Qubino ZMNHXD reports produced power, but it is actually consumed power #1048

Open
chris299 opened this issue Jan 30, 2024 · 10 comments
Open

Comments

@chris299
Copy link

chris299 commented Jan 30, 2024

Describe the bug
in the Z.Wave log (and in the datapoints of IOB) I see a message on produced power, but this is wrong.
actually, it seems to be consumed power wrongly reported (or interpreted)as being produced.
The log of my Node 18 as follows, and you find at 13:20:54 a message on produced power, which is wrong.
it is in a sequence of consumed power messages.....

2024-01-30T13:20:54.532Z SERIAL « 0x0120000400121a9f03c10004e2e5eb783cb2b5cc1ae557f53dd0abd674f9e1416 (34 bytes)
                                  960
2024-01-30T13:20:54.533Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:54.533Z CNTRLR   [Node 018] [Meter] value[66050]: metadata updated                 [Endpoint 1]
2024-01-30T13:20:54.533Z CNTRLR   [Node 018] [~] [Meter] value[66050]: 90.7 => 49.9                 [Endpoint 1]
2024-01-30T13:20:54.534Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 193
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      1
                                      │ destination: 0
                                      └─[MeterCCReport]
                                          type:       Electric
                                          scale:      W
                                          rate type:  Produced
                                          value:      49.9
                                          time delta: 0 seconds
2024-01-30T13:20:53.032Z SERIAL « 0x0120000400121a9f03bb00834db9c86820776f76d2a3f26f4b7b26026d51ec021 (34 bytes)
                                  750
2024-01-30T13:20:53.033Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:53.033Z CNTRLR   [Node 018] [Meter] value[66049]: metadata updated                 [Endpoint 1]
2024-01-30T13:20:53.033Z CNTRLR   [Node 018] [~] [Meter] value[66049]: 49.9 => 49.9                 [Endpoint 1]
2024-01-30T13:20:53.034Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 187
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      1
                                      │ destination: 0
                                      └─[MeterCCReport]
                                          type:       Electric
                                          scale:      W
                                          rate type:  Consumed
                                          value:      49.9
                                          time delta: 0 seconds
2024-01-30T13:20:53.034Z CNTRLR » [Node 018] querying meter value (type = Electric, scale = Power F [Endpoint 1]
                                  actor, rate type = Consumed)...
2024-01-30T13:20:53.037Z SERIAL » 0x011a001312139f037000caddf81f3ef7818199ee31314d7ddf25108f          (28 bytes)
2024-01-30T13:20:53.037Z DRIVER » [Node 018] [REQ] [SendData]
                                  │ transmit options: 0x25
                                  │ callback id:      16
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 112
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      0
                                      │ destination: 1
                                      └─[MeterCCGet]
                                          rate type: Consumed
                                          scale:     Power Factor
2024-01-30T13:20:53.039Z SERIAL « [ACK]                                                                   (0x06)
2024-01-30T13:20:53.047Z SERIAL « 0x0104011301e8                                                       (6 bytes)
2024-01-30T13:20:53.047Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:53.047Z DRIVER « [RES] [SendData]
                                    was sent: true
2024-01-30T13:20:53.177Z SERIAL « 0x010700131000000ef5                                                 (9 bytes)
2024-01-30T13:20:53.178Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:53.178Z DRIVER « [REQ] [SendData]
                                    callback id:     16
                                    transmit status: OK
2024-01-30T13:20:53.273Z SERIAL « 0x0120000400121a9f03bc000bdbe3e8bf867ac022c16c6d79c26063a717c81c6ad (34 bytes)
                                  52a
2024-01-30T13:20:53.274Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:53.275Z CNTRLR   [Node 018] [Meter] value[67073]: metadata updated                 [Endpoint 1]
2024-01-30T13:20:53.275Z CNTRLR   [Node 018] [~] [Meter] value[67073]: 0.0736 => 0.0736             [Endpoint 1]
2024-01-30T13:20:53.276Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 188
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      1
                                      │ destination: 0
                                      └─[MeterCCReport]
                                          type:       Electric
                                          scale:      Power Factor
                                          rate type:  Consumed
                                          value:      0.0736
                                          time delta: 0 seconds
2024-01-30T13:20:53.278Z CNTRLR » [Node 018] querying meter value (type = Electric, scale = kVar, r [Endpoint 1]
                                  ate type = Consumed)...
2024-01-30T13:20:53.285Z SERIAL » 0x011b001312149f037100c1dfea6ff2335cf39d8bfbec5e7aadf52511a0        (29 bytes)
2024-01-30T13:20:53.285Z DRIVER » [Node 018] [REQ] [SendData]
                                  │ transmit options: 0x25
                                  │ callback id:      17
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 113
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      0
                                      │ destination: 1
                                      └─[MeterCCGet]
                                          rate type: Consumed
                                          scale:     kVar
2024-01-30T13:20:53.288Z SERIAL « [ACK]                                                                   (0x06)
2024-01-30T13:20:53.295Z SERIAL « 0x0104011301e8                                                       (6 bytes)
2024-01-30T13:20:53.295Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:53.295Z DRIVER « [RES] [SendData]
                                    was sent: true
2024-01-30T13:20:53.428Z SERIAL « 0x010700131100000ef4                                                 (9 bytes)
2024-01-30T13:20:53.429Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:53.429Z DRIVER « [REQ] [SendData]
                                    callback id:     17
                                    transmit status: OK
2024-01-30T13:20:53.523Z SERIAL « 0x0121000400121b9f03bd00d914a1b80651a6780d3385cbd5764cbecd364fe68c9 (35 bytes)
                                  ce12d
2024-01-30T13:20:53.524Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:53.525Z CNTRLR   [Node 018] [Meter] value[67329]: metadata updated                 [Endpoint 1]
2024-01-30T13:20:53.525Z CNTRLR   [Node 018] [~] [Meter] value[67329]: -414.1 => -414.1             [Endpoint 1]
2024-01-30T13:20:53.526Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 189
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      1
                                      │ destination: 0
                                      └─[MeterCCReport]
