Skip to content
Permalink
Branch: master
Find file Copy path
Find file Copy path
Fetching contributors…
Cannot retrieve contributors at this time
executable file 47 lines (37 sloc) 1.65 KB

check_snmp_apc_ups.py


Check state of a Schneider APC UPS: The plugin checks various characteristics of an APC UPS. It gets an SNMP value according to the defined check type and compares the returned value against the set thresholds.

Checkable values:

  • input voltage, frequency
  • output voltage, current, power, load
  • remaining runtime
  • remaining battery capacity
  • battery state
  • environmental temperature

Tested device: None. Just simulated with a snmpwalk of a "Smart-UPS RT 3000 XL"

Example:

Check Input Voltage

./check_snmp_apc_ups.py -H 172.29.1.2 -t INPUT_VOLTAGE -w 228:232 -c 226:234

=>

Critical - Input Voltage is 114 VAC | 'INPUT_VOLTAGE'=114VAC;228:232;226:234;;

Parameters

Options:
 -h, --help            show this help message and exit
 -H HOSTNAME           Hostname or ip address
 -C COMMUNITY, --community=COMMUNITY
                       SNMP community of the SNMP service on target host.
 -V VERSION, --snmpversion=VERSION
                       SNMP version. (1 or 2)
 -t CHECKTYPE          The value you want to monitor 
                       One out of BASIC_BATTERY_STATUS, TIME_ON_BATTERY,
                       BATTERY_CAPACITY, INTERNAL_TEMPERATURE,
                       RUNTIME_REMAINING, BATTERY_REPLACE_INDICATOR,
                       INPUT_VOLTAGE, INPUT_FREQUENCY, OUTPUT_VOLTAGE,
                       OUTPUT_LOAD, OUTPUT_CURRENT, OUTPUT_POWER,
                       LAST_TEST_RESULT, ENVIRONMENT_TEMPERATURE
 -w WARNING_THRESHOLDS Thresholds in icinga threshold range syntax
 -c CRITICAL_THRESHOLDS Thresholds in icinga threshold syntax