diff --git a/rdflib/namespace/_BRICK.ttl b/rdflib/namespace/_BRICK.ttl new file mode 100644 index 000000000..ddf0bed0b --- /dev/null +++ b/rdflib/namespace/_BRICK.ttl @@ -0,0 +1,1219 @@ + +class BRICK(DefinedNamespace): + """ + Generated from: https://github.com/BrickSchema/Brick/releases/download/nightly/Brick.ttl + Date: 2021-09-22T09:59:11 + """ + + # http://www.w3.org/2002/07/owl#Class + Class: URIRef # + Point: URIRef # + Status: URIRef # A Status is input point that reports the current operating mode, state, position, or condition of an item. Statuses are observations and should be considered 'read-only' + Emergency_Push_Button_Status: URIRef # Indicates if an emergency button has been pushed + Enable_Status: URIRef # Indicates if a system or piece of functionality has been enabled + Heat_Exchanger_System_Enable_Status: URIRef # Indicates if the heat exchanger system has been enabled + Availability_Status: URIRef # Indicates if a piece of equipment, system, or functionality is available for operation + Pressure_Status: URIRef # Indicates if pressure is within expected bounds + Discharge_Air_Duct_Pressure_Status: URIRef # Indicates if air pressure in discharge duct is within expected bounds + Differential_Pressure_Load_Shed_Status: URIRef # + Hot_Water_Differential_Pressure_Load_Shed_Status: URIRef # + Hot_Water_Differential_Pressure_Load_Shed_Reset_Status: URIRef # + Chilled_Water_Differential_Pressure_Load_Shed_Status: URIRef # + Chilled_Water_Differential_Pressure_Load_Shed_Reset_Status: URIRef # + Medium_Temperature_Hot_Water_Differential_Pressure_Load_Shed_Status: URIRef # + Medium_Temperature_Hot_Water_Differential_Pressure_Load_Shed_Reset_Status: URIRef # + Supply_Air_Duct_Pressure_Status: URIRef # Indicates if air pressure in supply duct is within expected bounds + Hold_Status: URIRef # + Drive_Ready_Status: URIRef # Indicates if a hard drive or other storage device is ready to be used, e.g. in the context of RAID + Speed_Status: URIRef # Indicates the operating speed of a device or equipment, e.g. fan + Load_Shed_Status: URIRef # Indicates if a load shedding policy is in effect + Hot_Water_Supply_Temperature_Load_Shed_Status: URIRef # + Medium_Temperature_Hot_Water_Supply_Temperature_Load_Shed_Status: URIRef # + Hot_Water_Discharge_Temperature_Load_Shed_Status: URIRef # + Direction_Status: URIRef # Indicates which direction a device is operating in + Motor_Direction_Status: URIRef # Indicates which direction a motor is operating in, e.g. forward or reverse + Disable_Status: URIRef # Indicates if functionality has been disabled + Fan_Status: URIRef # Indicates properties of fans + Fan_On_Off_Status: URIRef # + Mode_Status: URIRef # Indicates which mode a system, device or control loop is currently in + Operating_Mode_Status: URIRef # Indicates the current operating mode of a system, device or control loop + Vent_Operating_Mode_Status: URIRef # Indicates the current operating mode of a vent + Occupied_Mode_Status: URIRef # Indicates if a system, device or control loop is in "Occupied" mode + Off_Status: URIRef # Indicates if a control loop, relay or equipment is off + Overridden_Off_Status: URIRef # Indicates if a control loop, relay or equipment has been turned off when it would otherwise be scheduled to be on + On_Off_Status: URIRef # Indicates the on/off status of a control loop, relay or equipment + Motor_On_Off_Status: URIRef # + Locally_On_Off_Status: URIRef # + Remotely_On_Off_Status: URIRef # + Standby_Unit_On_Off_Status: URIRef # Indicates the on/off status of a standby unit + Standby_Glycool_Unit_On_Off_Status: URIRef # Indicates the on/off status of a standby glycool unit + Start_Stop_Status: URIRef # Indicates the active/inactive status of a control loop (but not equipment activities or relays -- use On/Off for this purpose) + Dehumidification_Start_Stop_Status: URIRef # + Heating_Start_Stop_Status: URIRef # + Cooling_Start_Stop_Status: URIRef # + Humidification_Start_Stop_Status: URIRef # + Run_Status: URIRef # + Run_Request_Status: URIRef # Indicates if a request has been filed to start a device or equipment + EconCycle_Start_Stop_Status: URIRef # + Pump_On_Off_Status: URIRef # + Emergency_Power_Off_System_Status: URIRef # + Emergency_Power_Off_System_Activated_By_Leak_Detection_System_Status: URIRef # + Emergency_Power_Off_System_Activated_By_High_Temperature_Status: URIRef # + On_Status: URIRef # Indicates if a control loop, relay or equipment is on + Overridden_On_Status: URIRef # Indicates if a control loop, relay or equipment has been turned on when it would otherwise be scheduled to be off + Occupancy_Status: URIRef # Indicates if a room or space is occupied + Temporary_Occupancy_Status: URIRef # For systems that differentiate between scheduled occupied/unoccupied mode, this indicates if a space is temporarily occupied when it would otherwise be unoccupied + Freeze_Status: URIRef # Indicates if a substance contained within a vessel has frozen + Fault_Status: URIRef # Indicates the presence of a fault in a device, system or control loop + Humidifier_Fault_Status: URIRef # Indicates the presence of a fault in a humidifier + Last_Fault_Code_Status: URIRef # Indicates the last fault code that occurred + Overridden_Status: URIRef # Indicates if the expected operating status of an equipment or control loop has been overridden + Even_Month_Status: URIRef # + System_Status: URIRef # Indicates properties of the activity of a system + System_Shutdown_Status: URIRef # Indicates if a system has been shutdown + Emergency_Air_Flow_System_Status: URIRef # + Emergency_Generator_Status: URIRef # Indicates if an emergency generator is active + Filter_Status: URIRef # Indicates if a filter needs to be replaced + Pre_Filter_Status: URIRef # Indicates if a prefilter needs to be replaced + Stages_Status: URIRef # Indicates which stage a control loop or equipment is in + Lead_Lag_Status: URIRef # Indicates if lead/lag operation is enabled + Lockout_Status: URIRef # Indicates if a piece of equipment, system, or functionality has been locked out from operation + Open_Close_Status: URIRef # Indicates the open/close status of a device such as a damper or valve + Manual_Auto_Status: URIRef # Indicates if a system is under manual or automatic operation + Sensor: URIRef # A Sensor is an input point that represents the value of a device or instrument designed to detect and measure a variable (ASHRAE Dictionary). + Motion_Sensor: URIRef # Detects the presence of motion in some area + PIR_Sensor: URIRef # Detects the presense of motion in some area using the differential change in infrared intensity between two or more receptors + Angle_Sensor: URIRef # Measues the planar angle of some phenomenon + Solar_Zenith_Angle_Sensor: URIRef # Measures the zenith angle of the sun + Solar_Azimuth_Angle_Sensor: URIRef # Measures the azimuth angle of the sun + Humidity_Sensor: URIRef # Measures the concentration of water vapor in air + Relative_Humidity_Sensor: URIRef # Measures the present state of absolute humidity relative to a maximum humidity given the same temperature + Outside_Air_Humidity_Sensor: URIRef # Measures the relative humidity of outside air + Supply_Air_Humidity_Sensor: URIRef # Measures the relative humidity of supply air + Zone_Air_Humidity_Sensor: URIRef # Measures the relative humidity of zone air + Return_Air_Humidity_Sensor: URIRef # Measures the relative humidity of return air + Exhaust_Air_Humidity_Sensor: URIRef # Measures the relative humidity of exhaust air + Mixed_Air_Humidity_Sensor: URIRef # Measures the humidity of mixed air + Discharge_Air_Humidity_Sensor: URIRef # Measures the relative humidity of discharge air + Heat_Sensor: URIRef # Measures heat + Trace_Heat_Sensor: URIRef # Measures the surface temperature of pipelines carrying temperature-sensitive products; typically used to avoid frosting/freezing + Water_Level_Sensor: URIRef # Measures the height/level of water in some container + Deionised_Water_Level_Sensor: URIRef # Measures the height/level of deionised water in some container + Collection_Basin_Water_Level_Sensor: URIRef # Measures the level of the water in the collection basin, e.g. within a Cooling_Tower + Torque_Sensor: URIRef # Measures torque, the tendency of a force to rotate an object about some axis + Motor_Torque_Sensor: URIRef # Measures the torque, or rotating power, of a motor + Dewpoint_Sensor: URIRef # Senses the dewpoint temperature . Dew point is the temperature to which air must be cooled to become saturated with water vapor + Discharge_Air_Dewpoint_Sensor: URIRef # Measures dewpoint of discharge air + Outside_Air_Dewpoint_Sensor: URIRef # Senses the dewpoint temperature of outside air + Exhaust_Air_Dewpoint_Sensor: URIRef # Measures dewpoint of exhaust air + Zone_Air_Dewpoint_Sensor: URIRef # Measures dewpoint of zone air + Return_Air_Dewpoint_Sensor: URIRef # Senses the dewpoint temperature of return air + Voltage_Sensor: URIRef # Measures the voltage of an electrical device or object + Battery_Voltage_Sensor: URIRef # Measures the capacity of a battery + DC_Bus_Voltage_Sensor: URIRef # Measures the voltage across a DC bus + Output_Voltage_Sensor: URIRef # Measures the voltage output by some process or device + Position_Sensor: URIRef # Measures the current position of a component in terms of a fraction of its full range of motion + Sash_Position_Sensor: URIRef # Measures the current position of a sash in terms of the percent of fully open + Damper_Position_Sensor: URIRef # Measures the current position of a damper in terms of the percent of fully open + Valve_Position_Sensor: URIRef # Measures the current position of a valve in terms of the percent of fully open + Hail_Sensor: URIRef # Measures hail in terms of its size and damage potential + Direction_Sensor: URIRef # Measures the direction in degrees in which a phenomenon is occuring + Wind_Direction_Sensor: URIRef # Measures the direction of wind in degrees relative to North + Energy_Sensor: URIRef # Measures energy consumption + Energy_Usage_Sensor: URIRef # Measures the total amount of energy used over some period of time + Current_Sensor: URIRef # Senses the amperes of electrical current passing through the sensor + Current_Output_Sensor: URIRef # Senses the amperes of electrical current produced as output by a device + Photovoltaic_Current_Output_Sensor: URIRef # Senses the amperes of electrical current produced as output by a photovoltaic device + PV_Current_Output_Sensor: URIRef # See Photovoltaic_Current_Output_Sensor + Motor_Current_Sensor: URIRef # Measures the current consumed by a motor + Load_Current_Sensor: URIRef # Measures the current consumed by a load + Rain_Sensor: URIRef # Measures the amount of precipitation fallen + Rain_Duration_Sensor: URIRef # Measures the duration of precipitation within some time frame + Solar_Radiance_Sensor: URIRef # The amount of light that passes through or is emitted from the sun and falls within a given solid angle in a specified direction + Occupancy_Sensor: URIRef # Detects occupancy of some space or area + Power_Sensor: URIRef # Measures the amount of instantaneous power consumed + Thermal_Power_Sensor: URIRef # + Heating_Thermal_Power_Sensor: URIRef # + Electrical_Power_Sensor: URIRef # Measures the amount of instantaneous electric power consumed + Active_Power_Sensor: URIRef # Measures the portion of power that, averaged over a complete cycle of the AC waveform, results in net transfer of energy in one direction + Peak_Power_Demand_Sensor: URIRef # The peak power consumed by a process over some period of time + Reactive_Power_Sensor: URIRef # Measures the portion of power that, averaged over a complete cycle of the AC waveform, is due to stored energy which returns to the source in each cycle + Imbalance_Sensor: URIRef # A sensor which measures difference (imbalance) between phases of an electrical system + Current_Imbalance_Sensor: URIRef # A sensor which measures the current difference (imbalance) between phases of an electrical system + Voltage_Imbalance_Sensor: URIRef # A sensor which measures the voltage difference (imbalance) between phases of an electrical system + Pressure_Sensor: URIRef # Measure the amount of force acting on a unit area + Static_Pressure_Sensor: URIRef # Measures resistance to airflow in a heating and cooling system's components and duct work + Supply_Air_Static_Pressure_Sensor: URIRef # The static pressure of air within supply regions of an HVAC system + Discharge_Air_Static_Pressure_Sensor: URIRef # The static pressure of air within discharge regions of an HVAC system + Exhaust_Air_Static_Pressure_Sensor: URIRef # The static pressure of air within exhaust regions of an HVAC system + Lowest_Exhaust_Air_Static_Pressure_Sensor: URIRef # The lowest observed static pressure of air in exhaust regions of an HVAC system over some period of time + Average_Exhaust_Air_Static_Pressure_Sensor: URIRef # The computed average static pressure of air in exhaust regions of an HVAC system over some period of time + Underfloor_Air_Plenum_Static_Pressure_Sensor: URIRef # Measures the outward push of air against the plenum surfaces and used to measure the resistance when air moves through the plenum + Building_Air_Static_Pressure_Sensor: URIRef # The static pressure of air within a building + Differential_Pressure_Sensor: URIRef # Measures the difference between two applied pressures + Chilled_Water_Differential_Pressure_Sensor: URIRef # Measures the difference in water pressure on either side of a chilled water valve + Hot_Water_Differential_Pressure_Sensor: URIRef # Measures the difference in water pressure on either side of a hot water valve + Medium_Temperature_Hot_Water_Differential_Pressure_Sensor: URIRef # Measures the difference in water pressure between sections of a medium temperature hot water system + Filter_Differential_Pressure_Sensor: URIRef # Measures the difference in pressure on either side of a filter + Air_Differential_Pressure_Sensor: URIRef # Measures the difference in pressure between two regions of air + Return_Air_Differential_Pressure_Sensor: URIRef # Measures the difference in pressure between the return and supply side + Supply_Air_Differential_Pressure_Sensor: URIRef # Measures the difference in pressure between an upstream and downstream of an air duct or other air conduit used to supply air into the building + Exhaust_Air_Differential_Pressure_Sensor: URIRef # Measures the difference in pressure between an upstream and downstream of an air duct or other air conduit used to exhaust air from the building + Velocity_Pressure_Sensor: URIRef # Measures the difference between total pressure and static pressure + Supply_Air_Velocity_Pressure_Sensor: URIRef # + Discharge_Air_Velocity_Pressure_Sensor: URIRef # + Exhaust_Air_Velocity_Pressure_Sensor: URIRef # + Speed_Sensor: URIRef # Measures the magnitude of velocity of some form of movement + Wind_Speed_Sensor: URIRef # Measured speed of wind, caused by air moving from high to low pressure + Motor_Speed_Sensor: URIRef # + Differential_Speed_Sensor: URIRef # + Frost_Sensor: URIRef # Senses the presence of frost or conditions that may cause frost + Enthalpy_Sensor: URIRef # Measures the total heat content of some substance + Air_Enthalpy_Sensor: URIRef # Measures the total heat content of air + Outside_Air_Enthalpy_Sensor: URIRef # Measures the total heat content of outside air + Return_Air_Enthalpy_Sensor: URIRef # Measures the total heat content of return air + Frequency_Sensor: URIRef # Measures the frequency of a phenomenon or aspect of a phenomenon, e.g. the frequency of a fan turning + Output_Frequency_Sensor: URIRef # + Usage_Sensor: URIRef # Measures the amount of some substance that is consumed or used, over some period of time + Steam_Usage_Sensor: URIRef # Measures the amount of steam that is consumed or used, over some period of time + Water_Usage_Sensor: URIRef # Measures the amount of water that is consumed, over some period of time + Hot_Water_Usage_Sensor: URIRef # Measures the amount of hot water that is consumed, over some period of time + Contact_Sensor: URIRef # Senses or detects contact, such as for determining if a door is closed. + Flow_Sensor: URIRef # Measures the rate of flow of some substance + Water_Flow_Sensor: URIRef # Measures the rate of flow of water + Bypass_Water_Flow_Sensor: URIRef # Measures the rate of flow of bypass water + Return_Water_Flow_Sensor: URIRef # + Chilled_Water_Return_Flow_Sensor: URIRef # Measures the rate of flow of chilled return water + Hot_Water_Return_Flow_Sensor: URIRef # Measures the rate of flow of hot return water + Return_Condenser_Water_Flow_Sensor: URIRef # Measures the flow of the return condenser water + Discharge_Water_Flow_Sensor: URIRef # Measures the rate of flow of discharge water + Hot_Water_Discharge_Flow_Sensor: URIRef # Measures the rate of flow of hot discharge water + Chilled_Water_Discharge_Flow_Sensor: URIRef # Measures the rate of flow of chilled discharge water + Chilled_Water_Flow_Sensor: URIRef # Measures the rate of flow in a chilled water circuit + Chilled_Water_Supply_Flow_Sensor: URIRef # Measures the rate of flow of chilled supply water + Supply_Water_Flow_Sensor: URIRef # Measures the rate of flow of hot supply water + Hot_Water_Supply_Flow_Sensor: URIRef # Measures the rate of flow of hot supply water + Supply_Condenser_Water_Flow_Sensor: URIRef # Measures the flow of the supply condenser water + Leaving_Water_Flow_Sensor: URIRef # Measures the rate of flow of water that is leaving a piece of equipment or system + Hot_Water_Flow_Sensor: URIRef # Measures the rate of flow of hot water + Hot_Water_Flow_Sensor: URIRef # Measures the rate of flow in a hot water circuit + Entering_Water_Flow_Sensor: URIRef # Measures the rate of flow of water entering a piece of equipment or system + Air_Flow_Sensor: URIRef # Measures the rate of flow of air + Fume_Hood_Air_Flow_Sensor: URIRef # Measures the rate of flow of air in a fume hood + Return_Air_Flow_Sensor: URIRef # Measures the rate of flow of return air + Bypass_Air_Flow_Sensor: URIRef # Measures the rate of flow of bypass air + Exhaust_Air_Flow_Sensor: URIRef # Measures the rate of flow of exhaust air + Exhaust_Air_Stack_Flow_Sensor: URIRef # Measures the rate of flow of air in the exhaust air stack + Discharge_Air_Flow_Sensor: URIRef # Measures the rate of flow of discharge air + Average_Discharge_Air_Flow_Sensor: URIRef # The computed average flow of discharge air over some interval + Outside_Air_Flow_Sensor: URIRef # Measures the rate of flow of outside air into the system + Mixed_Air_Flow_Sensor: URIRef # Measures the rate of flow of mixed air + Supply_Air_Flow_Sensor: URIRef # Measures the rate of flow of supply air + Average_Supply_Air_Flow_Sensor: URIRef # The computed average flow of supply air over some interval + Duration_Sensor: URIRef # Measures the duration of a phenomenon or event + On_Timer_Sensor: URIRef # Measures the duration for which a device was in an active or "on" state + Run_Time_Sensor: URIRef # Measures the duration for which a device was in an active or "on" state + Illuminance_Sensor: URIRef # Measures the total luminous flux incident on a surface, per unit area + Outside_Illuminance_Sensor: URIRef # Measures the total luminous flux incident on an outside, per unit area + Fire_Sensor: URIRef # Measures the presence of fire + Adjust_Sensor: URIRef # Measures user-provided adjustment of some value + Warm_Cool_Adjust_Sensor: URIRef # User provided adjustment of zone temperature, typically in the range of +/- 5 degrees + Temperature_Sensor: URIRef # Measures temperature: the physical property of matter that quantitatively expresses the common notions of hot and cold + Water_Temperature_Sensor: URIRef # Measures the temperature of water + Condenser_Water_Temperature_Sensor: URIRef # Measures the temperature of condenser water + Return_Condenser_Water_Temperature_Sensor: URIRef # Measures the temperature of the return condenser water + Supply_Condenser_Water_Temperature_Sensor: URIRef # Measures the temperature of the supply condenser water + Hot_Water_Supply_Temperature_Sensor: URIRef # Measures the temperature of water supplied by a hot water system + Hot_Water_Differential_Temperature_Sensor: URIRef # Measures the difference in temperature between the entering water to the boiler or other water heating device and leaving water from the same boiler or other water heating device + Medium_Temperature_Hot_Water_Supply_Temperature_Sensor: URIRef # Measures the temperature of medium-temperature hot water supplied by a hot water system + High_Temperature_Hot_Water_Supply_Temperature_Sensor: URIRef # Measures the temperature of high-temperature hot water supplied by a hot water system + Domestic_Hot_Water_Supply_Temperature_Sensor: URIRef # Measures the temperature of domestic water supplied by a hot water system + Leaving_Water_Temperature_Sensor: URIRef # Measures the temperature of water leaving a piece of equipment or system + Ice_Tank_Leaving_Water_Temperature_Sensor: URIRef # Measures the temperature of water leaving an ice tank + Entering_Water_Temperature_Sensor: URIRef # Measures the temperature of water entering a piece of equipment or system + Water_Differential_Temperature_Sensor: URIRef # Measures the difference in water temperature between an upstream and downstream point in a pipe or conduit + Chilled_Water_Differential_Temperature_Sensor: URIRef # Measures the difference in temperature between the entering water to the chiller or other water cooling device and leaving water from the same chiller or other water cooling device + Differential_Supply_Return_Water_Temperature_Sensor: URIRef # Measures the difference in temperature between return and supply water of water a circuit + Heat_Exchanger_Supply_Water_Temperature_Sensor: URIRef # Measures the temperature of water supplied by a heat exchanger + Discharge_Water_Temperature_Sensor: URIRef # Measures the temperature of discharge water + Collection_Basin_Water_Temperature_Sensor: URIRef # Measures the temperature of the water in the collection basin, e.g. within a Cooling_Tower + Chilled_Water_Temperature_Sensor: URIRef # Measures the temperature of chilled water + Chilled_Water_Supply_Temperature_Sensor: URIRef # Measures the temperature of chilled water that is supplied from a chiller + Chilled_Water_Return_Temperature_Sensor: URIRef # Measures the temperature of chilled water that is returned to a cooling tower + Return_Water_Temperature_Sensor: URIRef # Measures the temperature of return water + Hot_Water_Return_Temperature_Sensor: URIRef # Measures the temperature of water returned to a hot water system + High_Temperature_Hot_Water_Return_Temperature_Sensor: URIRef # Measures the temperature of high-temperature hot water returned to a hot water system + Medium_Temperature_Hot_Water_Return_Temperature_Sensor: URIRef # Measures the temperature of medium-temperature hot water returned to a hot water system + Radiant_Panel_Temperature_Sensor: URIRef # Measures the temperature of the radiant panel of the radiant heating and cooling HVAC system. + Embedded_Temperature_Sensor: URIRef # Measures the internal temperature of the radiant layer of the radiant heating and cooling HVAC system. + Core_Temperature_Sensor: URIRef # Measures the internal temperature of the radiant layer at the heat source or sink level of the radiant heating and cooling HVAC system. + Outside_Face_Surface_Temperature_Sensor: URIRef # Measures the outside surface (relative to the space) of the radiant panel of a radiant heating and cooling HVAC system. + Inside_Face_Surface_Temperature_Sensor: URIRef # Measures the inside surface (relative to the space) of the radiant panel of the radiant heating and cooling HVAC system. + Air_Wet_Bulb_Temperature_Sensor: URIRef # + Outside_Air_Wet_Bulb_Temperature_Sensor: URIRef # A sensor measuring the wet-bulb temperature of outside air + Air_Temperature_Sensor: URIRef # Measures the temperature of air + Outside_Air_Temperature_Sensor: URIRef # Measures the temperature of outside air + Intake_Air_Temperature_Sensor: URIRef # Measures air at the interface between the building and the outside + Outside_Air_Temperature_Enable_Differential_Sensor: URIRef # + Low_Outside_Air_Temperature_Enable_Differential_Sensor: URIRef # + Zone_Air_Temperature_Sensor: URIRef # Measures the temperature of air in a zone + Average_Zone_Air_Temperature_Sensor: URIRef # The computed average temperature of air in a zone, over some period of time + Warmest_Zone_Air_Temperature_Sensor: URIRef # The zone temperature that is warmest; drives the supply temperature of cold air. A computed value rather than a physical sensor. Also referred to as a 'Highest Zone Air Temperature Sensor' + Coldest_Zone_Air_Temperature_Sensor: URIRef # The zone temperature that is coldest; drives the supply temperature of hot air. A computed value rather than a physical sensor. Also referred to as a 'Lowest Zone Air Temperature Sensor' + Return_Air_Temperature_Sensor: URIRef # Measures the temperature of return air + Supply_Air_Temperature_Sensor: URIRef # Measures the temperature of supply air + Preheat_Supply_Air_Temperature_Sensor: URIRef # Measures the temperature of supply air before it is heated + Mixed_Air_Temperature_Sensor: URIRef # Measures the temperature of mixed air + Underfloor_Air_Temperature_Sensor: URIRef # Measures the temperature of underfloor air + Exhaust_Air_Temperature_Sensor: URIRef # Measures the temperature of exhaust air + Discharge_Air_Temperature_Sensor: URIRef # Measures the temperature of discharge air + Preheat_Discharge_Air_Temperature_Sensor: URIRef # Measures the temperature of discharge air before heating is applied + Conductivity_Sensor: URIRef # Measures electrical conductance + Deionised_Water_Conductivity_Sensor: URIRef # Measures the electrical conductance of deionised water + Luminance_Sensor: URIRef # Measures the luminous intensity per unit area of light travelling in a given direction + Piezoelectric_Sensor: URIRef # Senses changes pressure, acceleration, temperature, force or strain via the piezoelectric effect + Demand_Sensor: URIRef # Measures the amount of power consumed by the use of some process; typically found by multiplying the tonnage of a unit (e.g. RTU) by the efficiency rating in kW/ton + Cooling_Demand_Sensor: URIRef # Measures the amount of power consumed by a cooling process; typically found by multiplying the tonnage of a unit (e.g. RTU) by the efficiency rating in kW/ton + Average_Cooling_Demand_Sensor: URIRef # Measures the average power consumed by a cooling process as the amount of power consumed over some interval + Heating_Demand_Sensor: URIRef # Measures the amount of power consumed by a heating process; typically found by multiplying the tonnage of a unit (e.g. RTU) by the efficiency rating in kW/ton + Average_Heating_Demand_Sensor: URIRef # Measures the average power consumed by a heating process as the amount of power consumed over some interval + Air_Quality_Sensor: URIRef # A sensor which provides a measure of air quality + CO_Sensor: URIRef # Measures properties of CO + Return_Air_CO_Sensor: URIRef # Measures the concentration of CO in return air + CO_Level_Sensor: URIRef # Measures the concentration of CO + CO_Differential_Sensor: URIRef # + Outside_Air_CO_Sensor: URIRef # Measures the concentration of CO in outside air + NO2_Level_Sensor: URIRef # Measures the concentration of NO2 in air + Formaldehyde_Level_Sensor: URIRef # Measures the concentration of formaldehyde in air + Ozone_Level_Sensor: URIRef # Measures the concentration of ozone in air + Particulate_Matter_Sensor: URIRef # Detects pollutants in the ambient air + PM2.5_Sensor: URIRef # Detects matter of size 2.5 microns + PM2.5_Level_Sensor: URIRef # Detects level of particulates of size 2.5 microns + PM1_Sensor: URIRef # Detects matter of size 1 micron + PM1_Level_Sensor: URIRef # Detects level of particulates of size 1 microns + PM1_Level_Sensor: URIRef # Detects level of particulates of size 1 micron + PM10_Sensor: URIRef # Detects matter of size 10 microns + PM10_Level_Sensor: URIRef # Detects level of particulates of size 10 microns + TVOC_Sensor: URIRef # + TVOC_Level_Sensor: URIRef # A sensor measuring the level of all VOCs in air + Radioactivity_Concentration_Sensor: URIRef # Measures the concentration of radioactivity + Radon_Concentration_Sensor: URIRef # Measures the concentration of radioactivity due to radon + CO2_Sensor: URIRef # Measures properties of CO2 in air + Outside_Air_CO2_Sensor: URIRef # Measures the concentration of CO2 in outside air + CO2_Level_Sensor: URIRef # Measures the concentration of CO2 in air + CO2_Differential_Sensor: URIRef # Measures the difference between CO2 levels of inside and outside air + Return_Air_CO2_Sensor: URIRef # Measures the concentration of CO2 in return air + Methane_Level_Sensor: URIRef # Measures the concentration of methane in air + Capacity_Sensor: URIRef # + Gas_Sensor: URIRef # Measures gas concentration (other than CO2) + Air_Grains_Sensor: URIRef # Measures the mass of water vapor in air + Outside_Air_Grains_Sensor: URIRef # Measures the mass of water vapor in outside air + Return_Air_Grains_Sensor: URIRef # Measures the mass of water vapor in return air + Alarm: URIRef # Alarm points are signals (either audible or visual) that alert an operator to an off-normal condition which requires some form of corrective action + Failure_Alarm: URIRef # Alarms that indicate the failure of devices, equipment, systems and control loops + Unit_Failure_Alarm: URIRef # An alarm that indicates the failure of an equipment or device + Humidity_Alarm: URIRef # An alarm that indicates the off-normal conditions associated with the concentration of water vapor in the air. + High_Humidity_Alarm: URIRef # An alarm that indicates high concentration of water vapor in the air. + Low_Humidity_Alarm: URIRef # An alarm that indicates low concentration of water vapor in the air. + Luminance_Alarm: URIRef # + Temperature_Alarm: URIRef # An alarm that indicates the off-normal conditions associated with temperature. + Low_Temperature_Alarm: URIRef # An alarm that indicates low temperature. + Low_Return_Air_Temperature_Alarm: URIRef # An alarm that indicates that return air temperature is too low + High_Temperature_Alarm: URIRef # An alarm that indicates high temperature. + High_Return_Air_Temperature_Alarm: URIRef # An alarm that indicates that return air temperature is too high + High_Discharge_Air_Temperature_Alarm: URIRef # An alarm that indicates that discharge air temperature is too high + Water_Temperature_Alarm: URIRef # An alarm that indicates the off-normal conditions associated with temperature of water. + Supply_Water_Temperature_Alarm: URIRef # An alarm that indicates the off-normal conditions associated with temperature of the supply water. + Discharge_Water_Temperature_Alarm: URIRef # An alarm that indicates the off-normal conditions associated with temperature of the discharge water. + Air_Temperature_Alarm: URIRef # An alarm that indicates the off-normal conditions associated with the temperature of air. + Return_Air_Temperature_Alarm: URIRef # An alarm that indicates the off-normal conditions associated with the temperature of return air. + Supply_Air_Temperature_Alarm: URIRef # An alarm that indicates the off-normal conditions associated with the temperature of supply air. + Discharge_Air_Temperature_Alarm: URIRef # An alarm that indicates the off-normal conditions associated with the temperature of discharge air. + Overload_Alarm: URIRef # An alarm that can indicate when a full-load current is exceeded. + Communication_Loss_Alarm: URIRef # An alarm that indicates a loss of communication e.g. with a device or controller + Emergency_Alarm: URIRef # Alarms that indicate off-normal conditions associated with emergency systems + Emergency_Generator_Alarm: URIRef # An alarm that indicates off-normal conditions associated with an emergency generator + Maintenance_Required_Alarm: URIRef # An alarm that indicates that repair/maintenance is required on an associated device or equipment + Liquid_Detection_Alarm: URIRef # + Cycle_Alarm: URIRef # An alarm that indicates off-normal conditions associated with HVAC cycles + Short_Cycle_Alarm: URIRef # An alarm that indicates a short cycle occurred. A short cycle occurs when a cooling cycle is prevented from completing its full cycle + Pressure_Alarm: URIRef # An alarm that indicates the off-normal conditions associated with pressure. + High_Head_Pressure_Alarm: URIRef # An alarm that indicates a high pressure generated on the output side of a gas compressor in a refrigeration or air conditioning system. + Low_Suction_Pressure_Alarm: URIRef # An alarm that indicates a low suction pressure in the compressor in a refrigeration or air conditioning system. + CO2_Alarm: URIRef # An alarm that indicates the off-normal conditions associated with the presence of carbon dioxide. + High_CO2_Alarm: URIRef # A device that indicates high concentration of carbon dioxide. + Smoke_Alarm: URIRef # An alarm that indicates the off-normal conditions associated with smoke. + Smoke_Detection_Alarm: URIRef # + Discharge_Air_Smoke_Detection_Alarm: URIRef # + Leak_Alarm: URIRef # An alarm that indicates leaks occured in systems containing fluids + Condensate_Leak_Alarm: URIRef # An alarm that indicates a leak of condensate from a cooling system + Water_Alarm: URIRef # Alarm that indicates an undesirable event with a pipe, container, or equipment carrying water e.g. water leak + Water_Loss_Alarm: URIRef # An alarm that indicates a loss of water e.g. during transport + Deionized_Water_Alarm: URIRef # An alarm that indicates deionized water leaks. + Water_Level_Alarm: URIRef # An alarm that indicates a high or low water level e.g. in a basin + Max_Water_Level_Alarm: URIRef # Alarm indicating that the maximum water level was reached + Min_Water_Level_Alarm: URIRef # Alarm indicating that the minimum water level was reached + Collection_Basin_Water_Level_Alarm: URIRef # An alarm that indicates a high or low level of water in the collection basin, e.g. within a Cooling_Tower + No_Water_Alarm: URIRef # Alarm indicating that there is no water in the equipment or system + Air_Alarm: URIRef # + Air_Flow_Loss_Alarm: URIRef # An alarm that indicates loss in air flow. + Change_Filter_Alarm: URIRef # An alarm that indicates that a filter must be changed + Power_Alarm: URIRef # An alarm that indicates the off-normal conditions associated with electrical power. + Power_Loss_Alarm: URIRef # An alarm that indicates a power failure. + Parameter: URIRef # Parameter points are configuration settings used to guide the operation of equipment and control systems; for example they may provide bounds on valid setpoint values + Limit: URIRef # A parameter that places a lower or upper bound on the range of permitted values of a Setpoint. + Limit: URIRef # A parameter that places an upper or lower bound on the range of permitted values of another point + Air_Temperature_Setpoint_Limit: URIRef # A parameter that places a lower or upper bound on the range of permitted values of a Air_Temperature_Setpoint. + Discharge_Air_Temperature_Setpoint_Limit: URIRef # A parameter that places a lower or upper bound on the range of permitted values of a Discharge_Air_Temperature_Setpoint. + Min_Discharge_Air_Temperature_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Discharge_Air_Temperature_Setpoint. + Max_Discharge_Air_Temperature_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Discharge_Air_Temperature_Setpoint. + Max_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Setpoint. + Max_Position_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Position_Setpoint. + Max_Speed_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Speed_Setpoint. + Max_Static_Pressure_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Static_Pressure_Setpoint. + Max_Discharge_Air_Static_Pressure_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Discharge_Air_Static_Pressure_Setpoint. + Max_Supply_Air_Static_Pressure_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Supply_Air_Static_Pressure_Setpoint. + Max_Temperature_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Temperature_Setpoint. + Max_Air_Flow_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Air_Flow_Setpoint. + Max_Heating_Supply_Air_Flow_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Heating_Supply_Air_Flow_Setpoint. + Max_Occupied_Heating_Supply_Air_Flow_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Occupied_Heating_Supply_Air_Flow_Setpoint. + Max_Unoccupied_Heating_Supply_Air_Flow_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Unoccupied_Heating_Supply_Air_Flow_Setpoint. + Max_Cooling_Supply_Air_Flow_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Cooling_Supply_Air_Flow_Setpoint. + Max_Unoccupied_Cooling_Supply_Air_Flow_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Unoccupied_Cooling_Supply_Air_Flow_Setpoint. + Max_Occupied_Cooling_Supply_Air_Flow_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Occupied_Cooling_Supply_Air_Flow_Setpoint. + Max_Cooling_Discharge_Air_Flow_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Cooling_Discharge_Air_Flow_Setpoint. + Max_Occupied_Cooling_Discharge_Air_Flow_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Occupied_Cooling_Discharge_Air_Flow_Setpoint. + Max_Unoccupied_Cooling_Discharge_Air_Flow_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Unoccupied_Cooling_Discharge_Air_Flow_Setpoint. + Max_Heating_Discharge_Air_Flow_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Heating_Discharge_Air_Flow_Setpoint. + Max_Occupied_Heating_Discharge_Air_Flow_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Occupied_Heating_Discharge_Air_Flow_Setpoint. + Max_Unoccupied_Heating_Discharge_Air_Flow_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Unoccupied_Heating_Discharge_Air_Flow_Setpoint. + Max_Hot_Water_Differential_Pressure_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Hot_Water_Differential_Pressure_Setpoint. + Max_Chilled_Water_Differential_Pressure_Setpoint_Limit: URIRef # A parameter that places an upper bound on the range of permitted values of a Chilled_Water_Differential_Pressure_Setpoint. + Min_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Setpoint. + Min_Discharge_Air_Static_Pressure_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Discharge_Air_Static_Pressure_Setpoint. + Min_Supply_Air_Static_Pressure_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Supply_Air_Static_Pressure_Setpoint. + Min_Chilled_Water_Differential_Pressure_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Chilled_Water_Differential_Pressure_Setpoint. + Min_Static_Pressure_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Static_Pressure_Setpoint. + Min_Hot_Water_Differential_Pressure_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Hot_Water_Differential_Pressure_Setpoint. + Min_Speed_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Speed_Setpoint. + Min_Fresh_Air_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Fresh_Air_Setpoint. + Min_Temperature_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Temperature_Setpoint. + Min_Air_Flow_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Air_Flow_Setpoint. + Min_Cooling_Supply_Air_Flow_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Cooling_Supply_Air_Flow_Setpoint. + Min_Unoccupied_Cooling_Supply_Air_Flow_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Unoccupied_Cooling_Supply_Air_Flow_Setpoint. + Min_Occupied_Cooling_Supply_Air_Flow_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Occupied_Cooling_Supply_Air_Flow_Setpoint. + Min_Outside_Air_Flow_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Outside_Air_Flow_Setpoint. + Min_Heating_Discharge_Air_Flow_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Heating_Discharge_Air_Flow_Setpoint. + Min_Unoccupied_Heating_Discharge_Air_Flow_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Unoccupied_Heating_Discharge_Air_Flow_Setpoint. + Min_Occupied_Heating_Discharge_Air_Flow_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Occupied_Heating_Discharge_Air_Flow_Setpoint. + Min_Heating_Supply_Air_Flow_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Heating_Supply_Air_Flow_Setpoint. + Min_Occupied_Heating_Supply_Air_Flow_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Occupied_Heating_Supply_Air_Flow_Setpoint. + Min_Unoccupied_Heating_Supply_Air_Flow_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Unoccupied_Heating_Supply_Air_Flow_Setpoint. + Min_Cooling_Discharge_Air_Flow_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Cooling_Discharge_Air_Flow_Setpoint. + Min_Unoccupied_Cooling_Discharge_Air_Flow_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Unoccupied_Cooling_Discharge_Air_Flow_Setpoint. + Min_Occupied_Cooling_Discharge_Air_Flow_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Occupied_Cooling_Discharge_Air_Flow_Setpoint. + Min_Position_Setpoint_Limit: URIRef # A parameter that places a lower bound on the range of permitted values of a Position_Setpoint. + Air_Flow_Setpoint_Limit: URIRef # A parameter that places a lower or upper bound on the range of permitted values of a Air_Flow_Setpoint. + Current_Limit: URIRef # A parameter that places a lower or upper bound on the range of permitted values of a Current_Setpoint. + Fresh_Air_Setpoint_Limit: URIRef # A parameter that places a lower or upper bound on the range of permitted values of a Fresh_Air_Setpoint. + Close_Limit: URIRef # A parameter that places a lower or upper bound on the range of permitted values of a Close_Setpoint. + Ventilation_Air_Flow_Ratio_Limit: URIRef # A parameter that places a lower or upper bound on the range of permitted values of a Ventilation_Air_Flow_Ratio_Setpoint. + Position_Limit: URIRef # A parameter that places a lower or upper bound on the range of permitted values of a Position_Setpoint. + Speed_Setpoint_Limit: URIRef # A parameter that places a lower or upper bound on the range of permitted values of a Speed_Setpoint. + Differential_Pressure_Setpoint_Limit: URIRef # A parameter that places a lower or upper bound on the range of permitted values of a Differential_Pressure_Setpoint. + Static_Pressure_Setpoint_Limit: URIRef # A parameter that places a lower or upper bound on the range of permitted values of a Static_Pressure_Setpoint. + High_Static_Pressure_Cutout_Setpoint_Limit: URIRef # A parameter that places a lower or upper bound on the range of permitted values of a High_Static_Pressure_Cutout_Setpoint. + Delay_Parameter: URIRef # A parameter determining how long to delay a subsequent action to take place after a received signal + Alarm_Delay_Parameter: URIRef # A parameter determining how long to delay an alarm after sufficient conditions have been met + Tolerance_Parameter: URIRef # difference between upper and lower limits of size for a given nominal dimension or value. + Humidity_Tolerance_Parameter: URIRef # A parameter determining the difference between upper and lower limits of humidity. + Temperature_Tolerance_Parameter: URIRef # A parameter determining the difference between upper and lower limits of temperature. + Load_Parameter: URIRef # + Max_Load_Setpoint: URIRef # + PID_Parameter: URIRef # + Step_Parameter: URIRef # + Static_Pressure_Step_Parameter: URIRef # + Air_Static_Pressure_Step_Parameter: URIRef # + Discharge_Air_Static_Pressure_Step_Parameter: URIRef # + Differential_Pressure_Step_Parameter: URIRef # + Chilled_Water_Differential_Pressure_Step_Parameter: URIRef # + Temperature_Step_Parameter: URIRef # + Air_Temperature_Step_Parameter: URIRef # + Supply_Air_Temperature_Step_Parameter: URIRef # + Discharge_Air_Temperature_Step_Parameter: URIRef # + Time_Parameter: URIRef # + Derivative_Time_Parameter: URIRef # + Integral_Time_Parameter: URIRef # + Exhaust_Air_Flow_Integral_Time_Parameter: URIRef # + Exhaust_Air_Stack_Flow_Integral_Time_Parameter: URIRef # + Static_Pressure_Integral_Time_Parameter: URIRef # + Discharge_Air_Static_Pressure_Integral_Time_Parameter: URIRef # + Supply_Air_Static_Pressure_Integral_Time_Parameter: URIRef # + Supply_Water_Temperature_Integral_Time_Parameter: URIRef # + Supply_Water_Differential_Pressure_Integral_Time_Parameter: URIRef # + Air_Temperature_Integral_Time_Parameter: URIRef # + Cooling_Discharge_Air_Temperature_Integral_Time_Parameter: URIRef # + Heating_Supply_Air_Temperature_Integral_Time_Parameter: URIRef # + Cooling_Supply_Air_Temperature_Integral_Time_Parameter: URIRef # + Heating_Discharge_Air_Temperature_Integral_Time_Parameter: URIRef # + Differential_Pressure_Integral_Time_Parameter: URIRef # + Chilled_Water_Differential_Pressure_Integral_Time_Parameter: URIRef # + Hot_Water_Differential_Pressure_Integral_Time_Parameter: URIRef # + Discharge_Water_Differential_Pressure_Integral_Time_Parameter: URIRef # + Proportional_Band_Parameter: URIRef # + Supply_Water_Temperature_Proportional_Band_Parameter: URIRef # + Exhaust_Air_Flow_Proportional_Band_Parameter: URIRef # + Exhaust_Air_Stack_Flow_Proportional_Band_Parameter: URIRef # + Supply_Air_Temperature_Proportional_Band_Parameter: URIRef # + Cooling_Supply_Air_Temperature_Proportional_Band_Parameter: URIRef # + Heating_Supply_Air_Temperature_Proportional_Band_Parameter: URIRef # + Discharge_Air_Temperature_Proportional_Band_Parameter: URIRef # + Heating_Discharge_Air_Temperature_Proportional_Band_Parameter: URIRef # + Cooling_Discharge_Air_Temperature_Proportional_Band_Parameter: URIRef # + Static_Pressure_Proportional_Band_Parameter: URIRef # + Exhaust_Air_Static_Pressure_Proportional_Band_Parameter: URIRef # + Discharge_Air_Static_Pressure_Proportional_Band_Parameter: URIRef # + Supply_Air_Static_Pressure_Proportional_Band_Parameter: URIRef # + Differential_Pressure_Proportional_Band: URIRef # + Chilled_Water_Differential_Pressure_Proportional_Band_Parameter: URIRef # + Supply_Water_Differential_Pressure_Proportional_Band_Parameter: URIRef # + Discharge_Water_Differential_Pressure_Proportional_Band_Parameter: URIRef # + Hot_Water_Differential_Pressure_Proportional_Band_Parameter: URIRef # + Discharge_Water_Temperature_Proportional_Band_Parameter: URIRef # + Gain_Parameter: URIRef # + Proportional_Gain_Parameter: URIRef # + Supply_Air_Proportional_Gain_Parameter: URIRef # + Integral_Gain_Parameter: URIRef # + Supply_Air_Integral_Gain_Parameter: URIRef # + Derivative_Gain_Parameter: URIRef # + Temperature_Parameter: URIRef # Parameters relevant to temperature-related systems and points + Low_Temperature_Alarm_Parameter: URIRef # A parameter determining the temperature level at which to trigger a low temperature alarm + Lockout_Temperature_Differential_Parameter: URIRef # + Outside_Air_Lockout_Temperature_Differential_Parameter: URIRef # + High_Outside_Air_Lockout_Temperature_Differential_Parameter: URIRef # The upper bound of the outside air temperature lockout range + Low_Outside_Air_Lockout_Temperature_Differential_Parameter: URIRef # The lower bound of the outside air temperature lockout range + Low_Freeze_Protect_Temperature_Parameter: URIRef # + High_Temperature_Alarm_Parameter: URIRef # A parameter determining the temperature level at which to trigger a high temperature alarm + Humidity_Parameter: URIRef # Parameters relevant to humidity-related systems and points + Low_Humidity_Alarm_Parameter: URIRef # A parameter determining the humidity level at which to trigger a low humidity alarm + High_Humidity_Alarm_Parameter: URIRef # A parameter determining the humidity level at which to trigger a high humidity alarm + Setpoint: URIRef # A Setpoint is an input value at which the desired property is set + Deadband_Setpoint: URIRef # Sets the size of a deadband + Air_Flow_Deadband_Setpoint: URIRef # Sets the size of a deadband of air flow + Exhaust_Air_Stack_Flow_Deadband_Setpoint: URIRef # Sets the size of a deadband of exhaust air stack flow + Differential_Pressure_Deadband_Setpoint: URIRef # Sets the size of a deadband of differential pressure + Supply_Water_Differential_Pressure_Deadband_Setpoint: URIRef # Sets the size of a deadband of differential pressure of supply water + Chilled_Water_Differential_Pressure_Deadband_Setpoint: URIRef # Sets the size of a deadband of differential pressure of chilled water + Chilled_Water_Pump_Differential_Pressure_Deadband_Setpoint: URIRef # Sets the size of a deadband of differential pressure of chilled water in a chilled water pump + Discharge_Water_Differential_Pressure_Deadband_Setpoint: URIRef # Sets the size of a deadband of differential pressure of discharge water + Hot_Water_Differential_Pressure_Deadband_Setpoint: URIRef # Sets the size of a deadband of differential pressure of hot water + Temperature_Deadband_Setpoint: URIRef # Sets the size of a deadband of temperature + Supply_Water_Temperature_Deadband_Setpoint: URIRef # Sets the size of a deadband of temperature of supply water + Occupied_Heating_Temperature_Deadband_Setpoint: URIRef # Sets the size of a deadband of temperature for heating when occupied + Occupied_Cooling_Temperature_Deadband_Setpoint: URIRef # Sets the size of a deadband of temperature for cooling when occupied + Discharge_Air_Temperature_Deadband_Setpoint: URIRef # Sets the size of a deadband of temperature of discharge air + Heating_Discharge_Air_Temperature_Deadband_Setpoint: URIRef # Sets the size of a deadband of temperature of heating discharge air + Cooling_Discharge_Air_Temperature_Deadband_Setpoint: URIRef # Sets the size of a deadband of temperature of cooling discharge air + Supply_Air_Temperature_Deadband_Setpoint: URIRef # Sets the size of a deadband of temperature of supply air + Heating_Supply_Air_Temperature_Deadband_Setpoint: URIRef # Sets the size of a deadband of temperature of supply air for heating + Cooling_Supply_Air_Temperature_Deadband_Setpoint: URIRef # Sets the size of a deadband of temperature of supply air for cooling + Static_Pressure_Deadband_Setpoint: URIRef # Sets the size of a deadband of static pressure + Supply_Air_Static_Pressure_Deadband_Setpoint: URIRef # Sets the size of a deadband of static pressure of supply air + Discharge_Air_Static_Pressure_Deadband_Setpoint: URIRef # Sets the size of a deadband of static pressure of discharge air + Luminance_Setpoint: URIRef # Sets luminance + Demand_Setpoint: URIRef # Sets the rate required for a process + Heating_Demand_Setpoint: URIRef # Sets the rate required for heating + Preheat_Demand_Setpoint: URIRef # Sets the rate required for preheat + Cooling_Demand_Setpoint: URIRef # Sets the rate required for cooling + Air_Flow_Demand_Setpoint: URIRef # Sets the rate of air flow required for a process + Discharge_Air_Flow_Demand_Setpoint: URIRef # Sets the rate of discharge air flow required for a process + Supply_Air_Flow_Demand_Setpoint: URIRef # Sets the rate of supply air flow required for a process + Reset_Setpoint: URIRef # Setpoints used in reset strategies + Temperature_Differential_Reset_Setpoint: URIRef # + Discharge_Air_Temperature_Reset_Differential_Setpoint: URIRef # + Discharge_Air_Temperature_Low_Reset_Setpoint: URIRef # + Discharge_Air_Temperature_High_Reset_Setpoint: URIRef # + Supply_Air_Temperature_Reset_Differential_Setpoint: URIRef # + Temperature_High_Reset_Setpoint: URIRef # + Return_Air_Temperature_High_Reset_Setpoint: URIRef # + Outside_Air_Temperature_High_Reset_Setpoint: URIRef # + Hot_Water_Supply_Temperature_High_Reset_Setpoint: URIRef # + Medium_Temperature_Hot_Water_Supply_Temperature_High_Reset_Setpoint: URIRef # + Medium_Temperature_Hot_Water_Discharge_Temperature_High_Reset_Setpoint: URIRef # + Supply_Air_Temperature_High_Reset_Setpoint: URIRef # + Discharge_Air_Flow_Reset_Setpoint: URIRef # Setpoints used in Reset strategies + Discharge_Air_Flow_Low_Reset_Setpoint: URIRef # + Discharge_Air_Flow_High_Reset_Setpoint: URIRef # + Temperature_Low_Reset_Setpoint: URIRef # + Outside_Air_Temperature_Low_Reset_Setpoint: URIRef # + Hot_Water_Supply_Temperature_Low_Reset_Setpoint: URIRef # + Medium_Temperature_Hot_Water_Supply_Temperature_Low_Reset_Setpoint: URIRef # + Medium_Temperature_Hot_Water_Discharge_Temperature_Low_Reset_Setpoint: URIRef # + Return_Air_Temperature_Low_Reset_Setpoint: URIRef # + Supply_Air_Temperature_Low_Reset_Setpoint: URIRef # + Flow_Setpoint: URIRef # Sets flow + Air_Flow_Setpoint: URIRef # Sets air flow + Supply_Air_Flow_Setpoint: URIRef # Sets supply air flow rate + Heating_Supply_Air_Flow_Setpoint: URIRef # Sets supply air flow rate for heating + Occupied_Heating_Supply_Air_Flow_Setpoint: URIRef # Sets supply air flow rate for heating when occupied + Cooling_Supply_Air_Flow_Setpoint: URIRef # Sets supply air flow rate for cooling + Occupied_Cooling_Supply_Air_Flow_Setpoint: URIRef # Sets supply air flow rate for cooling when occupied + Occupied_Supply_Air_Flow_Setpoint: URIRef # Sets supply air flow rate when occupied + Exhaust_Air_Flow_Setpoint: URIRef # Sets exhaust air flow rate + Exhaust_Air_Stack_Flow_Setpoint: URIRef # Sets exhaust air stack flow rate + Outside_Air_Flow_Setpoint: URIRef # Sets outside air flow rate + Discharge_Air_Flow_Setpoint: URIRef # Sets discharge air flow + Heating_Discharge_Air_Flow_Setpoint: URIRef # Sets discharge air flow for heating + Occupied_Heating_Discharge_Air_Flow_Setpoint: URIRef # Sets discharge air flow for heating when occupied + Cooling_Discharge_Air_Flow_Setpoint: URIRef # Sets discharge air flow for cooling + Occupied_Cooling_Discharge_Air_Flow_Setpoint: URIRef # Sets discharge air flow for cooling when occupied + Unoccupied_Cooling_Discharge_Air_Flow_Setpoint: URIRef # Sets discharge air flow for cooling when unoccupied + Occupied_Discharge_Air_Flow_Setpoint: URIRef # Sets discharge air flow when occupied + Water_Flow_Setpoint: URIRef # Sets the target flow rate of water + Discharge_Water_Flow_Setpoint: URIRef # Sets the target flow rate of discharge water + Chilled_Water_Discharge_Flow_Setpoint: URIRef # Sets the target flow rate of chilled discharge water + Hot_Water_Discharge_Flow_Setpoint: URIRef # Sets the target flow rate of hot discharge water + Supply_Water_Flow_Setpoint: URIRef # Sets the flow rate of hot supply water + Chilled_Water_Supply_Flow_Setpoint: URIRef # Sets the target flow rate of chilled supply water + Hot_Water_Supply_Flow_Setpoint: URIRef # Sets the target flow rate of hot supply water + Entering_Water_Flow_Setpoint: URIRef # Sets the target flow rate of entering water + Hot_Water_Flow_Setpoint: URIRef # Sets the target flow rate of hot water + Bypass_Water_Flow_Setpoint: URIRef # Sets the target flow rate of bypass water + Leaving_Water_Flow_Setpoint: URIRef # Sets the target flow rate of leaving water + Chilled_Water_Flow_Setpoint: URIRef # Sets the target flow rate of chilled water + Humidity_Setpoint: URIRef # Sets humidity + Air_Humidity_Setpoint: URIRef # + Bypass_Air_Humidity_Setpoint: URIRef # Humidity setpoint for bypass air + Zone_Air_Humidity_Setpoint: URIRef # Humidity setpoint for zone air + Exhaust_Air_Humidity_Setpoint: URIRef # Humidity setpoint for exhaust air + Return_Air_Humidity_Setpoint: URIRef # Humidity setpoint for return air + Building_Air_Humidity_Setpoint: URIRef # Setpoint for humidity in a building + Mixed_Air_Humidity_Setpoint: URIRef # Humidity setpoint for mixed air + Discharge_Air_Humidity_Setpoint: URIRef # Humidity setpoint for discharge air + Outside_Air_Humidity_Setpoint: URIRef # Humidity setpoint for outside air + Supply_Air_Humidity_Setpoint: URIRef # Humidity setpoint for supply air + Damper_Position_Setpoint: URIRef # Sets the position of damper + Enthalpy_Setpoint: URIRef # Sets enthalpy + Temperature_Setpoint: URIRef # Sets temperature + Radiant_Panel_Temperature_Setpoint: URIRef # Sets temperature of radiant panel. + Outside_Face_Surface_Temperature_Setpoint: URIRef # Sets temperature for the outside face surface temperature of the radiant panel. + Embedded_Temperature_Setpoint: URIRef # Sets temperature for the internal material, e.g. concrete slab, of the radiant panel. + Core_Temperature_Setpoint: URIRef # Sets temperature for the core, i.e. the temperature at the heat source or sink level, of the radiant panel. + Inside_Face_Surface_Temperature_Setpoint: URIRef # Sets temperature for the inside face surface temperature of the radiant panel. + Cooling_Temperature_Setpoint: URIRef # Sets temperature for cooling + Effective_Air_Temperature_Cooling_Setpoint: URIRef # + Unoccupied_Air_Temperature_Cooling_Setpoint: URIRef # Sets temperature of air when unoccupied for cooling + Discharge_Air_Temperature_Cooling_Setpoint: URIRef # Sets temperature of discharge air for cooling + Zone_Air_Cooling_Temperature_Setpoint: URIRef # The upper (cooling) setpoint for zone air temperature + Schedule_Temperature_Setpoint: URIRef # The current setpoint as indicated by the schedule + Air_Temperature_Setpoint: URIRef # Sets temperature of air + Effective_Air_Temperature_Setpoint: URIRef # + Effective_Discharge_Air_Temperature_Setpoint: URIRef # + Effective_Return_Air_Temperature_Setpoint: URIRef # + Effective_Air_Temperature_Heating_Setpoint: URIRef # + Effective_Supply_Air_Temperature_Setpoint: URIRef # + Effective_Zone_Air_Temperature_Setpoint: URIRef # + Effective_Room_Air_Temperature_Setpoint: URIRef # + Occupied_Air_Temperature_Setpoint: URIRef # + Occupied_Zone_Air_Temperature_Setpoint: URIRef # + Occupied_Room_Air_Temperature_Setpoint: URIRef # + Occupied_Supply_Air_Temperature_Setpoint: URIRef # + Occupied_Discharge_Air_Temperature_Setpoint: URIRef # + Occupied_Return_Air_Temperature_Setpoint: URIRef # + Supply_Air_Temperature_Setpoint: URIRef # Temperature setpoint for supply air + Unoccupied_Supply_Air_Temperature_Setpoint: URIRef # + Zone_Air_Temperature_Setpoint: URIRef # Sets temperature of zone air + Zone_Air_Heating_Temperature_Setpoint: URIRef # The lower (heating) setpoint for zone air temperature + Unoccupied_Zone_Air_Temperature_Setpoint: URIRef # + Discharge_Air_Temperature_Setpoint: URIRef # Sets temperature of discharge air + Discharge_Air_Temperature_Heating_Setpoint: URIRef # Sets temperature of discharge air for heating + Unoccupied_Discharge_Air_Temperature_Setpoint: URIRef # + Max_Air_Temperature_Setpoint: URIRef # Setpoint for maximum air temperature + Return_Air_Temperature_Setpoint: URIRef # The target temperature for return air, often used as an approximation of zone air temperature + Unoccupied_Return_Air_Temperature_Setpoint: URIRef # + Unoccupied_Air_Temperature_Setpoint: URIRef # Sets temperature of air when unoccupied + Unoccupied_Room_Air_Temperature_Setpoint: URIRef # + Unoccupied_Air_Temperature_Heating_Setpoint: URIRef # Sets temperature of air when unoccupied for heating + Min_Air_Temperature_Setpoint: URIRef # Setpoint for minimum air temperature + Room_Air_Temperature_Setpoint: URIRef # Sets temperature of room air + Outside_Air_Temperature_Setpoint: URIRef # Sets temperature of outside air + Enable_Hot_Water_System_Outside_Air_Temperature_Setpoint: URIRef # Enables hot water system when outside air temperature reaches the indicated value + Open_Heating_Valve_Outside_Air_Temperature_Setpoint: URIRef # + Disable_Hot_Water_System_Outside_Air_Temperature_Setpoint: URIRef # Disables hot water system when outside air temperature reaches the indicated value + Outside_Air_Lockout_Temperature_Setpoint: URIRef # + Low_Outside_Air_Temperature_Enable_Setpoint: URIRef # + Differential_Air_Temperature_Setpoint: URIRef # Sets temperature of diffrential air + Mixed_Air_Temperature_Setpoint: URIRef # Sets temperature of mixed air + Water_Temperature_Setpoint: URIRef # Sets temperature of water + Discharge_Water_Temperature_Setpoint: URIRef # Sets temperature of discharge water + Leaving_Water_Temperature_Setpoint: URIRef # Sets temperature of leaving water + Min_Water_Temperature_Setpoint: URIRef # Setpoint for min water temperature + Return_Water_Temperature_Setpoint: URIRef # Sets the temperature of return water + Return_Hot_Water_Temperature_Setpoint: URIRef # Sets the temperature of return (downstream of the hot water load) hot water + Return_Chilled_Water_Temperature_Setpoint: URIRef # Sets the temperature of return (downstream of the chilled water load) chilled water + Hot_Water_Temperature_Setpoint: URIRef # Sets the temperature of hot water + Domestic_Hot_Water_Temperature_Setpoint: URIRef # Sets temperature of domestic hot water + Domestic_Hot_Water_Supply_Temperature_Setpoint: URIRef # Sets temperature of supplying part of domestic hot water + Supply_Hot_Water_Temperature_Setpoint: URIRef # Temperature setpoint for supply hot water + Chilled_Water_Temperature_Setpoint: URIRef # Sets the temperature of chilled water + Supply_Chilled_Water_Temperature_Setpoint: URIRef # Temperature setpoint for supply chilled water + Supply_Water_Temperature_Setpoint: URIRef # Sets temperature of supply water + Return_Condenser_Water_Temperature_Setpoint: URIRef # The temperature setpoint for the return condenser water + Supply_Condenser_Water_Temperature_Setpoint: URIRef # The temperature setpoint for the supply condenser water + Max_Water_Temperature_Setpoint: URIRef # Setpoint for max water temperature + Entering_Water_Temperature_Setpoint: URIRef # Sets temperature of entering water + Water_Differential_Temperature_Setpoint: URIRef # Sets the target differential temperature between the start and end of a heat transfer cycle in a water circuit + Heating_Temperature_Setpoint: URIRef # Sets temperature for heating + Pressure_Setpoint: URIRef # Sets pressure + Velocity_Pressure_Setpoint: URIRef # Sets static veloicty pressure + Differential_Pressure_Setpoint: URIRef # Sets differential pressure + Water_Differential_Pressure_Setpoint: URIRef # Sets the target water differential pressure between an upstream and downstream point in a water pipe or conduit + Hot_Water_Differential_Pressure_Setpoint: URIRef # Sets the target water differential pressure between an upstream and downstream point in a water pipe or conduit used to carry hot water + Medium_Temperature_Hot_Water_Differential_Pressure_Setpoint: URIRef # + Chilled_Water_Differential_Pressure_Setpoint: URIRef # Sets the target water differential pressure between an upstream and downstream point in a water pipe or conduit used to carry chilled water + Chilled_Water_Differential_Pressure_Load_Shed_Setpoint: URIRef # + Load_Shed_Differential_Pressure_Setpoint: URIRef # + Air_Differential_Pressure_Setpoint: URIRef # Sets the target air differential pressure between an upstream and downstream point in a air duct or conduit + Return_Air_Differential_Pressure_Setpoint: URIRef # Sets the target air differential pressure between an upstream and downstream point in a return air duct or conduit + Supply_Air_Differential_Pressure_Setpoint: URIRef # Sets the target air differential pressure between an upstream and downstream point in a supply air duct or conduit + Exhaust_Air_Differential_Pressure_Setpoint: URIRef # Sets the target air differential pressure between an upstream and downstream point in a exhaust air duct or conduit + Static_Pressure_Setpoint: URIRef # Sets static pressure + Chilled_Water_Static_Pressure_Setpoint: URIRef # Sets static pressure of chilled water + Building_Air_Static_Pressure_Setpoint: URIRef # Sets static pressure of the entire building + Hot_Water_Static_Pressure_Setpoint: URIRef # Sets static pressure of hot air + Supply_Air_Static_Pressure_Setpoint: URIRef # Sets static pressure of supply air + Discharge_Air_Static_Pressure_Setpoint: URIRef # Sets static pressure of discharge air + Underfloor_Air_Plenum_Static_Pressure_Setpoint: URIRef # Sets the underfloor air plenum static pressure + Exhaust_Air_Static_Pressure_Setpoint: URIRef # Sets static pressure of exhaust air + Time_Setpoint: URIRef # + Acceleration_Time_Setpoint: URIRef # + Deceleration_Time_Setpoint: URIRef # + Load_Setpoint: URIRef # + Load_Shed_Setpoint: URIRef # + Medium_Temperature_Hot_Water_Supply_Temperature_Load_Shed_Setpoint: URIRef # + Medium_Temperature_Hot_Water_Differential_Pressure_Load_Shed_Setpoint: URIRef # + Dew_Point_Setpoint: URIRef # Sets dew point + CO2_Setpoint: URIRef # Sets some property of CO2 + Return_Air_CO2_Setpoint: URIRef # Sets some property of CO2 in Return Air + Speed_Setpoint: URIRef # Sets speed + Rated_Speed_Setpoint: URIRef # Sets rated speed + Differential_Speed_Setpoint: URIRef # Sets differential speed + Command: URIRef # A Command is an output point that directly determines the behavior of equipment and/or affects relevant operational points. + Direction_Command: URIRef # Commands that affect the direction of some phenomenon + Occupancy_Command: URIRef # Controls whether or not a device or controller is operating in "Occupied" mode + Valve_Command: URIRef # Controls or reports the openness of a valve (typically as a proportion of its full range of motion) + Mode_Command: URIRef # Controls the operating mode of a device or controller + Automatic_Mode_Command: URIRef # Controls whether or not a device or controller is operating in "Automatic" mode + Maintenance_Mode_Command: URIRef # Controls whether or not a device or controller is operating in "Maintenance" mode + Box_Mode_Command: URIRef # + Heating_Command: URIRef # Controls the amount of heating to be delivered (typically as a proportion of total heating output) + Pump_Command: URIRef # Controls or reports the speed of a pump (typically as a proportion of its full pumping capacity) + Position_Command: URIRef # Controls or reports the position of some object + Damper_Position_Command: URIRef # Controls the position (the degree of openness) of a damper + Luminance_Command: URIRef # Controls the amount of luminance delivered by a lighting system + Humidify_Command: URIRef # + Bypass_Command: URIRef # + Lead_Lag_Command: URIRef # Enables lead/lag operation + Frequency_Command: URIRef # Controls the frequency of a device's operation (e.g. rotational frequency) + Max_Frequency_Command: URIRef # Sets the maximum permitted frequency + Load_Shed_Command: URIRef # Controls load shedding behavior provided by a control system + Standby_Load_Shed_Command: URIRef # + Zone_Standby_Load_Shed_Command: URIRef # + Unoccupied_Load_Shed_Command: URIRef # + Zone_Unoccupied_Load_Shed_Command: URIRef # + Disable_Command: URIRef # Commands that disable functionality + Disable_Fixed_Temperature_Command: URIRef # Disables the use of fixed temperature temperature + Disable_Differential_Temperature_Command: URIRef # Disables the use of differential temperature control + Disable_Fixed_Enthalpy_Command: URIRef # Disables the use of fixed enthalpy control + Disable_Differential_Enthalpy_Command: URIRef # Disables the use of differential enthalpy control + Exhaust_Fan_Disable_Command: URIRef # Disables operation of the exhaust fan + Override_Command: URIRef # Controls or reports whether or not a device or control loop is in 'override' + Curtailment_Override_Command: URIRef # + On_Off_Command: URIRef # An On/Off Command controls or reports the binary status of a control loop, relay or equipment activity + Lead_On_Off_Command: URIRef # Controls the active/inactive status of the "lead" part of a lead/lag system + Start_Stop_Command: URIRef # A Start/Stop Command controls or reports the active/inactive status of a control sequence + On_Command: URIRef # An On Command controls or reports the binary 'on' status of a control loop, relay or equipment activity. It can only be used to start/activate an associated equipment or process, or determine that the related entity is 'on' + Off_Command: URIRef # An Off Command controls or reports the binary 'off' status of a control loop, relay or equipment activity. It can only be used to stop/deactivate an associated equipment or process, or determine that the related entity is 'off' + Steam_On_Off_Command: URIRef # + Cooling_Command: URIRef # Controls the amount of cooling to be delivered (typically as a proportion of total cooling output) + Enable_Command: URIRef # Commands that enable functionality + Enable_Fixed_Temperature_Command: URIRef # Enables the use of fixed temperature control + Enable_Fixed_Enthalpy_Command: URIRef # Enables the use of fixed enthalpy control + Exhaust_Fan_Enable_Command: URIRef # Enables operation of the exhaust fan + Stage_Enable_Command: URIRef # A point representing a discrete stage which the equipment should be operating at. The desired stage number should be identified by an entity property + Enable_Differential_Temperature_Command: URIRef # Enables the use of differential temperature control + Run_Enable_Command: URIRef # + VFD_Enable_Command: URIRef # Enables operation of a variable frequency drive + System_Enable_Command: URIRef # Enables operation of a system + Chilled_Water_System_Enable_Command: URIRef # Enables operation of the chilled water system + Hot_Water_System_Enable_Command: URIRef # Enables operation of the hot water system + Domestic_Hot_Water_System_Enable_Command: URIRef # Enables operation of the domestic hot water system + Enable_Differential_Enthalpy_Command: URIRef # Enables the use of differential enthalpy control + Reset_Command: URIRef # Commands that reset a flag, property or value to its default + Fault_Reset_Command: URIRef # Clears a fault status + Speed_Reset_Command: URIRef # + Filter_Reset_Command: URIRef # + Damper_Command: URIRef # Controls properties of dampers + Measurable: URIRef # + Quantity: URIRef # + Substance: URIRef # + Solid: URIRef # one of the three states or phases of matter characterized by stability of dimensions, relative incompressibility, and molecular motion held to limited oscillation. + Ice: URIRef # Water in its solid form + Frost: URIRef # frost formed on the cold surface (tubes, plates) of a cooling coil. + Hail: URIRef # pellets of frozen rain which fall in showers from cumulonimbus clouds. + Fluid: URIRef # substance, as a liquid or gas, that is capable of flowing and that changes shape when acted on by a force. + Liquid: URIRef # state of matter intermediate between crystalline substances and gases in which the volume of a substance, but not the shape, remains relatively constant. + Water: URIRef # transparent, odorless, tasteless liquid; a compound of hydrogen and oxygen (H2O), containing 11.188% hydrogen and 88.812% oxygen by mass; freezing at 32°F (0°C); boiling near 212°F (100°C). + Supply_Water: URIRef # + Supply_Hot_Water: URIRef # + Supply_Chilled_Water: URIRef # + Return_Water: URIRef # The water is a system after it is used in a heat transfer cycle + Return_Hot_Water: URIRef # + Discharge_Water: URIRef # + Discharge_Chilled_Water: URIRef # + Discharge_Hot_Water: URIRef # + Hot_Water: URIRef # Hot water used for HVAC heating or supply to hot taps + Makeup_Water: URIRef # Water used used to makeup water loss through leaks, evaporation, or blowdown + Domestic_Water: URIRef # A collection of equipment that transport and regulate domestic water among each other + Domestic_Water: URIRef # Tap water for drinking, washing, cooking, and flushing of toliets + Potable_Water: URIRef # Water that is safe to drink + Collection_Basin_Water: URIRef # Water transiently collected and directed to the sump or pump suction line, typically integral with a cooling tower + Entering_Water: URIRef # Water that is entering a piece of equipment or system + Bypass_Water: URIRef # Water that circumvents a piece of equipment or system + Deionized_Water: URIRef # Water which has been purified by removing its ions (constituting the majority of non-particulate contaminants) + Blowdown_Water: URIRef # Water expelled from a system to remove mineral build up + Condenser_Water: URIRef # Water used used to remove heat through condensation + Supply_Condenser_Water: URIRef # In a condenser water loop, this is water being brought to the condenser side of a heat-rejection device (e.g. chiller). It is the 'cold' side. + Return_Condenser_Water: URIRef # In a condenser water loop, this is water being brought away from the condenser side of a heat-rejection device (e.g. chiller). It is the 'warm' side. + Leaving_Water: URIRef # Water that is leaving a piece of equipment or system + Chilled_Water: URIRef # water used as a cooling medium (particularly in air-conditioning systems or in processes) at below ambient temperature. + Oil: URIRef # a viscous liquid derived from petroleum, especially for use as a fuel or lubricant. + Fuel_Oil: URIRef # Petroleum based oil burned for energy + Gasoline: URIRef # Petroleum derived liquid used as a fuel source + Liquid_CO2: URIRef # Carbon Dioxide in the liquid phase + Glycol: URIRef # + Gas: URIRef # state of matter in which substances exist in the form of nonaggregated molecules and which, within acceptable limits of accuracy, satisfy the ideal gas laws; usually a highly superheated vapor. See [[state]]. + CO2: URIRef # Carbon Dioxide in the vapor phase + Steam: URIRef # water in the vapor phase. + Air: URIRef # the invisible gaseous substance surrounding the earth, a mixture mainly of oxygen and nitrogen. + Zone_Air: URIRef # air inside a defined zone (e.g., corridors). + Supply_Air: URIRef # (1) air delivered by mechanical or natural ventilation to a space, composed of any combination of outdoor air, recirculated air, or transfer air. (2) air entering a space from an air-conditioning, heating, or ventilating apparatus for the purpose of comfort conditioning. Supply air is generally filtered, fan forced, and either heated, cooled, humidified, or dehumidified as necessary to maintain specified conditions. Only the quantity of outdoor air within the supply airflow may be used as replacement air. + Exhaust_Air: URIRef # air that must be removed from a space due to contaminants, regardless of pressurization + Building_Air: URIRef # air contained within a building + Bypass_Air: URIRef # air in a bypass duct, used to relieve static pressure + Outside_Air: URIRef # air external to a defined zone (e.g., corridors). + Discharge_Air: URIRef # the air exiting the registers (vents). + Mixed_Air: URIRef # (1) air that contains two or more streams of air. (2) combined outdoor air and recirculated air. + Return_Air: URIRef # air removed from a space to be recirculated or exhausted. Air extracted from a space and totally or partially returned to an air conditioner, furnace, or other heating, cooling, or ventilating system. + Natural_Gas: URIRef # Fossil fuel energy source consisting largely of methane and other hydrocarbons + CO: URIRef # Carbon Monoxide in the vapor phase + Equipment: URIRef # devices that serve all or part of the building and may include electric power, lighting, transportation, or service water heating, including, but not limited to, furnaces, boilers, air conditioners, heat pumps, chillers, water heaters, lamps, luminaires, ballasts, elevators, escalators, or other devices or installations. + Solar_Thermal_Collector: URIRef # A type of solar panels that converts solar radiation into thermal energy. + PVT_Panel: URIRef # A type of solar panels that convert solar radiation into usable