                                          type:       Electric
                                          scale:      kVar
                                          rate type:  Consumed
                                          value:      -414.1
                                          time delta: 0 seconds
2024-01-30T13:20:53.527Z CNTRLR » [Node 018] querying meter value (type = Electric, scale = kVarh,  [Endpoint 1]
                                  rate type = Consumed)...
2024-01-30T13:20:53.534Z SERIAL » 0x011b001312149f0372000b733fdead429a96092f29d27557a199251295        (29 bytes)
2024-01-30T13:20:53.534Z DRIVER » [Node 018] [REQ] [SendData]
                                  │ transmit options: 0x25
                                  │ callback id:      18
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 114
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      0
                                      │ destination: 1
                                      └─[MeterCCGet]
                                          rate type: Consumed
                                          scale:     kVarh
2024-01-30T13:20:53.537Z SERIAL « [ACK]                                                                   (0x06)
2024-01-30T13:20:53.544Z SERIAL « 0x0104011301e8                                                       (6 bytes)
2024-01-30T13:20:53.544Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:53.544Z DRIVER « [RES] [SendData]
                                    was sent: true
2024-01-30T13:20:53.678Z SERIAL « 0x010700131200000ef7                                                 (9 bytes)
2024-01-30T13:20:53.679Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:53.679Z DRIVER « [REQ] [SendData]
                                    callback id:     18
                                    transmit status: OK
2024-01-30T13:20:53.775Z SERIAL « 0x0121000400121b9f03be00ae9b5896799eeb87083c223dc5f022cec547a69b585 (35 bytes)
                                  e61ab
2024-01-30T13:20:53.776Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:53.777Z CNTRLR   [Node 018] [Meter] value[67585]: metadata updated                 [Endpoint 1]
2024-01-30T13:20:53.777Z CNTRLR   [Node 018] [~] [Meter] value[67585]: 5064.2 => 5064.2             [Endpoint 1]
2024-01-30T13:20:53.778Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 190
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      1
                                      │ destination: 0
                                      └─[MeterCCReport]
                                          type:       Electric
                                          scale:      kVarh
                                          rate type:  Consumed
                                          value:      5064.2
                                          time delta: 0 seconds
2024-01-30T13:20:53.782Z CNTRLR » [Node 018] querying meter value (type = Electric, scale = kWh, ra [Endpoint 1]
                                  te type = Produced)...
2024-01-30T13:20:53.788Z SERIAL » 0x011a001312139f0373004d8e435ebe5ea4993eddd7d429e05825135c          (28 bytes)
2024-01-30T13:20:53.788Z DRIVER » [Node 018] [REQ] [SendData]
                                  │ transmit options: 0x25
                                  │ callback id:      19
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 115
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      0
                                      │ destination: 1
                                      └─[MeterCCGet]
                                          rate type: Produced
                                          scale:     kWh
2024-01-30T13:20:53.790Z SERIAL « [ACK]                                                                   (0x06)
2024-01-30T13:20:53.798Z SERIAL « 0x0104011301e8                                                       (6 bytes)
2024-01-30T13:20:53.798Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:53.798Z DRIVER « [RES] [SendData]
                                    was sent: true
2024-01-30T13:20:53.954Z SERIAL « 0x0107001313000010e8                                                 (9 bytes)
2024-01-30T13:20:53.954Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:53.954Z DRIVER « [REQ] [SendData]
                                    callback id:     19
                                    transmit status: OK
2024-01-30T13:20:54.043Z SERIAL « 0x0120000400121a9f03bf0015abf6db1b36d7a031bf7fb722d87ef9390dad9a472 (34 bytes)
                                  167
2024-01-30T13:20:54.044Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:54.045Z CNTRLR   [Node 018] [Meter] value[65538]: metadata updated                 [Endpoint 1]
2024-01-30T13:20:54.045Z CNTRLR   [Node 018] [~] [Meter] value[65538]: 73.1 => 73.1                 [Endpoint 1]
2024-01-30T13:20:54.049Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 191
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      1
                                      │ destination: 0
                                      └─[MeterCCReport]
                                          type:       Electric
                                          scale:      kWh
                                          rate type:  Produced
                                          value:      73.1
                                          time delta: 0 seconds
2024-01-30T13:20:54.052Z CNTRLR » [Node 018] querying meter value (type = Electric, scale = kVAh, r [Endpoint 1]
                                  ate type = Produced)...
2024-01-30T13:20:54.058Z SERIAL » 0x011a001312139f037400c93ad977a8c0970d30c36323fa1d5d251488          (28 bytes)
2024-01-30T13:20:54.059Z DRIVER » [Node 018] [REQ] [SendData]
                                  │ transmit options: 0x25
                                  │ callback id:      20
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 116
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      0
                                      │ destination: 1
                                      └─[MeterCCGet]
                                          rate type: Produced
                                          scale:     kVAh
2024-01-30T13:20:54.061Z SERIAL « [ACK]                                                                   (0x06)
2024-01-30T13:20:54.068Z SERIAL « 0x0104011301e8                                                       (6 bytes)
2024-01-30T13:20:54.068Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:54.068Z DRIVER « [RES] [SendData]
                                    was sent: true
2024-01-30T13:20:54.197Z SERIAL « 0x010700131400000ef1                                                 (9 bytes)
2024-01-30T13:20:54.197Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:54.198Z DRIVER « [REQ] [SendData]
                                    callback id:     20
                                    transmit status: OK
2024-01-30T13:20:54.292Z SERIAL « 0x0120000400121a9f03c000ef85b7b9ea67ffad334d9402561b033c88c09a5e067 (34 bytes)
                                  85c
2024-01-30T13:20:54.293Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:54.293Z CNTRLR   [Node 018] [Meter] value[65794]: metadata updated                 [Endpoint 1]
2024-01-30T13:20:54.293Z CNTRLR   [Node 018] [~] [Meter] value[65794]: 7914.3 => 7918.4             [Endpoint 1]
