type as follows:

DeviceType table

... so for an Axioline bus with a single I/O module of this type, the contents of the config.txt file will be:

1
192
1
0
3330

Inline

Line number(s) Meaning
1 Total number of I/O modules expected
2 Length code & ID code for first I/O module
3 Length code & ID code for second I/O module
4 Length code & ID code for third I/O module
: :
: Length code & ID code for last I/O module

Length code & ID code is specified as a 16 bit integer in base 10 format. The most significant byte represents the Length code, and the least significant byte represents the ID code.

The Length code and ID code for each type of I/O module can be found in the data sheet for that module. For example, the data sheet for the Inline module IB IL 24 DI8/HD-PAC (part number 2700173) shows the Length code and ID code as follows:

Length and ID codes table

... so for an Inline bus with a single I/O module of this type, the contents of the config.txt file will be:

1
33214

... where 33214 is the decimal representation of 81BE (hex).

Local bus diagnostics

Once the local I/O bus is running, diagnostics are available from the following standard GDS OUT port variables.

Axioline

A description of each of the variables in the table below is given in the document "UM EN AXL F SYS DIAG", available for download from the Phoenix Contact website.

Port Name IEC Type
Arp.Io.AxlC/AXIO_DIAG_STATUS_REG_HI Bitstring8
Arp.Io.AxlC/AXIO_DIAG_STATUS_REG_LOW Bitstring8
Arp.Io.AxlC/AXIO_DIAG_STATUS_REG_PF BOOL
Arp.Io.AxlC/AXIO_DIAG_STATUS_REG_BUS BOOL
Arp.Io.AxlC/AXIO_DIAG_STATUS_REG_RUN BOOL
Arp.Io.AxlC/AXIO_DIAG_STATUS_REG_ACT BOOL
Arp.Io.AxlC/AXIO_DIAG_STATUS_REG_RDY BOOL
Arp.Io.AxlC/AXIO_DIAG_STATUS_REG_SYSFAIL BOOL
Arp.Io.AxlC/AXIO_DIAG_STATUS_REG_PW BOOL
Arp.Io.AxlC/AXIO_DIAG_PARAM_REG_HI Bitstring8
Arp.Io.AxlC/AXIO_DIAG_PARAM_REG_LOW Bitstring8
Arp.Io.AxlC/AXIO_DIAG_PARAM_2_REG_HI Bitstring8
Arp.Io.AxlC/AXIO_DIAG_PARAM_2_REG_LOW Bitstring8

Inline

A description of each of the variables in the table below is given in the document "IBS SYS DIAG DSC UM E", available for download from the Phoenix Contact website.

Port Name IEC Type
Arp.Io.IbM/IB_DIAG_STATUS_REG_HI Bitstring8
Arp.Io.IbM/IB_DIAG_STATUS_REG_LOW Bitstring8
Arp.Io.IbM/IB_DIAG_STATUS_REG_PF BOOL
Arp.Io.IbM/IB_DIAG_STATUS_REG_BUS BOOL
Arp.Io.IbM/IB_DIAG_STATUS_REG_RUN BOOL
Arp.Io.IbM/IB_DIAG_STATUS_REG_ACT BOOL
Arp.Io.IbM/IB_DIAG_STATUS_REG_RDY BOOL
Arp.Io.IbM/IB_DIAG_STATUS_REG_SYSFAIL BOOL
Arp.Io.IbM/IB_DIAG_STATUS_REG_WARN BOOL
Arp.Io.IbM/IB_DIAG_STATUS_REG_QUAL BOOL
Arp.Io.IbM/IB_DIAG_STATUS_REG_USER BOOL
Arp.Io.IbM/IB_DIAG_STATUS_REG_CTRL BOOL
Arp.Io.IbM/IB_DIAG_STATUS_REG_DTC BOOL
Arp.Io.IbM/IB_DIAG_PARAM_REG_HI Bitstring8
Arp.Io.IbM/IB_DIAG_PARAM_REG_LOW Bitstring8
Arp.Io.IbM/IB_DIAG_PARAM_2_REG_HI Bitstring8
Arp.Io.IbM/IB_DIAG_PARAM_2_REG_LOW Bitstring8

Restarting the local bus after error

Axioline

If there is an error on the local bus (e.g. missing I/O module), then the Axioline bus will restart automatically when the originally configured I/O module arrangement is detected. This allows for hot-swapping of faulty I/O modules, for example.

Inline

If there is an error on the local bus (e.g. missing I/O module), then the Inline bus can be restarted by resetting the START_IO_REQ flag, and then setting it again. In the case of persistent errors, this restart procedure could be repeated periodically until the error is cleared, or until a maximum number of restart attempts are made. These types of restart procedures will be specific to each application, so it is left to the user to implement this if needed.

Dynamically changing the local bus configuration

If the arrangement of I/O modules on the local bus is changed, the user can restart the local bus by resetting the CONFIG_REQ and START_IO_REQ flags, and then setting them again in sequence.

Changing the local I/O update rate

By default, I/O data is exhanged with local I/O modules every 50 ms. This can be changed, if required, using either PLCnext Engineer or (for applications that do not use PLCnext Engineer) by editing configuration files directly on the PLC:

Using PLCnext Engineer

  • In PLCnext Engineer, double-click on the local I/O bus controller (e.g. "Axioline F") in the Project pane, click on the Settings tab, and select the "Update task" menu item.
  • Select a task from the drop-down list. Data will be exchanged with local I/O modules every time this task is executed.
  • If no task is selected, the I/O update rate defaults to 50 ms.

Without PLCnext Engineer

  • In the esm.config file for your project, define a task that will be used to trigger local I/O updates.
  • On the PLC, open the following file in an editor: /opt/plcnext/projects/Default/Plc/Esm/Axio.esm.config
  • In this file, change the taskName in the TaskEvent entries from "Globals" to the name of your I/O update task.

Troubleshooting

If the BusConductor component appears not to be working, check the contents of the file /opt/plcnext/logs/Output.log, and look for entries from the component BusConductor.BcComponent. This can be done with the following command:

cat /opt/plcnext/logs/Output.log | grep BusConductor.BcComponent

How to get support

This app is supported in the forum of the PLCnext Community. Please raise an issue with a detailed error description and always provide a copy of the Output.log file.

Design notes

  • This project was developed entirely in Eclipse, using the PLCnext CLI project template and the configuration/build process provided by the PLCnext Add-In for Eclipse. The current version of the PLCnext CLI (2019.0) provides limited support for the Component Ports feature of the PLCnext Control firmware, and more Component Port features could be utilised by moving away from the PLCnext CLI project template and build process.

  • This app is designed to be used in PLCnext Engineer, but also be useable by other C++ components. Note that the current version of PLCnext Engineer (2019.3) provides limited support for the "Component Ports" feature of the PLCnext Control firmware, and no support for component-only libraries. This project includes some features that work around these limitiations - for example, the only purpose of the program BcProgram in the BusConductor library is to force PLCnext Engineer to instantiate BcComponent, which would otherwise not be instantiated by PLCnext Engineer.

  • For software developers who would like to reproduce the functions of this app in their own IEC 61131 (PLCnext Engineer) project, use the AX_CONTROL and/or IB_CONTROL_NEXT function blocks to access the Axioline Master and Interbus Master RSC services respectively. These FBs are included in the PLCnext Controller library that comes with PLCnext Engineer.