thermal and electrical energy + Electrical_Equipment: URIRef # + Energy_Storage: URIRef # Devices or equipment that store energy in its various forms + Battery: URIRef # A container that stores chemical energy that can be converted into electricity and used as a source of power + Inverter: URIRef # A device that changes direct current into alternating current + Switchgear: URIRef # A main disconnect or service disconnect feeds power to a switchgear, which then distributes power to the rest of the building through smaller amperage-rated disconnects. + Disconnect_Switch: URIRef # Building power is most commonly provided by utility company through a master disconnect switch (sometimes called a service disconnect) in the main electrical room of a building. The Utility Company provided master disconnect switch often owns or restricts access to this switch. There can also be other cases where a disconnect is placed into an electrical system to allow service cut-off to a portion of the building. + PlugStrip: URIRef # A device containing a block of electrical sockets allowing multiple electrical devices to be powered from a single electrical socket. + Breaker_Panel: URIRef # Breaker Panel distributes power into various end-uses. + Motor_Control_Center: URIRef # The Motor Control Center is a specialized type of switchgear which provides electrical power to major mechanical systems in the building such as HVAC components. + Bus_Riser: URIRef # Bus Risers are commonly fed from a switchgear and rise up through a series of floors to the main power distribution source for each floor. + Transformer: URIRef # A Transformer is usually fed by a high-voltage source and then steps down the voltage to a lower-voltage feed for low-voltage application (such as lights). Transformers also can step up voltage, but this generally does not apply to in building distribution. + Safety_Equipment: URIRef # + First_Aid_Kit: URIRef # + Automated_External_Defibrillator: URIRef # + AED: URIRef # + Emergency_Wash_Station: URIRef # + Eye_Wash_Station: URIRef # + Safety_Shower: URIRef # + Drench_Hose: URIRef # + Fire_Safety_Equipment: URIRef # + Fire_Control_Panel: URIRef # A panel-mounted device that provides status and control of a fire safety system + Steam_Distribution: URIRef # Utilize a steam distribution source to represent how steam is distributed across multiple destinations + Water_Distribution: URIRef # Utilize a water distribution source to represent how water is distributed across multiple destinations (pipes) + Security_Equipment: URIRef # + Video_Surveillance_Equipment: URIRef # + NVR: URIRef # + Network_Video_Recorder: URIRef # + Surveillance_Camera: URIRef # + Intrusion_Detection_Equipment: URIRef # + Access_Control_Equipment: URIRef # + Access_Reader: URIRef # + Intercom_Equipment: URIRef # + Emergency_Phone: URIRef # + Video_Intercom: URIRef # + PV_Panel: URIRef # An integrated assembly of interconnected photovoltaic cells designed to deliver a selected level of working voltage and current at its output terminals packaged for protection against environment degradation and suited for incorporation in photovoltaic power systems. + Louver: URIRef # Device consisting of an assembly of parallel sloping vanes, intended to permit the passage of air while providing a measure of protection against environmental influences + HVAC_Equipment: URIRef # See Heating_Ventilation_Air_Conditioning_System + Air_Handler_Unit: URIRef # Assembly consisting of sections containing a fan or fans and other necessary equipment to perform one or more of the following functions: circulating, filtration, heating, cooling, heat recovery, humidifying, dehumidifying, and mixing of air. Is usually connected to an air-distribution system. + Thermostat: URIRef # An automatic control device used to maintain temperature at a fixed or adjustable setpoint. + Boiler: URIRef # A closed, pressure vessel that uses fuel or electricity for heating water or other fluids to supply steam or hot water for heating, humidification, or other applications. + Natural_Gas_Boiler: URIRef # A closed, pressure vessel that uses natural gas for heating water or other fluids to supply steam or hot water for heating, humidification, or other applications. + Condensing_Natural_Gas_Boiler: URIRef # A closed, pressure vessel that uses natural gas and heat exchanger that capture and reuse any latent heat for heating water or other fluids to supply steam or hot water for heating, humidification, or other applications. + Noncondensing_Natural_Gas_Boiler: URIRef # A closed, pressure vessel that uses natural gas with no system to capture latent heat for heating water or other fluids to supply steam or hot water for heating, humidification, or other applications. + Electric_Boiler: URIRef # A closed, pressure vessel that uses electricity for heating water or other fluids to supply steam or hot water for heating, humidification, or other applications. + Compressor: URIRef # (1) device for mechanically increasing the pressure of a gas. (2) often described as being either open, hermetic, or semihermetic to describe how the compressor and motor drive is situated in relation to the gas or vapor being compressed. Types include centrifugal, axial flow, reciprocating, rotary screw, rotary vane, scroll, or diaphragm. 1. device for mechanically increasing the pressure of a gas. 2. specific machine, with or without accessories, for compressing refrigerant vapor. + HX: URIRef # See Heat_Exchanger + Cooling_Tower: URIRef # A cooling tower is a heat rejection device that rejects waste heat to the atmosphere through the cooling of a water stream to a lower temperature. Cooling towers may either use the evaporation of water to remove process heat and cool the working fluid to near the wet-bulb air temperature or, in the case of closed circuit dry cooling towers, rely solely on air to cool the working fluid to near the dry-bulb air temperature. + Air_Handling_Unit: URIRef # + Valve: URIRef # A device that regulates, directs or controls the flow of a fluid by opening, closing or partially obstructing various passageways + Water_Valve: URIRef # A valve that modulates the flow of water + Chilled_Water_Valve: URIRef # A valve that modulates the flow of chilled water + Condenser_Water_Valve: URIRef # A valve that modulates the flow of condenser water + Hot_Water_Valve: URIRef # A valve regulating the flow of hot water + Domestic_Hot_Water_Valve: URIRef # A valve regulating the flow of domestic hot water + Preheat_Hot_Water_Valve: URIRef # + Makeup_Water_Valve: URIRef # A valve regulating the flow of makeup water into a water holding tank, e.g. a cooling tower, hot water tank + Steam_Valve: URIRef # + Heating_Valve: URIRef # A valve that controls air temperature by modulating the amount of hot water flowing through a heating coil + Reheat_Valve: URIRef # A valve that controls air temperature by modulating the amount of hot water flowing through a reheat coil + Return_Heating_Valve: URIRef # A valve installed on the return side of a heat exchanger + Isolation_Valve: URIRef # A valve that stops the flow of a fluid, usually for maintenance or safety purposes + Condenser_Water_Isolation_Valve: URIRef # An isolation valve installed in the condenser water loop + Bypass_Valve: URIRef # A type of valve installed in a bypass pipeline + Differential_Pressure_Bypass_Valve: URIRef # A 2-way, self contained proportional valve with an integral differential pressure adjustment setting. + Condenser_Water_Bypass_Valve: URIRef # A valve installed in a bypass line of a condenser water loop + Gas_Valve: URIRef # + Cooling_Valve: URIRef # A valve that controls air temperature by modulating the amount of cold water flowing through a cooling coil + Humidifier: URIRef # A device that adds moisture to air or other gases + Fan: URIRef # Any device with two or more blades or vanes attached to a rotating shaft used to produce an airflow for the purpose of comfort, ventilation, exhaust, heating, cooling, or any other gaseous transport. + Cooling_Tower_Fan: URIRef # A fan that pulls air through a cooling tower and across the louvers where the water falls to aid in heat exchange by the process of evaporation + Exhaust_Fan: URIRef # Fan moving exhaust air -- air that must be removed from a space due to contaminants + Return_Fan: URIRef # Fan moving return air -- air that is circulated from the building back into the HVAC system + Booster_Fan: URIRef # Fan activated to increase airflow beyond what is provided by the default configuration + Fresh_Air_Fan: URIRef # Fan moving fresh air -- air that is supplied into the building from the outdoors + Ceiling_Fan: URIRef # A fan installed on the ceiling of a room for the purpose of air circulation + Discharge_Fan: URIRef # Fan moving air discharged from HVAC vents + Relief_Fan: URIRef # A fan that is a component of a Relief Air System, ensuring building doesn't become over-pressurised + Standby_Fan: URIRef # Fan that is activated as part of a lead/lag operation or when a primary fan raises an alarm + Supply_Fan: URIRef # Fan moving supply air -- air that is supplied from the HVAC system into the building + Filter: URIRef # Device to remove gases from a mixture of gases or to remove solid material from a fluid + Mixed_Air_Filter: URIRef # A filter that is applied to the mixture of recirculated and outside air + Intake_Air_Filter: URIRef # Filters air intake + Final_Filter: URIRef # The last, high-efficiency filter installed in a sequence to remove the finest particulates from the substance being filtered + Pre_Filter: URIRef # A filter installed in front of a more efficient filter to extend the life of the more expensive higher efficiency filter + Return_Air_Filter: URIRef # Filters return air + Heat_Exchanger: URIRef # A heat exchanger is a piece of equipment built for efficient heat transfer from one medium to another. The media may be separated by a solid wall to prevent mixing or they may be in direct contact (BEDES) + Condenser_Heat_Exchanger: URIRef # A heat exchanger in which the primary heat transfer vapor changes its state to a liquid phase. + Evaporative_Heat_Exchanger: URIRef # + Heat_Wheel: URIRef # A rotary heat exchanger positioned within the supply and exhaust air streams of an air handling system in order to recover heat energy + Coil: URIRef # Cooling or heating element made of pipe or tube that may or may not be finned and formed into helical or serpentine shape (ASHRAE Dictionary) + Heating_Coil: URIRef # A heating element typically made of pipe, tube or wire that emits heat. Typically filled with hot water, or, in the case of wire, uses electricity. + Hot_Water_Coil: URIRef # A heating element typically made of pipe, tube or wire that emits heat that is filled with hot water. + Direct_Expansion_Heating_Coil: URIRef # + Cooling_Coil: URIRef # A cooling element made of pipe or tube that removes heat from equipment, machines or airflows. Typically filled with either refrigerant or cold water. + Chilled_Water_Coil: URIRef # A cooling element made of pipe or tube that removes heat from equipment, machines or airflows that is filled with chilled water. + Direct_Expansion_Cooling_Coil: URIRef # + Pump: URIRef # Machine for imparting energy to a fluid, causing it to do work, drawing a fluid into itself through an entrance port, and forcing the fluid out through an exhaust port. + Water_Pump: URIRef # A pump that performs work on water + Condenser_Water_Pump: URIRef # A pump that is part of a condenser system; the pump circulates condenser water from the chiller back to the cooling tower + Hot_Water_Pump: URIRef # A pump that performs work on hot water; typically part of a hot water system + Chilled_Water_Pump: URIRef # A pump that performs work on chilled water; typically part of a chilled water system + Terminal_Unit: URIRef # A device that regulates the volumetric flow rate and/or the temperature of the controlled medium. + VAV: URIRef # See Variable_Air_Volume_Box + Air_Diffuser: URIRef # A device that is a component of the air distribution system that controls the delivery of conditioned and/or ventilating air into a room + Displacement_Flow_Air_Diffuser: URIRef # An air diffuser that is designed for low discharge air speeds to minimize turbulence and induction of room air. This diffuser is used with displacement ventilation systems. + Jet_Nozzle_Air_Diffuser: URIRef # An air diffuser that is designed to produce high velocity discharge air stream to throw the air over a large distance or target the air stream to a localize area + Laminar_Flow_Air_Diffuser: URIRef # An air diffuser that is designed for low discharge air speeds to provide uniform and unidirectional air pattern which minimizes room air entrainment + FCU: URIRef # See Fan_Coil_Unit + Fan_Coil_Unit: URIRef # Terminal device consisting of a heating and/or cooling heat exchanger or 'coil' and fan that is used to control the temperature in the space where it is installed + Constant_Air_Volume_Box: URIRef # A terminal unit for which supply air flow rate is constant and the supply air temperature is varied to meet thermal load + Variable_Air_Volume_Box: URIRef # A device that regulates the volume and temperature of air delivered to a zone by opening or closing a damper + Variable_Air_Volume_Box_With_Reheat: URIRef # A VAV box with a reheat coil mounted on the discharge end of the unit that can heat the air delivered to a zone + RVAV: URIRef # See Variable_Air_Volume_Box_With_Reheat + CAV: URIRef # + Radiant_Panel: URIRef # A temperature-controlled surface that provides fifty percent (50%) or more of the design heat transfer by thermal radiation. + Thermally_Activated_Building_System_Panel: URIRef # Radiant panel heating and cooling system where the energy heat source or sink is embedded in the building structure such as in slabs and walls. + Embedded_Surface_System_Panel: URIRef # Radiant panel heating and cooling system where the energy heat source or sink is embedded in a radiant layer which is thermally insulated from the building structure. + TABS_Panel: URIRef # See Thermally_Activated_Building_System_Panel + Radiant_Ceiling_Panel: URIRef # Radiant panel heating and cooling system that are usually made from metal and suspended under the ceiling or insulated from the building structure. + RC_Panel: URIRef # See Radiant_Ceiling_Panel + ESS_Panel: URIRef # See Embedded_Surface_System_Panel + Radiator: URIRef # Heat exchangers designed to transfer thermal energy from one medium to another + Hot_Water_Radiator: URIRef # Radiator that uses hot water + Hot_Water_Baseboard_Radiator: URIRef # Hydronic heating device located at or near the floor + Electric_Radiator: URIRef # Electric heating device + Electric_Baseboard_Radiator: URIRef # Electric heating device located at or near the floor + Steam_Radiator: URIRef # Radiator that uses steam + Steam_Baseboard_Radiator: URIRef # Steam heating device located at or near the floor + Baseboard_Radiator: URIRef # Steam, hydronic, or