2024-01-30T13:20:54.294Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 192
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      1
                                      │ destination: 0
                                      └─[MeterCCReport]
                                          type:       Electric
                                          scale:      kVAh
                                          rate type:  Produced
                                          value:      7918.4
                                          time delta: 0 seconds
2024-01-30T13:20:54.294Z CNTRLR » [Node 018] querying meter value (type = Electric, scale = W, rate [Endpoint 1]
                                   type = Produced)...
2024-01-30T13:20:54.296Z SERIAL » 0x011a001312139f0375004adc5af08d2c4b47361930ef17b0372515df          (28 bytes)
2024-01-30T13:20:54.296Z DRIVER » [Node 018] [REQ] [SendData]
                                  │ transmit options: 0x25
                                  │ callback id:      21
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 117
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      0
                                      │ destination: 1
                                      └─[MeterCCGet]
                                          rate type: Produced
                                          scale:     W
2024-01-30T13:20:54.299Z SERIAL « [ACK]                                                                   (0x06)
2024-01-30T13:20:54.306Z SERIAL « 0x0104011301e8                                                       (6 bytes)
2024-01-30T13:20:54.306Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:54.306Z DRIVER « [RES] [SendData]
                                    was sent: true
2024-01-30T13:20:54.435Z SERIAL « 0x010700131500000ef0                                                 (9 bytes)
2024-01-30T13:20:54.435Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:54.436Z DRIVER « [REQ] [SendData]
                                    callback id:     21
                                    transmit status: OK
2024-01-30T13:20:54.532Z SERIAL « 0x0120000400121a9f03c10004e2e5eb783cb2b5cc1ae557f53dd0abd674f9e1416 (34 bytes)
                                  960
2024-01-30T13:20:54.533Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:54.533Z CNTRLR   [Node 018] [Meter] value[66050]: metadata updated                 [Endpoint 1]
2024-01-30T13:20:54.533Z CNTRLR   [Node 018] [~] [Meter] value[66050]: 90.7 => 49.9                 [Endpoint 1]
2024-01-30T13:20:54.534Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 193
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      1
                                      │ destination: 0
                                      └─[MeterCCReport]
                                          type:       Electric
                                          scale:      W
                                          rate type:  Produced
                                          value:      49.9
                                          time delta: 0 seconds
2024-01-30T13:20:54.534Z CNTRLR » [Node 018] querying meter value (type = Electric, scale = Power F [Endpoint 1]
                                  actor, rate type = Produced)...
2024-01-30T13:20:54.537Z SERIAL » 0x011a001312139f0376006aceae58c197300f75d2b1dcfc4d1c251672          (28 bytes)
2024-01-30T13:20:54.537Z DRIVER » [Node 018] [REQ] [SendData]
                                  │ transmit options: 0x25
                                  │ callback id:      22
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 118
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      0
                                      │ destination: 1
                                      └─[MeterCCGet]
                                          rate type: Produced
                                          scale:     Power Factor
2024-01-30T13:20:54.539Z SERIAL « [ACK]                                                                   (0x06)
2024-01-30T13:20:54.547Z SERIAL « 0x0104011301e8                                                       (6 bytes)
2024-01-30T13:20:54.547Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:54.547Z DRIVER « [RES] [SendData]
                                    was sent: true
2024-01-30T13:20:54.703Z SERIAL « 0x0107001316000010ed                                                 (9 bytes)
2024-01-30T13:20:54.703Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:54.704Z DRIVER « [REQ] [SendData]
                                    callback id:     22
                                    transmit status: OK
2024-01-30T13:20:54.793Z SERIAL « 0x0120000400121a9f03c200ee9fe79ee2fe3530b6e34ce7c4f42f01d58df28f653 (34 bytes)
                                  509
2024-01-30T13:20:54.794Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:54.795Z CNTRLR   [Node 018] [Meter] value[67074]: metadata updated                 [Endpoint 1]
2024-01-30T13:20:54.796Z CNTRLR   [Node 018] [~] [Meter] value[67074]: 0.2259 => 0.0736             [Endpoint 1]
2024-01-30T13:20:54.797Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 194
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      1
                                      │ destination: 0
                                      └─[MeterCCReport]
                                          type:       Electric
                                          scale:      Power Factor
                                          rate type:  Produced
                                          value:      0.0736
                                          time delta: 0 seconds
2024-01-30T13:20:54.799Z CNTRLR » [Node 018] querying meter value (type = Electric, scale = kVar, r [Endpoint 1]
                                  ate type = Produced)...
2024-01-30T13:20:54.805Z SERIAL » 0x011b001312149f037700dc85b88213b5221c86682eedefc106312517e7        (29 bytes)
2024-01-30T13:20:54.805Z DRIVER » [Node 018] [REQ] [SendData]
                                  │ transmit options: 0x25
                                  │ callback id:      23
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 119
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      0
                                      │ destination: 1
                                      └─[MeterCCGet]
                                          rate type: Produced
                                          scale:     kVar
2024-01-30T13:20:54.807Z SERIAL « [ACK]                                                                   (0x06)
2024-01-30T13:20:54.814Z SERIAL « 0x0104011301e8                                                       (6 bytes)
2024-01-30T13:20:54.814Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:54.815Z DRIVER « [RES] [SendData]
                                    was sent: true
2024-01-30T13:20:54.948Z SERIAL « 0x010700131700000ef2                                                 (9 bytes)
2024-01-30T13:20:54.948Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:54.948Z DRIVER « [REQ] [SendData]
                                    callback id:     23
                                    transmit status: OK
2024-01-30T13:20:55.043Z SERIAL « 0x0121000400121b9f03c3009a2ce0f21773a18b0c5f8491ef9c7c62b40f107c74f (35 bytes)
