From 76f10e942071f769e6fc7878c8df18db7f80dca0 Mon Sep 17 00:00:00 2001 From: AntoineGautier Date: Fri, 10 Jul 2020 02:50:07 -0700 Subject: [PATCH 1/2] Add revision notes and restore default gains for generic control blocks --- .../G36_PR1/AHUs/MultiZone/VAV/Controller.mo | 8 +++++++- .../AHUs/MultiZone/VAV/Economizers/Controller.mo | 8 +++++++- .../VAV/Economizers/Subsequences/Limits.mo | 9 ++++++++- Buildings/Examples/VAVReheat/ASHRAE2006.mo | 14 ++++++++------ .../VAVReheat/BaseClasses/PartialOpenLoop.mo | 6 ++++++ .../Examples/VAVReheat/Controls/Economizer.mo | 9 +++++++++ .../Controls/EconomizerTemperatureControl.mo | 6 ++++++ Buildings/Examples/VAVReheat/Guideline36.mo | 7 +++++++ 8 files changed, 58 insertions(+), 9 deletions(-) diff --git a/Buildings/Controls/OBC/ASHRAE/G36_PR1/AHUs/MultiZone/VAV/Controller.mo b/Buildings/Controls/OBC/ASHRAE/G36_PR1/AHUs/MultiZone/VAV/Controller.mo index 3b40827bb3f..8d45858c766 100644 --- a/Buildings/Controls/OBC/ASHRAE/G36_PR1/AHUs/MultiZone/VAV/Controller.mo +++ b/Buildings/Controls/OBC/ASHRAE/G36_PR1/AHUs/MultiZone/VAV/Controller.mo @@ -76,7 +76,7 @@ block Controller "Type of controller" annotation (Dialog(group="Economizer PID controller")); - parameter Real kMinOut(final unit="1")=0.03 + parameter Real kMinOut(final unit="1")=0.05 "Gain of controller for minimum outdoor air intake" annotation (Dialog(group="Economizer PID controller")); @@ -998,6 +998,12 @@ Buildings.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.SetPoints.SupplySignals revisions="