esphome:
name: "sdm"
friendly_name: "SDM120M ModBus Energy meter"
esp8266:
board: esp01_1m
logger:
baud_rate: 0
api:
ota:
wifi:
ssid: !secret wifi_ssid
password: !secret wifi_password
ap:
captive_portal:
uart:
tx_pin: 1
rx_pin: 3
baud_rate: 9600
parity: NONE
modbus:
flow_control_pin: 2
id: modbus1
modbus_controller:
- id: sdm
address: 1
modbus_id: modbus1
setup_priority: -10
sensor:
- platform: modbus_controller
modbus_controller_id: sdm
name: "Voltage"
id: "voltage"
register_type: read
address: 0x0000
value_type: FP32
accuracy_decimals: 2
unit_of_measurement: "V"
state_class: measurement
device_class: voltage
- platform: modbus_controller
modbus_controller_id: sdm
name: "Current"
id: "current"
register_type: read
address: 0x0006
value_type: FP32
accuracy_decimals: 2
unit_of_measurement: "A"
state_class: measurement
device_class: current
- platform: modbus_controller
modbus_controller_id: sdm
name: "Power"
id: "power"
register_type: read
address: 0x000C
value_type: FP32
accuracy_decimals: 2
unit_of_measurement: "W"
state_class: measurement
device_class: power
- platform: modbus_controller
modbus_controller_id: sdm
name: "Energy"
id: "energy"
register_type: read
address: 0x0156
value_type: FP32
accuracy_decimals: 2
unit_of_measurement: "kWh"
state_class: total
device_class: energy