                                  1b1ae
2024-01-30T13:20:55.044Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:55.044Z CNTRLR   [Node 018] [Meter] value[67330]: metadata updated                 [Endpoint 1]
2024-01-30T13:20:55.044Z CNTRLR   [Node 018] [~] [Meter] value[67330]: -338 => -415.5               [Endpoint 1]
2024-01-30T13:20:55.044Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 195
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      1
                                      │ destination: 0
                                      └─[MeterCCReport]
                                          type:       Electric
                                          scale:      kVar
                                          rate type:  Produced
                                          value:      -415.5
                                          time delta: 0 seconds
2024-01-30T13:20:55.045Z CNTRLR » [Node 018] querying meter value (type = Electric, scale = kVarh,  [Endpoint 1]
                                  rate type = Produced)...
2024-01-30T13:20:55.047Z SERIAL » 0x011b001312149f03780072715668a2fb6522a1ba79ef15631e88251866        (29 bytes)
2024-01-30T13:20:55.047Z DRIVER » [Node 018] [REQ] [SendData]
                                  │ transmit options: 0x25
                                  │ callback id:      24
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 120
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      0
                                      │ destination: 1
                                      └─[MeterCCGet]
                                          rate type: Produced
                                          scale:     kVarh
2024-01-30T13:20:55.050Z SERIAL « [ACK]                                                                   (0x06)
2024-01-30T13:20:55.058Z SERIAL « 0x0104011301e8                                                       (6 bytes)
2024-01-30T13:20:55.058Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:55.058Z DRIVER « [RES] [SendData]
                                    was sent: true
2024-01-30T13:20:55.184Z SERIAL « 0x010700131800000dfe                                                 (9 bytes)
2024-01-30T13:20:55.184Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:55.185Z DRIVER « [REQ] [SendData]
                                    callback id:     24
                                    transmit status: OK
2024-01-30T13:20:55.283Z SERIAL « 0x0121000400121b9f03c400d1e39d7bfb7cf2f09bc8642c4d45bd123efb4c02593 (35 bytes)
                                  b1d92
2024-01-30T13:20:55.285Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:55.286Z CNTRLR   [Node 018] [Meter] value[67586]: metadata updated                 [Endpoint 1]
2024-01-30T13:20:55.287Z CNTRLR   [Node 018] [~] [Meter] value[67586]: 5061 => 5064.2               [Endpoint 1]
2024-01-30T13:20:55.287Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 196
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      1
                                      │ destination: 0
                                      └─[MeterCCReport]
                                          type:       Electric
                                          scale:      kVarh
                                          rate type:  Produced
                                          value:      5064.2
                                          time delta: 0 seconds
2024-01-30T13:20:55.295Z CNTRLR » [Node 018] Meter CC values may be stale, refreshing...            [Endpoint 3]
2024-01-30T13:20:55.295Z CNTRLR » [Node 018] querying meter value (type = Electric, scale = W, rate [Endpoint 3]
                                   type = Consumed)...
2024-01-30T13:20:55.301Z SERIAL » 0x011a001312139f0379006e5fdc6b971dd5e3dfff60718209ce251960          (28 bytes)
2024-01-30T13:20:55.302Z DRIVER » [Node 018] [REQ] [SendData]
                                  │ transmit options: 0x25
                                  │ callback id:      25
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 121
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      0
                                      │ destination: 3
                                      └─[MeterCCGet]
                                          rate type: Consumed
                                          scale:     W
2024-01-30T13:20:55.304Z SERIAL « [ACK]                                                                   (0x06)
2024-01-30T13:20:55.312Z SERIAL « 0x0104011301e8                                                       (6 bytes)
2024-01-30T13:20:55.312Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:55.313Z DRIVER « [RES] [SendData]
                                    was sent: true
2024-01-30T13:20:55.420Z SERIAL « 0x0120000400121a9f03c5006e5fde68971e242c96d6e06c4a836d6cbc83830a9d2 (34 bytes)
                                  e8d
2024-01-30T13:20:55.421Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:55.422Z CNTRLR   [Node 018] [Meter] value[66817]: metadata updated                 [Endpoint 2]
2024-01-30T13:20:55.423Z CNTRLR   [Node 018] [~] [Meter] value[66817]: 0.443 => 0.442               [Endpoint 2]
2024-01-30T13:20:55.424Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 197
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      2
                                      │ destination: 0
                                      └─[MeterCCReport]
                                          type:       Electric
                                          scale:      A
                                          rate type:  Consumed
                                          value:      0.442
                                          time delta: 0 seconds
2024-01-30T13:20:56.439Z SERIAL « 0x010700131900007183                                                 (9 bytes)
2024-01-30T13:20:56.439Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:56.440Z DRIVER « [REQ] [SendData]
                                    callback id:     25
                                    transmit status: OK
2024-01-30T13:20:56.722Z SERIAL « 0x0120000400121a9f03c5006e5fde68971e242c96d6e06c4a836d6cbc83830a9d2 (34 bytes)
                                  e8d
2024-01-30T13:20:56.723Z DRIVER   Dropping message with invalid payload
2024-01-30T13:20:56.724Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation] [INVALID]
                                      error: Duplicate command (sequence number 197)
2024-01-30T13:20:56.725Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:56.905Z SERIAL « 0x011a00040012149f02c6016197ab2378783797fe9b91bc6f81fa003f          (28 bytes)
2024-01-30T13:20:56.907Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:56.908Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCNonceReport]
                                      sequence number:  198
                                      SOS:              true
                                      MOS:              false
                                      receiver entropy: 0x6197ab2378783797fe9b91bc6f81fa00
2024-01-30T13:20:56.909Z CNTRLR   [Node 018] failed to decode the message, retrying with SPAN extension...
2024-01-30T13:20:56.910Z SERIAL » 0x012c001312259f037a0112412e76523d88de98c9884492baea58ccf41272a8186 (46 bytes)
                                  eb07cc84d65be3586be37251a34
