Template for monitoring APC Smart-UPS SNMP v1 by uninterruptible power supplies.

Data elements:

APC Smart UPS - Ampers .1.3.6.1.4.1.318.1.1.1.4.2.4.0 APC Smart UPS - Battery Capacity .1.3.6.1.4.1.318.1.1.1.2.2.1.0 APC Smart UPS - Battery Temp .1.3.6.1.4.1.318.1.1.1.2.2.2.0 APC Smart UPS - Environment Temp .1.3.6.1.4.1.318.1.1.10.2.3.2.1.4.1 APC Smart UPS - Input Frequency .1.3.6.1.4.1.318.1.1.1.3.2.4.0 APC Smart UPS - Input Voltage .1.3.6.1.4.1.318.1.1.1.3.2.1.0 APC Smart UPS - Load .1.3.6.1.4.1.318.1.1.1.4.2.3.0 APC Smart UPS - On Battery .1.3.6.1.4.1.318.1.1.1.2.1.2.0 APC Smart UPS - Output Frequency .1.3.6.1.4.1.318.1.1.1.4.2.2.0 APC Smart UPS - Output Voltage .1.3.6.1.4.1.318.1.1.1.4.2.1.0 APC Smart UPS - Runtime .1.3.6.1.4.1.318.1.1.1.2.2.3.0

http://support.ipmonitor.com/tutorials/1b349d0e187f4746807ae10eda7fe2c8.aspx APC Smart UPS - Basic Output Status (On-line) .1.3.6.1.4.1.318.1.1.1.4.1.1.0 APC Smart UPS - Battery Status .1.3.6.1.4.1.318.1.1.1.2.1.1.0 APC Smart UPS - Replace Battery .1.3.6.1.4.1.318.1.1.1.2.2.4.0

For correct operation of the pattern, it is recommended to add the conversion values: "Administration -> General -> Convert values"

PC Battery Replacement Status: 1 unknown 2 notInstalled 3 ok 4 failed 5 highTemperature 6 replaceImmediately 7 lowCapacity

APC Battery Status: 1 unknown 2 batteryNormal 3 batteryLow