No description, website, or topics provided.
Switch branches/tags
Nothing to show
Clone or download
Fetching latest commit…
Cannot retrieve the latest commit at this time.
Permalink
Failed to load latest commit information.
doc/EMC
src
LICENSE
README.md
andino-ups-small.png
backup-time.png
block.png
states.png
states1.png
wiring.png

README.md

Andino-UPS

Andino UPS, a Uninterruptible Power Supply for 24 Volt DC Client Devices. It stores the Energy in long lasting Supercaps instead of Lead- or Lithium Batteries. Depending on the environment temperature, the livetime are up to 10 years without any maintance.

Homepage of Andino UPS

Andino UPS at the Clear Systems Shop

More details about the mode of operation of the Firmware and how to configure are here


Andino X2 - Raspberry Pi on DIN Rail

Overview

This UPS is designed for industrial PLC and other devices powered with 24 V DC. It is intended to allow the client device to bridge over short voltage drops and, in the event of a prolonged power failure, to shut down in a controlled manner.

Thus, the controlled device can close databases, connections and synchronize the file system without the risk of data loss.

The Andino UPS has an 24V DC Input and a 24V DC Output. This reduce the Energy loos for the conversion to mains power and backwards.

The UPS can deliver up to 10 Watts or 0,4 Ampere at 24 Volts.

Wiring

Andino UPS - Wiring

Backup times

Depending on the Load the backup times are:

Load Time
2 Watt 3 min 30 sec
4 Watt 1 min 12 sec
10 Watt 39 sec

In all cases, hopefully enough time to shut down the client PLC.

Andino UPS - Backup times

Shutdown - Power return and Bridge Mode

If the Charge Level is above the "Good" Level (witch is default 80% and you can change) the Client will not informed of the Power Fail. If the Power returns within this time, the gap is bridged.

State Machine up-down

If the Power returns after the Client is informed, the UPS will wait until the Charge Level is again above the good Level and give the Client time to Shut down (HYST-Timer). After that the Power of the Client will be shut down (DOWN Timer) and switched on again so that the client can restart.

State Machine up-down-up again

EMC Tests

The Andino UPS has been extensively tested for its electromagnetic compatibility (EMC).

The tests were based on the immunity to electrostatic discharge, high-frequency electromagnetic fields, fast transient electrical disturbances (burst), impulse voltages, conducted disturbances – induced by high-frequency fields and magnetic fields with energy-related frequencies.

The tested standards in detail

Radiated field strength / conducted emissions
DIN EN 55022: 2011 according to VDE 0875 part 22 of 12.2011
Störaussendung: Klasse B (Wohnbereich) (strengere Grenzwerte) 
Störfestigkeit: Klasse A (Industriebereich) herangezogen. (höhere Einstrahlung)

Immunity ESD
DIN EN 61000-4-2: 2009 according to VDE 0847 part 4-2 of 12.2009

Immunity radiated electromagnetic fields
DIN EN 61000-4-3: 2006+A1:2008+ A2: 2010 according to VDE 0847 part 4-3 of 04.2011

Immunity Burst
DIN EN 61000-4-4: 2012 according to VDE 0847 part 4-4 of 04.2013

Immunity Surge
DIN EN 61000-4-5: 1995 +A1: 2014 according to VDE 0847 part 4-5 of 03.2015

Immunity high frequent uncoupled emission
DIN EN 61000-4-6: 2014 according to VDE 0847 part 4-6 of 08.2014

Immunity magnetic fields
DIN EN 61000-4-8: 2010 according to VDE 0847 part 4-8 of 11.2010

Block diagram

Andino UPS - Wiring

For more details please see here

A Description of the internal charge and power controller see here