2024-01-30T13:20:56.911Z DRIVER » [Node 018] [REQ] [SendData]
                                  │ transmit options: 0x25
                                  │ callback id:      26
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 122
                                    │ extensions:
                                    │ · type: SPAN
                                    │   sender EI: 0x2e76523d88de98c9884492baea58ccf4
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      0
                                      │ destination: 3
                                      └─[MeterCCGet]
                                          rate type: Consumed
                                          scale:     W
2024-01-30T13:20:56.914Z SERIAL « [ACK]                                                                   (0x06)
2024-01-30T13:20:56.922Z SERIAL « 0x0104011301e8                                                       (6 bytes)
2024-01-30T13:20:56.923Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:56.923Z DRIVER « [RES] [SendData]
                                    was sent: true
2024-01-30T13:20:57.076Z SERIAL « 0x010700131a000010e1                                                 (9 bytes)
2024-01-30T13:20:57.076Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:57.076Z DRIVER « [REQ] [SendData]
                                    callback id:     26
                                    transmit status: OK
2024-01-30T13:20:57.173Z SERIAL « 0x0120000400121a9f03c700629da5be7ff16e97f6d3676193992102f5ab34c8317 (34 bytes)
                                  efc
2024-01-30T13:20:57.174Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:57.175Z CNTRLR   [Node 018] [Meter] value[66049]: metadata updated                 [Endpoint 3]
2024-01-30T13:20:57.175Z CNTRLR   [Node 018] [~] [Meter] value[66049]: 78 => 51.8                   [Endpoint 3]
2024-01-30T13:20:57.176Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 199
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      3
                                      │ destination: 0
                                      └─[MeterCCReport]
                                          type:       Electric
                                          scale:      W
                                          rate type:  Consumed
                                          value:      51.8
                                          time delta: 0 seconds
2024-01-30T13:20:57.177Z CNTRLR » [Node 018] querying meter value (type = Electric, scale = V, rate [Endpoint 3]
                                   type = Consumed)...
2024-01-30T13:20:57.184Z SERIAL » 0x011a001312139f037b000023c974d51a5f4fe784b3b4fc6f1b251b83          (28 bytes)
2024-01-30T13:20:57.185Z DRIVER » [Node 018] [REQ] [SendData]
                                  │ transmit options: 0x25
                                  │ callback id:      27
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 123
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      0
                                      │ destination: 3
                                      └─[MeterCCGet]
                                          rate type: Consumed
                                          scale:     V
2024-01-30T13:20:57.187Z SERIAL « [ACK]                                                                   (0x06)
2024-01-30T13:20:57.194Z SERIAL « 0x0104011301e8                                                       (6 bytes)
2024-01-30T13:20:57.194Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:57.194Z DRIVER « [RES] [SendData]
                                    was sent: true
2024-01-30T13:20:57.596Z SERIAL « 0x0121000400121b9f03c8000023cb77d5199e7f9942bea9333c422cc5bfa7cc32a (35 bytes)
                                  4fae5
2024-01-30T13:20:57.596Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:57.596Z CNTRLR   [Node 018] [Meter] value[67329]: metadata updated                 [Endpoint 2]
2024-01-30T13:20:57.597Z CNTRLR   [Node 018] [~] [Meter] value[67329]: -96.7 => -96.9               [Endpoint 2]
2024-01-30T13:20:57.597Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 200
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      2
                                      │ destination: 0
                                      └─[MeterCCReport]
                                          type:       Electric
                                          scale:      kVar
                                          rate type:  Consumed
                                          value:      -96.9
                                          time delta: 0 seconds
2024-01-30T13:20:58.236Z SERIAL « 0x011a00040012149f02c9013ed3faacb397eb383d49441cdbd1f2cee4          (28 bytes)
2024-01-30T13:20:58.236Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:58.237Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCNonceReport]
                                      sequence number:  201
                                      SOS:              true
                                      MOS:              false
                                      receiver entropy: 0x3ed3faacb397eb383d49441cdbd1f2ce
2024-01-30T13:20:58.237Z CNTRLR « [Node 018] received expected response prematurely, remembering it...
2024-01-30T13:20:58.486Z SERIAL « 0x0114000400180e32022144000003330e1000000331b0                      (22 bytes)
2024-01-30T13:20:58.487Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:58.488Z CNTRLR   [Node 024] [Meter] value[65537]: metadata updated                 [Endpoint 0]
2024-01-30T13:20:58.489Z CNTRLR   [Node 024] [~] [Meter] value[65537]: 8.17 => 8.19                 [Endpoint 0]
2024-01-30T13:20:58.489Z DRIVER « [Node 024] [REQ] [ApplicationCommand]
                                  └─[MeterCCReport]
                                      type:        Electric
                                      scale:       kWh
                                      rate type:   Consumed
                                      value:       8.19
                                      time delta:  3600 seconds
                                      prev. value: 8.17
2024-01-30T13:20:58.667Z SERIAL « 0x010900040012039f01cab7                                            (11 bytes)
2024-01-30T13:20:58.667Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:58.669Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCNonceGet]
                                      sequence number: 202
2024-01-30T13:20:59.116Z SERIAL « 0x010900040012039f01cab7                                            (11 bytes)
2024-01-30T13:20:59.117Z DRIVER   Dropping message with invalid payload
2024-01-30T13:20:59.117Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCNonceGet] [INVALID]
                                      error: Duplicate command (sequence number 202)
2024-01-30T13:20:59.117Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:59.192Z SERIAL « 0x011a00040012149f02c9013ed3faacb397eb383d49441cdbd1f2cee4          (28 bytes)
2024-01-30T13:20:59.193Z DRIVER   Dropping message with invalid payload
2024-01-30T13:20:59.193Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCNonceReport] [INVALID]
                                      error: Duplicate command (sequence number 201)