electric heating device located at or near the floor. + Induction_Unit: URIRef # A device with an primary air connection and integrated coil and condensate pan that performs sensible and latent cooling of a space. Essentially an Active Chilled Beam with a built in condensate pan. + Chilled_Beam: URIRef # A device with an integrated coil that performs sensible heating of a space via circulation of room air. Chilled Beams are not designed to perform latent cooling; see Induction Units. Despite their name, Chilled Beams may perform heating or cooling of a space depending on their configuration. + Active_Chilled_Beam: URIRef # A Chilled Beam with an integral primary air connection that induces air flow through the device. + Passive_Chilled_Beam: URIRef # A chilled beam that does not have an integral air supply and instead relies on natural convection to draw air through the device. + Damper: URIRef # Element inserted into an air-distribution system or element of an air-distribution system permitting modification of the air resistance of the system and consequently changing the airflow rate or shutting off the airflow. + Exhaust_Damper: URIRef # A damper that modulates the flow of exhaust air + Outside_Damper: URIRef # A damper that modulates the flow of outside air + Return_Damper: URIRef # A damper that modulates the flow of return air + Economizer_Damper: URIRef # A damper that is part of an economizer that is used to module the flow of air + Relief_Damper: URIRef # A damper that is a component of a Relief Air System, ensuring building doesn't become over-pressurised + Mixed_Damper: URIRef # A damper that modulates the flow of the mixed outside and return air streams + AHU: URIRef # Assembly consisting of sections containing a fan or fans and other necessary equipment to perform one or more of the following functions: circulating, filtration, heating, cooling, heat recovery, humidifying, dehumidifying, and mixing of air. Is usually connected to an air-distribution system. + RTU: URIRef # see Rooftop_Unit + MAU: URIRef # See Makeup_Air_Unit + Dedicated_Outdoor_Air_System_Unit: URIRef # A device that conditions and delivers 100% outdoor air to its assigned spaces. It decouples air-conditioning of the outdoor air, usually used to provide minimum outdoor air ventilation, from conditioning of the internal loads. + Rooftop_Unit: URIRef # Packaged air conditioner mounted on a roof, the conditioned air being discharged directly into the rooms below or through a duct system. + PAU: URIRef # A type of AHU, use to pre-treat the outdoor air before feed to AHU + Makeup_Air_Unit: URIRef # A device designed to condition ventilation air introduced into a space or to replace air exhausted from a process or general area exhaust. The device may be used to prevent negative pressure within buildings or to reduce airborne contaminants in a space. + DOAS: URIRef # See Dedicated_Outdoor_Air_System_Unit + CRAC: URIRef # + Standby_CRAC: URIRef # A CRAC that is activated as part of a lead/lag operation or when an alarm occurs in a primary unit + Economizer: URIRef # Device that, on proper variable sensing, initiates control signals or actions to conserve energy. A control system that reduces the mechanical heating and cooling requirement. + Space_Heater: URIRef # A heater used to warm the air in an enclosed area, such as a room or office + Computer_Room_Air_Conditioning: URIRef # A device that monitors and maintains the temperature, air distribution and humidity in a network room or data center. + Fume_Hood: URIRef # A fume-collection device mounted over a work space, table, or shelf and serving to conduct unwanted gases away from the area enclosed. + Chiller: URIRef # Refrigerating machine used to transfer heat between fluids. Chillers are either direct expansion with a compressor or absorption type. + Centrifugal_Chiller: URIRef # A chiller that uses the vapor compression cycle to chill water. It throws off the heat collected from the chilled water plus the heat from the compressor to a water loop + Absorption_Chiller: URIRef # A chiller that utilizes a thermal or/and chemical process to produce the refrigeration effect necessary to provide chilled water. There is no mechanical compression of the refrigerant taking place within the machine, as occurs within more traditional vapor compression type chillers. + Condenser: URIRef # A heat exchanger in which the primary heat transfer vapor changes its state to a liquid phase. + Air_Plenum: URIRef # A component of the HVAC the receives air from the air handling unit or room to distribute or exhaust to or from the building + Return_Air_Plenum: URIRef # A component of the HVAC the receives air from the room to recirculate or exhaust to or from the building + Supply_Air_Plenum: URIRef # A component of the HVAC the receives air from the air handling unit to distribute to the building + Underfloor_Air_Plenum: URIRef # An open space between a structural concrete slab and the underside of a raised access floor system that connects to an air handling unit to receive conditioned and/or ventilating air before delivery to the room(s) + Lighting_Equipment: URIRef # + Lighting: URIRef # + Luminaire: URIRef # A complete lighting unit consisting of a lamp or lamps and ballast(s) (when applicable) together with the parts designed to distribute the light, to position and protect the lamps, and to connect the lamps to the power supply. + Luminaire_Driver: URIRef # A power source for a luminaire + Interface: URIRef # A device that provides an occupant control over a lighting system + Touchpanel: URIRef # A switch used to operate all or part of a lighting installation that uses a touch-based mechanism (typically resistive or capacitive) rather than a mechanical actuator + Switch: URIRef # A switch used to operate all or part of a lighting installation + Dimmer: URIRef # A switch providing continuous control over all or part of a lighting installation; typically potentiometer-based + Gas_Distribution: URIRef # Utilize a gas distribution source to represent how gas is distributed across multiple destinations + Weather_Station: URIRef # A dedicated weather measurement station + Meter: URIRef # A device that measure usage or consumption of some media --- typically a form energy or power. + Gas_Meter: URIRef # A meter that measures the usage or consumption of gas + Building_Gas_Meter: URIRef # A meter that measures the usage or consumption of gas of a whole building + Electrical_Meter: URIRef # A meter that measures the usage or consumption of electricity + Building_Electrical_Meter: URIRef # A meter that measures the usage or consumption of electricity of a whole building + Building_Meter: URIRef # A meter that measures usage or consumption of some media for a whole building + Building_Hot_Water_Meter: URIRef # A meter that measures the usage or consumption of hot water of a whole building + Building_Water_Meter: URIRef # A meter that measures the usage or consumption of water of a whole building + Building_Chilled_Water_Meter: URIRef # A meter that measures the usage or consumption of chilled water of a whole building + Thermal_Power_Meter: URIRef # A standalone thermal power meter + Water_Meter: URIRef # A meter that measures the usage or consumption of water + Hot_Water_Meter: URIRef # A meter that measures the usage or consumption of hot water + Chilled_Water_Meter: URIRef # A meter that measures the usage or consumption of chilled water + Camera: URIRef # + Motor: URIRef # A machine in which power is applied to do work by the conversion of various forms of energy into mechanical force and motion. + Variable_Frequency_Drive: URIRef # Electronic device that varies its output frequency to vary the rotating speed of a motor, given a fixed input frequency. Used with fans or pumps to vary the flow in the system as a function of a maintained pressure. + VFD: URIRef # Electronic device that varies its output frequency to vary the rotating speed of a motor, given a fixed input frequency. Used with fans or pumps to vary the flow in the system as a function of a maintained pressure. + Pump_VFD: URIRef # Variable-frequency drive for pumps + Heat_Wheel_VFD: URIRef # A VFD that drives a heat wheel + Fan_VFD: URIRef # Variable-frequency drive for fans + Furniture: URIRef # Movable objects intended to support various human activities such as seating, eating and sleeping + Stage_Riser: URIRef # A low platform in a space or on a stage + Water_Heater: URIRef # An apparatus for heating and usually storing hot water + Collection_Basin_Water_Heater: URIRef # Basin heaters prevent cold water basin freeze-up, e.g. in cooling towers, closed circuit fluid coolers, or evaporative condensers + Elevator: URIRef # A device that provides vertical transportation between floors, levels or decks of a building, vessel or other structure + Collection: URIRef # + System: URIRef # A System is a combination of equipment and auxiliary devices (e.g., controls, accessories, interconnecting means, and termi­nal elements) by which energy is transformed so it performs a specific function such as HVAC, service water heating, or lighting. (ASHRAE Dictionary). + Heating_Ventilation_Air_Conditioning_System: URIRef # The equipment, distribution systems and terminals that provide, either collectively or individually, the processes of heating, ventilating or air conditioning to a building or portion of a building + Water_System: URIRef # The equipment, devices and conduits that handle the production and distribution of water in a building + Chilled_Water_System: URIRef # The equipment, devices and conduits that handle the production and distribution of chilled water in a building + Condenser_Water_System: URIRef # A heat rejection system consisting of (typically) cooling towers, condenser water pumps, chillers and the piping connecting the components + Hot_Water_System: URIRef # The equipment, devices and conduits that handle the production and distribution of hot water in a building + Reheat_Hot_Water_System: URIRef # + Preheat_Hot_Water_System: URIRef # + Radiation_Hot_Water_System: URIRef # + Heat_Recovery_Hot_Water_System: URIRef # + Steam_System: URIRef # The equipment, devices and conduits that handle the production and distribution of steam in a building + Air_System: URIRef # The equipment, distribution systems and terminals that introduce or exhaust, either collectively or individually, the air into and from the building + Ventilation_Air_System: URIRef # The equipment, distribution systems and terminals that introduce or exhaust, either collectively or individually, the air used for the ventilation system of the building + Ventilation_Air_System: URIRef # The equipment, devices, and conduits that handle the introduction and distribution of ventilation air in the building + Shading_System: URIRef # Devices that can control daylighting through various means + Gas_System: URIRef # + Domestic_Hot_Water_System: URIRef # The equipment, devices and conduits that handle the production and distribution of domestic hot water in a building + Lighting_System: URIRef # The equipment, devices and interfaces that serve or are a part of the lighting subsystem in a building + Safety_System: URIRef # + Fire_Safety_System: URIRef # A system containing devices and equipment that monitor, detect and suppress fire hazards + Emergency_Air_Flow_System: URIRef # + Emergency_Power_Off_System: URIRef # A system that can power down a single piece of equipment or a single system from a single point + HVAC_System: URIRef # See Heating_Ventilation_Air_Conditioning_System + Electrical_System: URIRef # Devices that serve or are part of the electrical subsystem in the building + Energy_System: URIRef # A collection of devices that generates, stores or transports electricity + Energy_Generation_System: URIRef # A collection of devices that generates electricity + PV_Generation_System: URIRef # A collection of photovoltaic devices that generates energy + Energy_Storage_System: URIRef # A collection of devices that stores electricity + Battery_Energy_Storage_System: URIRef # A collection of batteries that provides energy storage, along with their supporting equipment + Portfolio: URIRef # A collection of sites + PV_Array: URIRef # + Photovoltaic_Array: URIRef # A collection of photovoltaic panels + Loop: URIRef # A collection of connected equipment; part of a System + Air_Loop: URIRef # The set of connected equipment serving one path of air + Water_Loop: URIRef # A collection of equipment that transport and regulate water among each other + Hot_Water_Loop: URIRef # A collection of equipment that transport and regulate hot water among each other + Domestic_Water_Loop: URIRef # + Chilled_Water_Loop: URIRef # A collection of equipment that transport and regulate chilled water among each other + Location: URIRef # + Site: URIRef # A geographic region containing 0 or more buildings. Typically used as the encapsulating location for a collection of Brick entities through the hasSite/isSiteOf relationships + Wing: URIRef # A wing is part of a building – or any feature of a building – that is subordinate to the main, central structure. + Outdoor_Area: URIRef # A class of spaces that exist outside of a building + Bench_Space: URIRef # For areas of play in a stadium, the area for partcipants and referees by the side of the field + Information_Area: URIRef # An information booth or kiosk where visitors would look for information + Field_Of_Play: URIRef # The area of a stadium where athletic events occur, e.g. the soccer pitch + Storey: URIRef # + Space: URIRef # A part of the physical world or a virtual world whose 3D spatial extent is bounded actually or theoretically, and provides for certain functions within the zone it is contained in. + Entrance: URIRef # The location and space of a building where people enter and exit the building + Ticketing_Booth: URIRef # A room or space used to sell or distribute tickets to events at a venue + Tunnel: URIRef # An enclosed space that connects buildings. Often underground + Room: URIRef # Base class for all more specific room types. + Laboratory: URIRef # facility acceptable to the local, national, or international recognized authority having jurisdiction and which provides uniform testing and examination procedures and standards for meeting design, manufacturing, and factory testing requirements. + Freezer: URIRef # cold chamber usually kept at a temperature of 22°F to 31°F (–5°C to –1°C), with high-volume air circulation. + Environment_Box: URIRef # (also known as climatic chamber), enclosed space designed to create a particular environment. + Cold_Box: URIRef # in a gas separation unit, the insulated section that contains the low-temperature heat exchangers and distillation columns. + Hot_Box: URIRef # hot air chamber forming part of an air handler. + Storage_Room: URIRef # A class of spaces used for storage + Hazardous_Materials_Storage: URIRef # A storage space set aside (usually with restricted access) for the storage of materials that can be hazardous to living beings or the environment + Waste_Storage: URIRef # A room used for storing waste such as trash or recycling + Prayer_Room: URIRef # A room set aside for prayer + Telecom_Room: URIRef # A class of spaces used to support telecommuncations and IT equipment + Switch_Room: URIRef # A telecommuncations room housing network switches + Distribution_Frame: URIRef # A class of spaces where the cables carrying signals meet and connect, e.g. a wiring closet or a broadcast downlink room + IDF: URIRef # An room for an intermediate distribution frame, where cables carrying signals from the main distrubtion frame terminate and then feed out to endpoints + MDF: URIRef # A room for the Main Distribution Frame, the central place of a building where cables carrying signals meet and connect to the outside world + Equipment_Room: URIRef # A telecommunications room where equipment that serves the building is stored + TETRA_Room: URIRef # A room used for local two-way radio networks, e.g. the portable radios carried by facilities staff + Massage_Room: URIRef # Usually adjunct to an athletic facility, a private/semi-private space where massages are performed + Janitor_Room: URIRef # A room set aside for the storage of cleaning equipment and supplies + Workshop: URIRef # A space used to house equipment that can be used to repair or fabricate things + Loading_Dock: URIRef # A part of a facility where delivery trucks can load and unload. Usually partially enclosed with specific traffic lanes leading to the dock + Hospitality_Box: URIRef # A room at a stadium, usually overlooking the field of play, that is physical separate from the other seating at the venue + Security_Service_Room: URIRef # A class of spaces used by the security staff of a facility + Detention_Room: URIRef # A space for the temporary involuntary confinement of people + Reception: URIRef # A space, usually in a lobby, where visitors to a building or space can go to after arriving at a building and inform building staff that they have arrived + Mail_Room: URIRef # A room where mail is recieved and sorted for distribution to the rest of the building + Control_Room: URIRef # A space from which operations are managed + Breakroom: URIRef # A space for people to relax while not working + Server_Room: URIRef # + Library: URIRef # A place for the storage and/or consumption of physical media, e.g. books, periodicals, and DVDs/CDs + Rest_Room: URIRef # A room that provides toilets and washbowls. Alternate spelling of Restroom + Ablutions_Room: URIRef # A room for performing cleansing rituals before prayer + Exercise_Room: URIRef # An indoor room used for exercise and physical activities + Sports_Service_Room: URIRef # A class of spaces used in the support of sports + Copy_Room: URIRef # A room set aside for common office equipment, including printers and copiers + Office: URIRef # A class of rooms dedicated for work or study + Enclosed_Office: URIRef # A space for individuals to work with walls and a door + Team_Room: URIRef # An office used by multiple team members for specific work tasks. Distinct from Conference Room + Private_Office: URIRef # An office devoted to a single individual, with walls and door + Shared_Office: URIRef # An office used by multiple people + Open_Office: URIRef # An open space used for work or study by mulitple people. Usuaully subdivided into cubicles or desks + Cubicle: URIRef # A smaller space set aside for an individual, but not with a door and without full-height walls + Conference_Room: URIRef # A space dedicated in which to hold a meetings + Wardrobe: URIRef # Storage for clothing, costumes, or uniforms + Break_Room: URIRef # A space for people to relax while not working + Media_Room: URIRef # A class of spaces related to the creation of media + Broadcast_Room: URIRef # A space to organize and manage a broadcast. Separate from studio + Media_Production_Room: URIRef # A enclosed space used by media professionals for the production of media + Studio: URIRef # A room used for the production or media, usually with either a specialized set or a specialized sound booth for recording + Food_Service_Room: URIRef # A space used in the production, storage, serving, or cleanup of food and beverages + Concession: URIRef # A space to sell food and beverages. Usually embedded in a larger space and does not include a space where people consume their purchases + Medical_Room: URIRef # A class of rooms used for medical purposes + First_Aid_Room: URIRef # A room for a person with minor injuries can be treated or temporarily treated until transferred to a more advanced medical facility + Restroom: URIRef # A room that provides toilets and washbowls. + Service_Room: URIRef # A class of spaces related to the operations of building subsystems, e.g. HVAC, electrical, IT, plumbing, etc + Mechanical_Room: URIRef # A class of service rooms where mechanical equipment (HVAC) operates + Pump_Room: URIRef # A mechanical room that houses pumps + Plumbing_Room: URIRef # A service room devoted to the operation and routing of water in a building. Usually distinct from the HVAC subsystems. + Electrical_Room: URIRef # A class of service rooms that house electrical equipment for a building + Transformer_Room: URIRef # An electrical room where electricity enters and is transformed to different voltages and currents by the equipment contained in the room + Generator_Room: URIRef # A room for electrical equipment, specifically electrical generators. + Battery_Room: URIRef # A room used to hold batteries for backup power + Office_Kitchen: URIRef # A common space, usually near or in a breakroom, where minor food preperation occurs + Retail_Room: URIRef # A space set aside for retail in a larger establishment, e.g. a gift shop in a hospital + Shower: URIRef # A space containing showers, usually adjacent to an athletic or execise area + Water_Tank: URIRef # A space used to hold water + Vertical_Space: URIRef # A class of spaces used to connect multiple floors or levels.. + Staircase: URIRef # A vertical space containing stairs + Elevator_Space: URIRef # The vertical space in whcih an elevator ascends and descends + Elevator_Shaft: URIRef # The vertical space in which an elevator ascends and descends + Riser: URIRef # A vertical shaft indented for installing building infrastructure e.g., electrical wire, network communication wire, plumbing, etc + Gatehouse: URIRef # The standalone building used to manage the entrance to a campus or building grounds + Parking_Space: URIRef # An area large enough to park an individual vehicle + Media_Hot_Desk: URIRef # A non-enclosed space used by members of the media temporarily to cover an event while they are present at a venue + Common_Space: URIRef # A class of spaces that are used by multiple people at the same time + Cafeteria: URIRef # A space to serve food and beverages + Lobby: URIRef # A space just after the entrance to a building or other space of a building, where visitors can wait + Visitor_Lobby: URIRef # A lobby for visitors to the building. Sometimes used to distinguish from an employee entrance looby + Employee_Entrance_Lobby: URIRef # An open space near an entrance that is typicaly only used for employees + Auditorium: URIRef # A space for performances or larger gatherings + Hallway: URIRef # A common space, used to connect other parts of a building + Lounge: URIRef # A room for lesiure activities or relaxing + Majlis: URIRef # In Arab countries, an Majlis is a private lounge where visitors are recieved and entertained + Outside: URIRef # + Floor: URIRef # A level, typically representing a horizontal aggregation of spaces that are vertically bound. (referring to IFC) + Rooftop: URIRef # + Parking_Level: URIRef # A floor of a parking structure + Basement: URIRef # The floor of a building which is partly or entirely below ground level. + Building: URIRef # An independent unit of the built environment with a characteristic spatial structure, intended to serve at least one function or user activity [ISO 12006-2:2013] + Building: URIRef # a structure wholly or partially enclosed within exterior walls, or within exterior and party walls, and a roof, affording shelter to persons, animals, or property. + Parking_Structure: URIRef # A building or part of a building devoted to vehicle parking + Region: URIRef # A unit of geographic space, usually contigious or somehow related to a geopolitical feature + Zone: URIRef # (1) a separately controlled heated or cooled space. (2) one occupied space or several occupied spaces with similar occupancy category, occupant density, zone air distribution effectiveness, and zone primary airflow per unit area. (3) space or group of spaces within a building for which the heating, cooling, or lighting requirements are sufficiently similar that desired conditions can be maintained throughout by a single controlling device. + Energy_Zone: URIRef # A space or group of spaces that are managed or monitored as one unit for energy purposes + HVAC_Zone: URIRef # a space or group of spaces, within a building with heating, cooling, and ventilating requirements, that are sufficiently similar so that desired conditions (e.g., temperature) can be maintained throughout using a single sensor (e.g., thermostat or temperature sensor). + Fire_Zone: URIRef # combustion chamber in a furnace or boiler. + Lighting_Zone: URIRef # + + # http://www.w3.org/2002/07/owl#Property + isRegulatedBy: URIRef # + value: URIRef # The basic value of an entity property + latitude: URIRef # + hasPoint: URIRef # The subject has a source of telemetry identified by the object. In some systems the source of telemetry may be represented as a digital/analog input/output point + feeds: URIRef # The subject is upstream of the object in the context of some sequential process; some media is passed between them + isPartOf: URIRef # + measures: URIRef # The subject measures a quantity or substance given by the object + timeseries: URIRef # Relates a Brick point to the TimeseriesReference that indicates where and how the data for this point is stored + hasOutputSubstance: URIRef # The subject produces or exports the given substance from its internal process + isTagOf: URIRef # + isFedBy: URIRef # + hasAddress: URIRef # To specify the address of a building. + hasAddress: URIRef # + isLocationOf: URIRef # Subject is the physical location encapsulating the object + hasTimeseriesId: URIRef # The unique identifier (primary key) for this TimeseriesReference in some database + hasLocation: URIRef # Subject is physically located in the location given by the object + hasTag: URIRef # The subject has the given tag + hasUnit: URIRef # The QUDT unit associated with this Brick entity (usually a Brick Point instance or Entity Property) + hasQUDTReference: URIRef # Points to the relevant QUDT definition + isMeasuredBy: URIRef # + regulates: URIRef # The subject contributes to or performs the regulation of the substance given by the object + isPointOf: URIRef # The subject is a source of telemetry related to the object. In some systems the source of telemetry may be represented as a digital/analog input/output point + hasAssociatedTag: URIRef # The class is associated with the given tag + feedsAir: URIRef # Passes air + hasPart: URIRef # The subject is composed in part of the entity given by the object + hasInputSubstance: URIRef # The subject receives the given substance as an input to its internal process + longitude: URIRef # + isAssociatedWith: URIRef # The tag is associated with the given class + storedAt: URIRef # A reference to where the data for this TimeseriesReference is stored + + # https://brickschema.org/schema/Brick#EntityProperty + powerComplexity: URIRef # Entity has this power complexity + azimuth: URIRef # (Horizontal) angle between a projected vector and a reference vector (typically a compass bearing). The projected vector usually indicates the direction of a face or plane. + temperatureCoefficientofPmax: URIRef # The % change in power output for every degree celsius that the entity is hotter than 25 degrees celsius + volume: URIRef # Entity has 3-dimensional volume + ratedModuleConversionEfficiency: URIRef # The *rated* percentage of sunlight that is converted into usable power, as measured using Standard Test Conditions (STC): 1000 W/sqm irradiance, 25 degC panel temperature, no wind + buildingPrimaryFunction: URIRef # Enumerated string applied to a site record to indicate the building's primary function. The list of primary functions is derived from the US Energy Star program (adopted from Project Haystack) + netArea: URIRef # Entity has net 2-dimensional area + currentFlowType: URIRef # The current flow type of the entity + ratedPowerOutput: URIRef # The nominal rated power output of the entity + coordinates: URIRef # The location of an entity in latitude/longitude + yearBuilt: URIRef # Four digit year that a building was first built. (adopted from Project Haystack) + electricalPhases: URIRef # Entity has these electrical AC phases + tilt: URIRef # The direction an entity is facing in degrees above the horizon + grossArea: URIRef # Entity has gross 2-dimensional area + powerFlow: URIRef # Entity has this power flow relative to the building' + coolingCapacity: URIRef # Measurement of a chiller ability to remove heat (adopted from Project Haystack) + measuredModuleConversionEfficiency: URIRef # The measured percentage of sunlight that is converted into usable power + conversionEfficiency: URIRef # The percent efficiency of the conversion process (usually to power or energy) carried out by the entity + buildingThermalTransmittance: URIRef # The area-weighted average heat transfer coefficient (commonly referred to as a U-value) for a building envelope + aggregate: URIRef # Description of how the dta for this point is aggregated + panelArea: URIRef # Surface area of a panel, such as a PV panel + operationalStageCount: URIRef # The number of operational stages supported by this eqiupment + operationalStage: URIRef # The associated operational stage + measuredPowerOutput: URIRef # The nominal measured power output of the entity + thermalTransmittance: URIRef # The area-weighted average heat transfer coefficient (commonly referred to as a U-value) + electricalPhaseCount: URIRef # Entity has these phases + area: URIRef # Entity has 2-dimensional area + + _NS = Namespace("https://brickschema.org/schema/Brick#") diff --git a/rdflib/namespace/__init__.py b/rdflib/namespace/__init__.py index 23f4ec0ea..686aed6a5 100644 --- a/rdflib/namespace/__init__.py +++ b/rdflib/namespace/__init__.py @@ -46,6 +46,7 @@ The following namespaces are available by directly importing from rdflib: +* BRICK * CSVW * DC * DCMITYPE @@ -696,6 +697,7 @@ def get_longest_namespace(trie, value): return None +from rdflib.namespace._BRICK import BRICK from rdflib.namespace._CSVW import CSVW from rdflib.namespace._DC import DC from rdflib.namespace._DCAT import DCAT