Starting with WinCC OA Version 3.20, developers can leverage Node.js and JavaScript to implement business logic within the WinCC OA environment. This functionality is enabled by integrating the Node.js runtime with native connectivity to WinCC OA features, offering a powerful and flexible platform for creating custom automation solutions.
This open-source Java library serves as a wrapper for WinCC OA's Node.js functions, providing a seamless way to write business logic in Java while maintaining direct access to WinCC OA's capabilities through Node.js.
By utilizing the GraalVM Node.js runtime, this integration enables the creation of solutions for WinCC OA that leverage the power of Java and its extensive library ecosystem, alongside the flexibility of JavaScript.
Please be aware that the GraalVM Node.js Runtime is not officially supported by WinCC Open Architecture.
-
Download and Extract GraalVM Node.js Runtime
Download the GraalVM Node.js Runtime from this link and unzip it to a directory. In this example, we extracted it toC:\Tools\graalnodejs-community-jvm-24.0.1-windows-amd64. Make sure to download the correct file, which is named graalnodejs and also has "jvm" in the name (Windows version). After extraction, set thePATHvariable to point to the bin directory of the extracted files:set PATH="C:\Tools\graalnodejs-community-24.0.1-windows-amd64\bin";%PATH%
-
Create a WinCC OA Project
Create a new WinCC OA project. In this example, we will name the projectTest320. -
Copy the Files from this GIT Repository
Copy thewinccoa-graalvmdirectory into thejavascriptdirectory within your project directory (C:\WinCC_OA_Proj\Test320\javascript\winccoa-graalvm). -
Install Node.js Dependencies
Navigate to the Node.js directory and install the required dependencies using npm:cd C:\WinCC_OA_Proj\Test320\javascript\winccoa-graalvm\nodejs npm install
-
Build the Java Project
Open a terminal (with thePATHvariable set to the GraalVM Node.js Runtime) and navigate to the Java directory. Then, build the project using Gradle (make sure Gradle is installed):cd C:\WinCC_OA_Proj\Test320\javascript\winccoa-graalvm\java gradlew build
-
Start the MQTT Server
You can now start the MQTT Server example by runningstartMqtt.bat. If everything is set up correctly, the manager should start and connect to WinCC OA. The server will now host a simple MQTT server interface on port 1883. You can use any MQTT client to subscribe to WinCC OA datapoints, such asExampleDP_Arg1.Note: The provided MQTT server is a basic implementation and not a fully compliant MQTT server.
CREATE OR REPLACE SCHEMA scada;
CREATE TABLE IF NOT EXISTS scada.scada (
system character varying(1000) NOT NULL,
datapoint character varying(1000) NOT NULL,
sourcetime timestamp with time zone NOT NULL,
servertime timestamp with time zone NOT NULL,
numericvalue numeric,
stringvalue text,
status character varying(30),
CONSTRAINT scada_pk PRIMARY KEY (system, datapoint, sourcetime)
);
Generate key: https://docs.snowflake.com/en/user-guide/key-pair-auth
openssl genrsa 2048 | openssl pkcs8 -topk8 -v2 des3 -inform PEM -out snowflake.p8 -nocrypt
openssl rsa -in snowflake.p8 -pubout -out snowflake.pub
ALTER USER xxxxxx SET RSA_PUBLIC_KEY='MIIBIjANBgkqh...'; -- Replace this with your public key from the snowflake.pub file (without -----BEGIN PRIVATE KEY----- and without -----END PRIVATE KEY-----)
Copy snowflake-template.json to snowflake.json and set your connection settings and your scada query.
cd C:\WinCC_OA_Proj\Test320\javascript\winccoa-graalvm\java