2024-01-30T13:20:59.193Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:59.463Z SERIAL « 0x010700131b0000e313                                                 (9 bytes)
2024-01-30T13:20:59.463Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:59.464Z DRIVER « [REQ] [SendData]
                                    callback id:     27
                                    transmit status: OK
2024-01-30T13:20:59.468Z SERIAL » 0x011b001312149f027c0194f7ab53333bb8f22800445ac53b2aa5051c96        (29 bytes)
2024-01-30T13:20:59.469Z DRIVER » [Node 018] [REQ] [SendData]
                                  │ transmit options: 0x05
                                  │ callback id:      28
                                  └─[Security2CCNonceReport]
                                      sequence number:  124
                                      SOS:              true
                                      MOS:              false
                                      receiver entropy: 0x94f7ab53333bb8f22800445ac53b2aa5
2024-01-30T13:20:59.470Z CNTRLR   [Node 018] failed to decode the message, retrying with SPAN extension...
2024-01-30T13:20:59.473Z SERIAL « [ACK]                                                                   (0x06)
2024-01-30T13:20:59.477Z SERIAL « 0x0104011301e8                                                       (6 bytes)
2024-01-30T13:20:59.478Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:59.478Z DRIVER « [RES] [SendData]
                                    was sent: true
2024-01-30T13:20:59.558Z SERIAL « 0x010700131c000009fe                                                 (9 bytes)
2024-01-30T13:20:59.558Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:59.559Z DRIVER « [REQ] [SendData]
                                    callback id:     28
                                    transmit status: OK
2024-01-30T13:20:59.560Z SERIAL » 0x012c001312259f037d0112415416031548745407e6c888a87a785a9aa2c68dbab (46 bytes)
                                  5f3f52ff1579dc8366be2251d08
2024-01-30T13:20:59.560Z DRIVER » [Node 018] [REQ] [SendData]
                                  │ transmit options: 0x25
                                  │ callback id:      29
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 125
                                    │ extensions:
                                    │ · type: SPAN
                                    │   sender EI: 0x5416031548745407e6c888a87a785a9a
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      0
                                      │ destination: 3
                                      └─[MeterCCGet]
                                          rate type: Consumed
                                          scale:     V
2024-01-30T13:20:59.564Z SERIAL « [ACK]                                                                   (0x06)
2024-01-30T13:20:59.572Z SERIAL « 0x0104011301e8                                                       (6 bytes)
2024-01-30T13:20:59.572Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:59.572Z DRIVER « [RES] [SendData]
                                    was sent: true
2024-01-30T13:20:59.649Z SERIAL « 0x010700131d000008fe                                                 (9 bytes)
2024-01-30T13:20:59.650Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:59.650Z DRIVER « [REQ] [SendData]
                                    callback id:     29
                                    transmit status: OK
2024-01-30T13:20:59.754Z SERIAL « 0x0132000400122c9f03cb011241cca1f29fbd8eeacdcb2eef51ab380158539b168 (52 bytes)
                                  ee442eec808ec8427986925f041e25075665e7a
2024-01-30T13:20:59.755Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:59.755Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation] [INVALID]
                                      error: Security2CC_CannotDecode
2024-01-30T13:20:59.756Z CNTRLR » [Node 018] Message authentication failed, cannot decode command. Requesting a 
                                  nonce...
2024-01-30T13:20:59.760Z SERIAL » 0x011b001312149f027e01747bd422e3dd7ba8bef9d7daebe993e2051e25        (29 bytes)
2024-01-30T13:20:59.761Z DRIVER » [Node 018] [REQ] [SendData]
                                  │ transmit options: 0x05
                                  │ callback id:      30
                                  └─[Security2CCNonceReport]
                                      sequence number:  126
                                      SOS:              true
                                      MOS:              false
                                      receiver entropy: 0x747bd422e3dd7ba8bef9d7daebe993e2
2024-01-30T13:20:59.763Z SERIAL « [ACK]                                                                   (0x06)
2024-01-30T13:20:59.770Z SERIAL « 0x0104011301e8                                                       (6 bytes)
2024-01-30T13:20:59.770Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:59.771Z DRIVER « [RES] [SendData]
                                    was sent: true
2024-01-30T13:20:59.823Z SERIAL « 0x011a00040012149f02cc016f5bd4a70468611a2cc7c49fa59df123bd          (28 bytes)
2024-01-30T13:20:59.824Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:59.824Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCNonceReport]
                                      sequence number:  204
                                      SOS:              true
                                      MOS:              false
                                      receiver entropy: 0x6f5bd4a70468611a2cc7c49fa59df123
2024-01-30T13:20:59.824Z CNTRLR   [Node 018] failed to decode the message after re-transmission with SPAN extens
                                  ion, dropping the message.
2024-01-30T13:20:59.825Z CNTRLR   [Node 018] failed to refresh values for Meter CC: The node failed [Endpoint 3]
                                   to decode the message. (ZW1405)
2024-01-30T13:20:59.974Z SERIAL « 0x010700131e000014e1                                                 (9 bytes)
2024-01-30T13:20:59.974Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:20:59.975Z DRIVER « [REQ] [SendData]
                                    callback id:     30
                                    transmit status: OK
2024-01-30T13:21:01.123Z SERIAL « 0x0132000400122c9f03cd0112414a9b21f0ebcd21a9173d0f5858970914ee3acc8 (52 bytes)
                                  a887f38bb6159f0d77f02873ae2810f20c76720
2024-01-30T13:21:01.124Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:21:01.125Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation] [INVALID]
                                      error: Security2CC_NoSPAN
2024-01-30T13:21:01.125Z CNTRLR » [Node 018] No SPAN is established yet, cannot decode command. Requesting a non
                                  ce...
2024-01-30T13:21:01.130Z SERIAL » 0x011b001312149f027f01c51893b499ca48718bd1df6dbf5f2b60051fdb        (29 bytes)
2024-01-30T13:21:01.131Z DRIVER » [Node 018] [REQ] [SendData]
                                  │ transmit options: 0x05
                                  │ callback id:      31
                                  └─[Security2CCNonceReport]
                                      sequence number:  127
                                      SOS:              true
                                      MOS:              false
