% Program for Gauss - Seidel Load Flow Analysis
% Praviraj P G, MTech I Year, EE Dept., IIT Roorkee, India, Email :pravirajpg@gmail.com
% Modified by Y Gu. Adding self-conductance for passive load
% Assumption, Bus 1 is considered as Slack bus.
function [V,I,Av,P,Q,Vm]=PowerFlow(busdata,linedata)
ybus = YbusCalc(linedata); % Calling program "YbusCalc.m" to get Y-Bus.
bus = busdata(:,1); % Bus number.
type= busdata(:,2); % Type of Bus 1-Slack, 2-PV, 3-PQ
V = busdata(:,3); % Initial Bus Voltages.
th = busdata(:,4); % Initial Bus Voltage Angles.
GenMW = busdata(:,5); % PGi, Real Power injected into the buses.
GenMVAR = busdata(:,6); % QGi, Reactive Power injected into the buses.
LoadMW = busdata(:,7); % PLi, Real Power Drawn from the buses.
LoadMVAR= busdata(:,8); % QLi, Reactive Power Drawn from the buses.
Qmin = busdata(:,9); % Minimum Reactive Power Limit
Qmax = busdata(:,10); % Maximum Reactive Power Limit
nbus = max(bus); % To get no. of buses
P = GenMW - LoadMW; % Pi = PGi - PLi, Real Power at the buses.
Q = GenMVAR - LoadMVAR; % Qi = QGi - QLi, Reactive Power at the buses.
Vprev = V;
toler = 1; % Tolerence.
iteration = 0; % iteration starting
tolermax = 1e-9;
iteramax = 1e4;
%tolermax = 1e-12;
%iteramax = 1e6;
while (toler>tolermax) && (iteration<iteramax)
for i = 2:nbus
sumyv = 0;
for k = 1:nbus
if i ~= k
sumyv = sumyv + ybus(i,k)* V(k); % Vk * Yik
end
end
if type(i) == 2 % Computing Qi for PV bus
Q(i) = -imag(conj(V(i))*(sumyv + ybus(i,i)*V(i)));
if (Q(i) > Qmax(i)) || (Q(i) < Qmin(i)) % Checking for Qi Violation.
if Q(i) < Qmin(i) % Whether violated the lower limit.
Q(i) = Qmin(i);
else % No, violated the upper limit.
Q(i) = Qmax(i);
end
type(i) = 3; % If Violated, change PV bus to PQ bus.
end
end
V(i) = (1/ybus(i,i))*((P(i)-1j*Q(i))/conj(V(i)) - sumyv); % Compute Bus Voltages.
if type(i) == 2 % For PV Buses, Voltage Magnitude remains same, but Angle changes.
V(i) = pol2rect(abs(Vprev(i)), angle(V(i)));
end
end
iteration = iteration + 1; % Increment iteration count.
I = ybus*V;
S = I.*conj(V);
N = length(V);
tolerV = max(abs(abs(V) - abs(Vprev))); % Calculate V tolerance.
tolerP = max(abs(real(S(2:N))-P(2:N))); % Calculate P tolerance, exclude the slack terminal
tolerQ = max(abs(imag(S(2:N))+Q(2:N))); % Calculate Q tolerance, exclude the slack terminal
toler = max([tolerV,tolerP,tolerQ]); % Calculate total tolerance
Vprev = V; % Vprev is required for next iteration, V(i) = pol2rect(abs(Vprev(i)), angle(V(i)));
end % End of while loop / Iteration
Av = angle(V); % Final Bus Voltage Angles in rad.
Vm = abs(V); % Final Bus Voltage Amplitude.
S = V.*conj(I); % Final Appearant Power, Generator Convention.
P = real(S); % Final Active Power, Generator Convention.
Q = imag(S); % Final Reactive Power, Generator Convention.
end
function rect = pol2rect(r,o) % r = magnitude, o = angle in radians.
rect = r*cos(o) + 1j*r*sin(o); % rect = real + j*imag
end