                                      receiver entropy: 0xc51893b499ca48718bd1df6dbf5f2b60
2024-01-30T13:21:01.133Z SERIAL « [ACK]                                                                   (0x06)
2024-01-30T13:21:01.140Z SERIAL « 0x0104011301e8                                                       (6 bytes)
2024-01-30T13:21:01.141Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:21:01.141Z DRIVER « [RES] [SendData]
                                    was sent: true
2024-01-30T13:21:01.255Z SERIAL « 0x010700131f00000cf8                                                 (9 bytes)
2024-01-30T13:21:01.255Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:21:01.256Z DRIVER « [REQ] [SendData]
                                    callback id:     31
                                    transmit status: OK
2024-01-30T13:21:01.762Z SERIAL « 0x0133000400122d9f03ce011241c71042bf59c9c7973d9044e55c15c18e673ac11 (53 bytes)
                                  20106ee154304a1a2dfb4d8a82e0bffc919058ebb
2024-01-30T13:21:01.764Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:21:01.765Z CNTRLR   [Node 018] [Meter] value[67329]: metadata updated                 [Endpoint 3]
2024-01-30T13:21:01.766Z CNTRLR   [Node 018] [~] [Meter] value[67329]: -205.3 => -205.7             [Endpoint 3]
2024-01-30T13:21:01.766Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 206
                                    │ extensions:
                                    │ · type: SPAN
                                    │   sender EI: 0xc71042bf59c9c7973d9044e55c15c18e
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      3
                                      │ destination: 0
                                      └─[MeterCCReport]
                                          type:       Electric
                                          scale:      kVar
                                          rate type:  Consumed
                                          value:      -205.7
                                          time delta: 0 seconds
2024-01-30T13:21:02.374Z SERIAL « 0x0120000400121a9f03cf009be2255cf3e3a3731b4203d3ade220100b6b11cb21c (34 bytes)
                                  3ee
2024-01-30T13:21:02.375Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:21:02.376Z CNTRLR   [Node 018] [Meter] value[66561]: metadata updated                 [Endpoint 4]
2024-01-30T13:21:02.376Z CNTRLR   [Node 018] [~] [Meter] value[66561]: 236.4 => 236.4               [Endpoint 4]
2024-01-30T13:21:02.377Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 207
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      4
                                      │ destination: 0
                                      └─[MeterCCReport]
                                          type:       Electric
                                          scale:      V
                                          rate type:  Consumed
                                          value:      236.4
                                          time delta: 0 seconds
2024-01-30T13:21:02.991Z SERIAL « 0x0120000400121a9f03d00055bb0bb56ae13f4efeaa5f51cecee2c60723c6ecdc2 (34 bytes)
                                  6bf
2024-01-30T13:21:02.992Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:21:02.992Z CNTRLR   [Node 018] [Meter] value[66817]: metadata updated                 [Endpoint 4]
2024-01-30T13:21:02.993Z CNTRLR   [Node 018] [~] [Meter] value[66817]: 0.482 => 0.482               [Endpoint 4]
2024-01-30T13:21:02.994Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 208
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      4
                                      │ destination: 0
                                      └─[MeterCCReport]
                                          type:       Electric
                                          scale:      A
                                          rate type:  Consumed
                                          value:      0.482
                                          time delta: 0 seconds
2024-01-30T13:21:03.615Z SERIAL « 0x0121000400121b9f03d1007ed6f15e3fa6ddb4f6bbd1270696fe7c5fba05f3ed0 (35 bytes)
                                  f0a3b
2024-01-30T13:21:03.616Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:21:03.617Z CNTRLR   [Node 018] [Meter] value[67329]: metadata updated                 [Endpoint 4]
2024-01-30T13:21:03.617Z CNTRLR   [Node 018] [~] [Meter] value[67329]: -111.5 => -111.4             [Endpoint 4]
2024-01-30T13:21:03.618Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 209
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      4
                                      │ destination: 0
                                      └─[MeterCCReport]
                                          type:       Electric
                                          scale:      kVar
                                          rate type:  Consumed
                                          value:      -111.4
                                          time delta: 0 seconds
2024-01-30T13:21:04.234Z SERIAL « 0x0120000400121a9f03d2008a8e12edd5f4e29a7e61981a23f6867dcac46fef4eb (34 bytes)
                                  bf7
2024-01-30T13:21:04.235Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:21:04.236Z CNTRLR   [Node 018] [Meter] value[67073]: metadata updated                 [Endpoint 4]
2024-01-30T13:21:04.236Z CNTRLR   [Node 018] [~] [Meter] value[67073]: 0.0111 => 0.011              [Endpoint 4]
2024-01-30T13:21:04.237Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 210
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      4
                                      │ destination: 0
                                      └─[MeterCCReport]
                                          type:       Electric
                                          scale:      Power Factor
                                          rate type:  Consumed
                                          value:      0.011
                                          time delta: 0 seconds
2024-01-30T13:21:04.859Z SERIAL « 0x0120000400121a9f03d3008d32d3c675426e72329ad33abf63b8740c716f2fae9 (34 bytes)
                                  946
2024-01-30T13:21:04.860Z SERIAL » [ACK]                                                                   (0x06)
2024-01-30T13:21:04.860Z CNTRLR   [Node 018] [Meter] value[66049]: metadata updated                 [Endpoint 1]
2024-01-30T13:21:04.861Z CNTRLR   [Node 018] [~] [Meter] value[66049]: 49.9 => 41.6                 [Endpoint 1]
2024-01-30T13:21:04.861Z DRIVER « [Node 018] [REQ] [ApplicationCommand]
                                  └─[Security2CCMessageEncapsulation]
                                    │ sequence number: 211
                                    │ security class:  S2_Authenticated
                                    └─[MultiChannelCCCommandEncapsulation]
                                      │ source:      1
                                      │ destination: 0
                                      └─[MeterCCReport]
                                          type:       Electric
                                          scale:      W
                                          rate type:  Consumed
                                          value:      41.6
                                          time delta: 0 seconds

To Reproduce
Steps to reproduce the behavior:

it happens every day....

Expected behavior
getting correct values from the device

Screenshots & Logfiles

Versions:

  • Adapter version: 3.1.0
  • JS-Controller version: 4.0.24
  • Node version: 16.10.2
  • Operating system: Ubuntu 22.04 bare metal

Additional context

@AlCalzone
Copy link
Owner

Duplicate of #1023

@AlCalzone AlCalzone marked this as a duplicate of #1023 Feb 1, 2024
@AlCalzone AlCalzone closed this as not planned Won't fix, can't repro, duplicate, stale Feb 1, 2024
@AlCalzone
Copy link
Owner

Bisschen vergesslich? ;)

@chris299
Copy link
Author

chris299 commented Feb 1, 2024

@AlCalzone das andere issue ist zwar thematisch verwandt, ich habe das nochmal auf gemacht, weil ich evtl. die Antwort in dem anderen Issue nicht vollständig verstanden habe, bzw. mir das auch keine Ruhe lässt, so zwischen den Stühlen zu sitzen mit offensichtlich fehlerhaften Daten.
Wenn mein Gerät, das nicht unerheblich teuer war, fehlerhaft ist, dann sollte das vom Hersteller in Ordnung gebracht werden.

Das Thema damals war für mich die Frage, warum in "produced" nichts drin steht.
Dann kam das re-interview und auf einmal steht was drin, das ich ignorieren kann.
Bei einmaligem Vorkommen wäre das auch ok für mich.
Jetzt sehe ich aber, dass das nicht nur ein Wert einmal ist, sondern es kommen ständig neue und offensichtlich falsche Werte.
Wenn ich also irgendwie sicher nachweisen könnte, dass mein Gerät diesen Quatsch erzeugt (und nicht der USB-dongle oder der IO-Broker-Adapter das missverstehen), dann kann ich das auch bei Fa. Qubino reklamieren.
(Die sagen dazu bisher, dass es sich um eine fehlerhafte Interpretation des Geräte-Interviews handel könnte)

Insofern ist die Frage für mich, ob das o.e. Log schon die unterste Schicht ist, die der Adapter sehen kann, so dass der Fehler beim USB-Dongle oder beim Gerät liegen muss. (Kann das überhaupt am Dongle liegen? wo werden die Nutzdaten entschlüsselt?)

Vielen Dank für Deine Hilfe und deinen Einsatz für den IOBroker und diesen Adapter! 🙏

@AlCalzone
Copy link
Owner

Du, lass mich da mal nachhaken. Ich hab seit neuestem nen direkten Kontakt.

@AlCalzone AlCalzone reopened this Feb 1, 2024
@chris299
Copy link
Author

chris299 commented Feb 2, 2024

@AlCalzone hier noch als Ergänzung der Auszug aus der History des Datenpunkts im IOB. Da kommen immer wieder unsinnige Werte. Für mich sehen die alle nach "consumed" aus, so als ob hin und wieder das Attribut "consumed" auf "produced" "kippt" und die Werte dann im falschen Datenpunkt im IOB landen...
grafik

@chris299
Copy link
Author

chris299 commented Feb 9, 2024

@AlCalzone vielen Dank für Deinen Einsatz:
grafik

@AlCalzone
Copy link
Owner

Habe dich nicht vergessen! Der Support hat mich auf etwas hingewiesen, wo ich selbst erst noch genauer nachprüfen muss, ob das laut Spezifikation so gedacht ist - aber es macht zumindest Sinn für mich:

  • kWh, kVAh, Pulse count und kVarh sind akkumulierte Werte - nur für diese sind separate Zähler (produced, consumed) vorgesehen.
  • W, V, A, Power factor und kVar sind nicht akkumuliert - diese werden negativ bei Produktion und positiv bei Verbrauch.

Als Folge dessen unterscheidet der SmartMeter nicht zwischen Verbrauch und Produktion, wenn der Adapter nach den aktuellen Werten von W, V, A, Power factor und kVar fragt, und liefert in beiden Fällen den gleichen Wert (weil das Flag für Verbrauch/Produktion einfach nicht beachtet wird). Deswegen siehst du direkt nach dem Interview die gleichen Werte in _consumed und _produced.
Wenn sich dann etwas tut, berichtet der SmartMeter alles unter _consumed. Die _produced Werte werden dann nicht mehr aktualisiert.

Wenn also obige Information stimmt, muss ich den Adapter so anpassen, dass er die _produced Datenpunkte für nicht-akkumulierte Werte entfernt.

@chris299
Copy link
Author

@AlCalzone vielen Dank für die Info. 🙏 Das klingt ja durchaus plausibel....

@chris299
Copy link
Author

@AlCalzone gibt es hierzu was neues?

@AlCalzone
Copy link
Owner

Leider nicht. Bin erst seit kurzem aus der Elternzeit zurück und wühle mich durch den Stapel an offenen Themen.

Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment