#Luxtronik 2.0

This documentation is an attempt to document the meaning of data supplied to the Luxtronik webinterface.

Connection

In order to access the data, one has to create a TCP connection to port 8889 (8888 if SW version is below 1.76) and send some magic bytes.

Commands

There are 4 commands, each has sa slightly different data structure for either request and result.

3002 - set parameter

Send 4 bytes with the command, 4 bytes with the parameter number and 4 bytes with the parameter value, all big endian.

0x00 0x00 0x0b 0xba 0x00 0x00 0x00 0x00 0x00 0x00 0x00 0x00

The result is 4 bytes with the command and 4 bytes with the parameter value, all big endian.

3003 - get parameter

Send 4 bytes with the command and 4 null bytes, all big endian.

0x00 0x00 0x0b 0xbb 0x00 0x00 0x00 0x00

The result is 4 bytes with the command and 4 bytes with number of parameters, all big endian. Once one knows the number of parameters, this ambount of 4 byte integers can be read.

3004 - get calculated

Send 4 bytes with the command and 4 null bytes, all big endian.

0x00 0x00 0x0b 0xbc 0x00 0x00 0x00 0x00

The result is 4 bytes with the command, 4 bytes for the status and 4 bytes with number of parameters, all big endian. Once one knows the number of parameters, this ambount of 4 byte integers can be read.

3005 - get visibility

Send 4 bytes with the command and 4 null bytes, all big endian.

0x00 0x00 0x0b 0xbd 0x00 0x00 0x00 0x00

The result is 4 bytes with the command and 4 bytes with number of parameters, all big endian. Once one knows the number of parameters, this ambount of bytes can be read.

Meaning of the data

3003

Number Internal ID Internal Text conversion Notes
0 ID_Transfert_LuxNet
1 ID_Einst_WK_akt
2 ID_Einst_BWS_akt
3 ID_Ba_Hz_akt
4 ID_Ba_Bw_akt
5 ID_Ba_Al_akt
6 ID_SU_FrkdHz
7 ID_SU_FrkdBw
8 ID_SU_FrkdAl
9 ID_Einst_HReg_akt
10 ID_Einst_HzHwMAt_akt
11 ID_Einst_HzHwHKE_akt
12 ID_Einst_HzHKRANH_akt
13 ID_Einst_HzHKRABS_akt
14 ID_Einst_HzMK1E_akt
15 ID_Einst_HzMK1ANH_akt
16 ID_Einst_HzMK1ABS_akt
17 ID_Einst_HzFtRl_akt
18 ID_Einst_HzFtMK1Vl_akt
19 ID_Einst_SUBW_akt
20 ID_Einst_BwTDI_akt_MO
21 ID_Einst_BwTDI_akt_DI
22 ID_Einst_BwTDI_akt_MI
23 ID_Einst_BwTDI_akt_DO
24 ID_Einst_BwTDI_akt_FR
25 ID_Einst_BwTDI_akt_SA
26 ID_Einst_BwTDI_akt_SO
27 ID_Einst_BwTDI_akt_AL
28 ID_Einst_AnlKonf_akt
29 ID_Einst_Sprache_akt
30 ID_Switchoff_Zahler
31 ID_Switchoff_index
32 ID_Einst_EvuTyp_akt
33 ID_Einst_RFVEinb_akt
34 ID_Einst_AbtZykMax_akt
35 ID_Einst_HREinb_akt
36 ID_Einst_ZWE1Art_akt
37 ID_Einst_ZWE1Fkt_akt
38 ID_Einst_ZWE2Art_akt
39 ID_Einst_ZWE2Fkt_akt
40 ID_Einst_BWBer_akt
41 ID_Einst_En_Inst
42 ID_Einst_MK1Typ_akt
43 ID_Einst_ABTLuft_akt
44 ID_Einst_TLAbt_akt
45 ID_Einst_LAbtTime_akt
46 ID_Einst_ASDTyp_akt
47 ID_Einst_LGST_akt
48 ID_Einst_BwWpTime_akt
49 ID_Einst_Popt_akt
50 ID_Einst_Kurzprog_akt
51 ID_Timer_Kurzprog_akt
52 ID_Einst_ManAbt_akt
53 ID_Einst_Ahz_akt
54 ID_Einst_TVL_Ahz_1
55 ID_Einst_TVL_Ahz_2
56 ID_Einst_TVL_Ahz_3
57 ID_Einst_TVL_Ahz_4
58 ID_Einst_TVL_Ahz_5
59 ID_Einst_TVL_Ahz_6
60 ID_Einst_TVL_Ahz_7
61 ID_Einst_TVL_Ahz_8
62 ID_Einst_TVL_Ahz_9
63 ID_Einst_TVL_Ahz_10
64 ID_Einst_TVL_Std_1
65 ID_Einst_TVL_Std_2
66 ID_Einst_TVL_Std_3
67 ID_Einst_TVL_Std_4
68 ID_Einst_TVL_Std_5
69 ID_Einst_TVL_Std_6
70 ID_Einst_TVL_Std_7
71 ID_Einst_TVL_Std_8
72 ID_Einst_TVL_Std_9
73 ID_Einst_TVL_Std_10
74 ID_Einst_BWS_Hyst_akt
75 ID_Temp_TBW_BwHD_saved
76 ID_Einst_ABT1_akt
77 ID_Einst_LABTpaus_akt
78 ID_AHZ_state_akt
79 ID_Sollwert_TRL_HZ_AHZ
80 ID_AHP_valid_records
81 ID_Timer_AHZ_akt
82 ID_Einst_BWTINP_akt
83 ID_Einst_ZUPTYP_akt
84 ID_Sollwert_TLG_max
85 ID_Einst_BWZIP_akt
86 ID_Einst_ERRmZWE_akt
87 ID_Einst_TRBegr_akt
88 ID_Einst_HRHyst_akt
89 ID_Einst_TRErhmax_akt
90 ID_Einst_ZWEFreig_akt
91 ID_Einst_TAmax_akt
92 ID_Einst_TAmin_akt
93 ID_Einst_TWQmin_akt
94 ID_Einst_THGmax_akt
95 ID_Einst_FRGT2VD_akt
96 ID_Einst_TV2VDBW_akt
97 ID_Einst_SuAll_akt
98 ID_Einst_TAbtEnd_akt
99 ID_Einst_NrKlingel_akt
100 ID_Einst_BWStyp_akt
101 ID_Einst_ABT2_akt
102 ID_Einst_UeVd_akt
103 ID_Einst_RTyp_akt
104 ID_Einst_AhpM_akt
105 ID_Soll_BWS_akt
106 ID_Timer_Password
107 ID_Einst_Zugangscode
108 ID_Einst_BA_Kuehl_akt
109 ID_Sollwert_Kuehl1_akt
110 ID_Einst_KuehlFreig_akt
111 ID_Einst_TAbsMin_akt
112 ID_TWQmin_saved
113 ID_CWP_saved
114 ID_Einst_Anode_akt
115 ID_Timer_pexoff_akt
116 ID_Einst_AnlPrio_Hzakt
117 ID_Einst_AnlPrio_Bwakt
118 ID_Einst_AnlPrio_Swakt
119 ID_Ba_Sw_akt
120 ID_Einst_RTypMK1_akt
121 ID_Einst_RTypMK2_akt
122 ID_Einst_TDC_Ein_akt
123 ID_Einst_TDC_Aus_akt
124 ID_Einst_TDC_Max_akt
125 ID_Einst_HysHzExEn_akt
126 ID_Einst_HysBwExEn_akt
127 ID_Einst_ZWE3Art_akt
128 ID_Einst_ZWE3Fkt_akt
129 ID_Einst_HzSup_akt
130 ID_Einst_MK2Typ_akt
131 ID_Einst_KuTyp_akt
132 ID_Sollwert_KuCft1_akt
133 ID_Sollwert_KuCft2_akt
134 ID_Sollwert_AtDif1_akt
135 ID_Sollwert_AtDif2_akt
136 ID_SU_FrkdSwb
137 ID_Einst_SwbBer_akt
138 ID_Einst_TV2VDSWB_akt
139 ID_Einst_MinSwan_Time_akt
140 ID_Einst_SuMk2_akt
141 ID_Einst_HzMK2E_akt
142 ID_Einst_HzMK2ANH_akt
143 ID_Einst_HzMK2ABS_akt
144 ID_Einst_HzMK2Hgr_akt
145 ID_Einst_HzFtMK2Vl_akt
146 ID_Temp_THG_BwHD_saved
147 ID_Temp_TA_BwHD_saved
148 ID_Einst_BwHup_akt
149 ID_Einst_TVLmax_akt
150 ID_Einst_MK1LzFaktor_akt
151 ID_Einst_MK2LzFaktor_akt
152 ID_Einst_MK1PerFaktor_akt
153 ID_Einst_MK2PerFaktor_akt
154 ID_Entl_Zyklus_akt
155 ID_Einst_Entl_time_akt
156 ID_Entl_Pause
157 ID_Entl_timer
158 ID_Einst_Entl_akt
159 ID_Ahz_HLeist_confirmed
160 ID_FirstInit_akt
161 ID_Einst_SuAll_akt2
162 ID_Einst_SuAllWo_zeit_0_0
163 ID_Einst_SuAllWo_zeit_0_1
164 ID_Einst_SuAllWo_zeit_1_0
165 ID_Einst_SuAllWo_zeit_1_1
166 ID_Einst_SuAllWo_zeit_2_0
167 ID_Einst_SuAllWo_zeit_2_1
168 ID_Einst_SuAll25_zeit_0_0
169 ID_Einst_SuAll25_zeit_0_1
170 ID_Einst_SuAll25_zeit_1_0
171 ID_Einst_SuAll25_zeit_1_1
172 ID_Einst_SuAll25_zeit_2_0
173 ID_Einst_SuAll25_zeit_2_1
174 ID_Einst_SuAll25_zeit_0_2
175 ID_Einst_SuAll25_zeit_0_3
176 ID_Einst_SuAll25_zeit_1_2
177 ID_Einst_SuAll25_zeit_1_3
178 ID_Einst_SuAll25_zeit_2_2
179 ID_Einst_SuAll25_zeit_2_3
180 ID_Einst_SuAllTg_zeit_0_0
181 ID_Einst_SuAllTg_zeit_0_1
182 ID_Einst_SuAllTg_zeit_1_0
183 ID_Einst_SuAllTg_zeit_1_1
184 ID_Einst_SuAllTg_zeit_2_0
185 ID_Einst_SuAllTg_zeit_2_1
186 ID_Einst_SuAllTg_zeit_0_2
187 ID_Einst_SuAllTg_zeit_0_3
188 ID_Einst_SuAllTg_zeit_1_2
189 ID_Einst_SuAllTg_zeit_1_3
190 ID_Einst_SuAllTg_zeit_2_2
191 ID_Einst_SuAllTg_zeit_2_3
192 ID_Einst_SuAllTg_zeit_0_4
193 ID_Einst_SuAllTg_zeit_0_5
194 ID_Einst_SuAllTg_zeit_1_4
195 ID_Einst_SuAllTg_zeit_1_5
196 ID_Einst_SuAllTg_zeit_2_4
197 ID_Einst_SuAllTg_zeit_2_5
198 ID_Einst_SuAllTg_zeit_0_6
199 ID_Einst_SuAllTg_zeit_0_7
200 ID_Einst_SuAllTg_zeit_1_6
201 ID_Einst_SuAllTg_zeit_1_7
202 ID_Einst_SuAllTg_zeit_2_6
203 ID_Einst_SuAllTg_zeit_2_7
204 ID_Einst_SuAllTg_zeit_0_8
205 ID_Einst_SuAllTg_zeit_0_9
206 ID_Einst_SuAllTg_zeit_1_8
207 ID_Einst_SuAllTg_zeit_1_9
208 ID_Einst_SuAllTg_zeit_2_8
209 ID_Einst_SuAllTg_zeit_2_9
210 ID_Einst_SuAllTg_zeit_0_10
211 ID_Einst_SuAllTg_zeit_0_11
212 ID_Einst_SuAllTg_zeit_1_10
213 ID_Einst_SuAllTg_zeit_1_11
214 ID_Einst_SuAllTg_zeit_2_10
215 ID_Einst_SuAllTg_zeit_2_11
216 ID_Einst_SuAllTg_zeit_0_12
217 ID_Einst_SuAllTg_zeit_0_13
218 ID_Einst_SuAllTg_zeit_1_12
219 ID_Einst_SuAllTg_zeit_1_13
220 ID_Einst_SuAllTg_zeit_2_12
221 ID_Einst_SuAllTg_zeit_2_13
222 ID_Einst_SuHkr_akt
223 ID_Einst_SuHkrW0_zeit_0_0
224 ID_Einst_SuHkrW0_zeit_0_1
225 ID_Einst_SuHkrW0_zeit_1_0
226 ID_Einst_SuHkrW0_zeit_1_1
227 ID_Einst_SuHkrW0_zeit_2_0
228 ID_Einst_SuHkrW0_zeit_2_1
229 ID_Einst_SuHkr25_zeit_0_0
230 ID_Einst_SuHkr25_zeit_0_1
231 ID_Einst_SuHkr25_zeit_1_0
232 ID_Einst_SuHkr25_zeit_1_1
233 ID_Einst_SuHkr25_zeit_2_0
234 ID_Einst_SuHkr25_zeit_2_1
235 ID_Einst_SuHkr25_zeit_0_2
236 ID_Einst_SuHkr25_zeit_0_3
237 ID_Einst_SuHkr25_zeit_1_2
238 ID_Einst_SuHkr25_zeit_1_3
239 ID_Einst_SuHkr25_zeit_2_2
240 ID_Einst_SuHkr25_zeit_2_3
241 ID_Einst_SuHkrTG_zeit_0_0
242 ID_Einst_SuHkrTG_zeit_0_1
243 ID_Einst_SuHkrTG_zeit_1_0
244 ID_Einst_SuHkrTG_zeit_1_1
245 ID_Einst_SuHkrTG_zeit_2_0
246 ID_Einst_SuHkrTG_zeit_2_1
247 ID_Einst_SuHkrTG_zeit_0_2
248 ID_Einst_SuHkrTG_zeit_0_3
249 ID_Einst_SuHkrTG_zeit_1_2
250 ID_Einst_SuHkrTG_zeit_1_3
251 ID_Einst_SuHkrTG_zeit_2_2
252 ID_Einst_SuHkrTG_zeit_2_3
253 ID_Einst_SuHkrTG_zeit_0_4
254 ID_Einst_SuHkrTG_zeit_0_5
255 ID_Einst_SuHkrTG_zeit_1_4
256 ID_Einst_SuHkrTG_zeit_1_5
257 ID_Einst_SuHkrTG_zeit_2_4
258 ID_Einst_SuHkrTG_zeit_2_5
259 ID_Einst_SuHkrTG_zeit_0_6
260 ID_Einst_SuHkrTG_zeit_0_7
261 ID_Einst_SuHkrTG_zeit_1_6
262 ID_Einst_SuHkrTG_zeit_1_7
263 ID_Einst_SuHkrTG_zeit_2_6
264 ID_Einst_SuHkrTG_zeit_2_7
265 ID_Einst_SuHkrTG_zeit_0_8
266 ID_Einst_SuHkrTG_zeit_0_9
267 ID_Einst_SuHkrTG_zeit_1_8
268 ID_Einst_SuHkrTG_zeit_1_9
269 ID_Einst_SuHkrTG_zeit_2_8
270 ID_Einst_SuHkrTG_zeit_2_9
271 ID_Einst_SuHkrTG_zeit_0_10
272 ID_Einst_SuHkrTG_zeit_0_11
273 ID_Einst_SuHkrTG_zeit_1_10
274 ID_Einst_SuHkrTG_zeit_1_11
275 ID_Einst_SuHkrTG_zeit_2_10
276 ID_Einst_SuHkrTG_zeit_2_11
277 ID_Einst_SuHkrTG_zeit_0_12
278 ID_Einst_SuHkrTG_zeit_0_13
279 ID_Einst_SuHkrTG_zeit_1_12
280 ID_Einst_SuHkrTG_zeit_1_13
281 ID_Einst_SuHkrTG_zeit_2_12
282 ID_Einst_SuHkrTG_zeit_2_13
283 ID_Einst_SuMk1_akt
284 ID_Einst_SuMk1W0_zeit_0_0
285 ID_Einst_SuMk1W0_zeit_0_1
286 ID_Einst_SuMk1W0_zeit_1_0
287 ID_Einst_SuMk1W0_zeit_1_1
288 ID_Einst_SuMk1W0_zeit_2_0
289 ID_Einst_SuMk1W0_zeit_2_1
290 ID_Einst_SuMk125_zeit_0_0
291 ID_Einst_SuMk125_zeit_0_1
292 ID_Einst_SuMk125_zeit_1_0
293 ID_Einst_SuMk125_zeit_1_1
294 ID_Einst_SuMk125_zeit_2_0
295 ID_Einst_SuMk125_zeit_2_1
296 ID_Einst_SuMk125_zeit_0_2
297 ID_Einst_SuMk125_zeit_0_3
298 ID_Einst_SuMk125_zeit_1_2
299 ID_Einst_SuMk125_zeit_1_3
300 ID_Einst_SuMk125_zeit_2_2
301 ID_Einst_SuMk125_zeit_2_3
302 ID_Einst_SuMk1TG_zeit_0_0
303 ID_Einst_SuMk1TG_zeit_0_1
304 ID_Einst_SuMk1TG_zeit_1_0
305 ID_Einst_SuMk1TG_zeit_1_1
306 ID_Einst_SuMk1TG_zeit_2_0
307 ID_Einst_SuMk1TG_zeit_2_1
308 ID_Einst_SuMk1TG_zeit_0_2
309 ID_Einst_SuMk1TG_zeit_0_3
310 ID_Einst_SuMk1TG_zeit_1_2
311 ID_Einst_SuMk1TG_zeit_1_3
312 ID_Einst_SuMk1TG_zeit_2_2
313 ID_Einst_SuMk1TG_zeit_2_3
314 ID_Einst_SuMk1TG_zeit_0_4
315 ID_Einst_SuMk1TG_zeit_0_5
316 ID_Einst_SuMk1TG_zeit_1_4
317 ID_Einst_SuMk1TG_zeit_1_5
318 ID_Einst_SuMk1TG_zeit_2_4
319 ID_Einst_SuMk1TG_zeit_2_5
320 ID_Einst_SuMk1TG_zeit_0_6
321 ID_Einst_SuMk1TG_zeit_0_7
322 ID_Einst_SuMk1TG_zeit_1_6
323 ID_Einst_SuMk1TG_zeit_1_7
324 ID_Einst_SuMk1TG_zeit_2_6
325 ID_Einst_SuMk1TG_zeit_2_7
326 ID_Einst_SuMk1TG_zeit_0_8
327 ID_Einst_SuMk1TG_zeit_0_9
328 ID_Einst_SuMk1TG_zeit_1_8
329 ID_Einst_SuMk1TG_zeit_1_9
330 ID_Einst_SuMk1TG_zeit_2_8
331 ID_Einst_SuMk1TG_zeit_2_9
332 ID_Einst_SuMk1TG_zeit_0_10
333 ID_Einst_SuMk1TG_zeit_0_11
334 ID_Einst_SuMk1TG_zeit_1_10
335 ID_Einst_SuMk1TG_zeit_1_11
336 ID_Einst_SuMk1TG_zeit_2_10
337 ID_Einst_SuMk1TG_zeit_2_11
338 ID_Einst_SuMk1TG_zeit_0_12
339 ID_Einst_SuMk1TG_zeit_0_13
340 ID_Einst_SuMk1TG_zeit_1_12
341 ID_Einst_SuMk1TG_zeit_1_13
342 ID_Einst_SuMk1TG_zeit_2_12
343 ID_Einst_SuMk1TG_zeit_2_13
344 ID_Einst_SuMk2_akt2
345 ID_Einst_SuMk2Wo_zeit_0_0
346 ID_Einst_SuMk2Wo_zeit_0_1
347 ID_Einst_SuMk2Wo_zeit_1_0
348 ID_Einst_SuMk2Wo_zeit_1_1
349 ID_Einst_SuMk2Wo_zeit_2_0
350 ID_Einst_SuMk2Wo_zeit_2_1
351 ID_Einst_SuMk225_zeit_0_0
352 ID_Einst_SuMk225_zeit_0_1
353 ID_Einst_SuMk225_zeit_1_0
354 ID_Einst_SuMk225_zeit_1_1
355 ID_Einst_SuMk225_zeit_2_0
356 ID_Einst_SuMk225_zeit_2_1
357 ID_Einst_SuMk225_zeit_0_2
358 ID_Einst_SuMk225_zeit_0_3
359 ID_Einst_SuMk225_zeit_1_2
360 ID_Einst_SuMk225_zeit_1_3
361 ID_Einst_SuMk225_zeit_2_2
362 ID_Einst_SuMk225_zeit_2_3
363 ID_Einst_SuMk2Tg_zeit_0_0
364 ID_Einst_SuMk2Tg_zeit_0_1
365 ID_Einst_SuMk2Tg_zeit_1_0
366 ID_Einst_SuMk2Tg_zeit_1_1
367 ID_Einst_SuMk2Tg_zeit_2_0
368 ID_Einst_SuMk2Tg_zeit_2_1
369 ID_Einst_SuMk2Tg_zeit_0_2
370 ID_Einst_SuMk2Tg_zeit_0_3
371 ID_Einst_SuMk2Tg_zeit_1_2
372 ID_Einst_SuMk2Tg_zeit_1_3
373 ID_Einst_SuMk2Tg_zeit_2_2
374 ID_Einst_SuMk2Tg_zeit_2_3
375 ID_Einst_SuMk2Tg_zeit_0_4
376 ID_Einst_SuMk2Tg_zeit_0_5
377 ID_Einst_SuMk2Tg_zeit_1_4
378 ID_Einst_SuMk2Tg_zeit_1_5
379 ID_Einst_SuMk2Tg_zeit_2_4
380 ID_Einst_SuMk2Tg_zeit_2_5
381 ID_Einst_SuMk2Tg_zeit_0_6
382 ID_Einst_SuMk2Tg_zeit_0_7
383 ID_Einst_SuMk2Tg_zeit_1_6
384 ID_Einst_SuMk2Tg_zeit_1_7
385 ID_Einst_SuMk2Tg_zeit_2_6
386 ID_Einst_SuMk2Tg_zeit_2_7
387 ID_Einst_SuMk2Tg_zeit_0_8
388 ID_Einst_SuMk2Tg_zeit_0_9
389 ID_Einst_SuMk2Tg_zeit_1_8
390 ID_Einst_SuMk2Tg_zeit_1_9
391 ID_Einst_SuMk2Tg_zeit_2_8
392 ID_Einst_SuMk2Tg_zeit_2_9
393 ID_Einst_SuMk2Tg_zeit_0_10
394 ID_Einst_SuMk2Tg_zeit_0_11
395 ID_Einst_SuMk2Tg_zeit_1_10
396 ID_Einst_SuMk2Tg_zeit_1_11
397 ID_Einst_SuMk2Tg_zeit_2_10
398 ID_Einst_SuMk2Tg_zeit_2_11
399 ID_Einst_SuMk2Tg_zeit_0_12
400 ID_Einst_SuMk2Tg_zeit_0_13
401 ID_Einst_SuMk2Tg_zeit_1_12
402 ID_Einst_SuMk2Tg_zeit_1_13
403 ID_Einst_SuMk2Tg_zeit_2_12
404 ID_Einst_SuMk2Tg_zeit_2_13
405 ID_Einst_SUBW_akt2
406 ID_Einst_SuBwWO_zeit_0_0
407 ID_Einst_SuBwWO_zeit_0_1
408 ID_Einst_SuBwWO_zeit_1_0
409 ID_Einst_SuBwWO_zeit_1_1
410 ID_Einst_SuBwWO_zeit_2_0
411 ID_Einst_SuBwWO_zeit_2_1
412 ID_Einst_SuBwWO_zeit_3_0
413 ID_Einst_SuBwWO_zeit_3_1
414 ID_Einst_SuBwWO_zeit_4_0
415 ID_Einst_SuBwWO_zeit_4_1
416 ID_Einst_SuBw25_zeit_0_0
417 ID_Einst_SuBw25_zeit_0_1
418 ID_Einst_SuBw25_zeit_1_0
419 ID_Einst_SuBw25_zeit_1_1
420 ID_Einst_SuBw25_zeit_2_0
421 ID_Einst_SuBw25_zeit_2_1
422 ID_Einst_SuBw25_zeit_3_0
423 ID_Einst_SuBw25_zeit_3_1
424 ID_Einst_SuBw25_zeit_4_0
425 ID_Einst_SuBw25_zeit_4_1
426 ID_Einst_SuBw25_zeit_0_2
427 ID_Einst_SuBw25_zeit_0_3
428 ID_Einst_SuBw25_zeit_1_2
429 ID_Einst_SuBw25_zeit_1_3
430 ID_Einst_SuBw25_zeit_2_2
431 ID_Einst_SuBw25_zeit_2_3
432 ID_Einst_SuBw25_zeit_3_2
433 ID_Einst_SuBw25_zeit_3_3
434 ID_Einst_SuBw25_zeit_4_2
435 ID_Einst_SuBw25_zeit_4_3
436 ID_Einst_SuBwTG_zeit_0_0
437 ID_Einst_SuBwTG_zeit_0_1
438 ID_Einst_SuBwTG_zeit_1_0
439 ID_Einst_SuBwTG_zeit_1_1
440 ID_Einst_SuBwTG_zeit_2_0
441 ID_Einst_SuBwTG_zeit_2_1
442 ID_Einst_SuBwTG_zeit_3_0
443 ID_Einst_SuBwTG_zeit_3_1
444 ID_Einst_SuBwTG_zeit_4_0
445 ID_Einst_SuBwTG_zeit_4_1
446 ID_Einst_SuBwTG_zeit_0_2
447 ID_Einst_SuBwTG_zeit_0_3
448 ID_Einst_SuBwTG_zeit_1_2
449 ID_Einst_SuBwTG_zeit_1_3
450 ID_Einst_SuBwTG_zeit_2_2
451 ID_Einst_SuBwTG_zeit_2_3
452 ID_Einst_SuBwTG_zeit_3_2
453 ID_Einst_SuBwTG_zeit_3_3
454 ID_Einst_SuBwTG_zeit_4_2
455 ID_Einst_SuBwTG_zeit_4_3
456 ID_Einst_SuBwTG_zeit_0_4
457 ID_Einst_SuBwTG_zeit_0_5
458 ID_Einst_SuBwTG_zeit_1_4
459 ID_Einst_SuBwTG_zeit_1_5
460 ID_Einst_SuBwTG_zeit_2_4
461 ID_Einst_SuBwTG_zeit_2_5
462 ID_Einst_SuBwTG_zeit_3_4
463 ID_Einst_SuBwTG_zeit_3_5
464 ID_Einst_SuBwTG_zeit_4_4
465 ID_Einst_SuBwTG_zeit_4_5
466 ID_Einst_SuBwTG_zeit_0_6
467 ID_Einst_SuBwTG_zeit_0_7
468 ID_Einst_SuBwTG_zeit_1_6
469 ID_Einst_SuBwTG_zeit_1_7
470 ID_Einst_SuBwTG_zeit_2_6
471 ID_Einst_SuBwTG_zeit_2_7
472 ID_Einst_SuBwTG_zeit_3_6
473 ID_Einst_SuBwTG_zeit_3_7
474 ID_Einst_SuBwTG_zeit_4_6
475 ID_Einst_SuBwTG_zeit_4_7
476 ID_Einst_SuBwTG_zeit_0_8
477 ID_Einst_SuBwTG_zeit_0_9
478 ID_Einst_SuBwTG_zeit_1_8
479 ID_Einst_SuBwTG_zeit_1_9
480 ID_Einst_SuBwTG_zeit_2_8
481 ID_Einst_SuBwTG_zeit_2_9
482 ID_Einst_SuBwTG_zeit_3_8
483 ID_Einst_SuBwTG_zeit_3_9
484 ID_Einst_SuBwTG_zeit_4_8
485 ID_Einst_SuBwTG_zeit_4_9
486 ID_Einst_SuBwTG_zeit_0_10
487 ID_Einst_SuBwTG_zeit_0_11
488 ID_Einst_SuBwTG_zeit_1_10
489 ID_Einst_SuBwTG_zeit_1_11
490 ID_Einst_SuBwTG_zeit_2_10
491 ID_Einst_SuBwTG_zeit_2_11
492 ID_Einst_SuBwTG_zeit_3_10
493 ID_Einst_SuBwTG_zeit_3_11
494 ID_Einst_SuBwTG_zeit_4_10
495 ID_Einst_SuBwTG_zeit_4_11
496 ID_Einst_SuBwTG_zeit_0_12
497 ID_Einst_SuBwTG_zeit_0_13
498 ID_Einst_SuBwTG_zeit_1_12
499 ID_Einst_SuBwTG_zeit_1_13
500 ID_Einst_SuBwTG_zeit_2_12
501 ID_Einst_SuBwTG_zeit_2_13
502 ID_Einst_SuBwTG_zeit_3_12
503 ID_Einst_SuBwTG_zeit_3_13
504 ID_Einst_SuBwTG_zeit_4_12
505 ID_Einst_SuBwTG_zeit_4_13
506 ID_Einst_SuZIP_akt
507 ID_Einst_SuZIPWo_zeit_0_0
508 ID_Einst_SuZIPWo_zeit_0_1
509 ID_Einst_SuZIPWo_zeit_1_0
510 ID_Einst_SuZIPWo_zeit_1_1
511 ID_Einst_SuZIPWo_zeit_2_0
512 ID_Einst_SuZIPWo_zeit_2_1
513 ID_Einst_SuZIPWo_zeit_3_0
514 ID_Einst_SuZIPWo_zeit_3_1
515 ID_Einst_SuZIPWo_zeit_4_0
516 ID_Einst_SuZIPWo_zeit_4_1
517 ID_Einst_SuZIP25_zeit_0_0
518 ID_Einst_SuZIP25_zeit_0_1
519 ID_Einst_SuZIP25_zeit_1_0
520 ID_Einst_SuZIP25_zeit_1_1
521 ID_Einst_SuZIP25_zeit_2_0
522 ID_Einst_SuZIP25_zeit_2_1
523 ID_Einst_SuZIP25_zeit_3_0
524 ID_Einst_SuZIP25_zeit_3_1
525 ID_Einst_SuZIP25_zeit_4_0
526 ID_Einst_SuZIP25_zeit_4_1
527 ID_Einst_SuZIP25_zeit_0_2
528 ID_Einst_SuZIP25_zeit_0_3
529 ID_Einst_SuZIP25_zeit_1_2
530 ID_Einst_SuZIP25_zeit_1_3
531 ID_Einst_SuZIP25_zeit_2_2
532 ID_Einst_SuZIP25_zeit_2_3
533 ID_Einst_SuZIP25_zeit_3_2
534 ID_Einst_SuZIP25_zeit_3_3
535 ID_Einst_SuZIP25_zeit_4_2
536 ID_Einst_SuZIP25_zeit_4_3
537 ID_Einst_SuZIPTg_zeit_0_0
538 ID_Einst_SuZIPTg_zeit_0_1
539 ID_Einst_SuZIPTg_zeit_1_0
540 ID_Einst_SuZIPTg_zeit_1_1
541 ID_Einst_SuZIPTg_zeit_2_0
542 ID_Einst_SuZIPTg_zeit_2_1
543 ID_Einst_SuZIPTg_zeit_3_0
544 ID_Einst_SuZIPTg_zeit_3_1
545 ID_Einst_SuZIPTg_zeit_4_0
546 ID_Einst_SuZIPTg_zeit_4_1
547 ID_Einst_SuZIPTg_zeit_0_2
548 ID_Einst_SuZIPTg_zeit_0_3
549 ID_Einst_SuZIPTg_zeit_1_2
550 ID_Einst_SuZIPTg_zeit_1_3
551 ID_Einst_SuZIPTg_zeit_2_2
552 ID_Einst_SuZIPTg_zeit_2_3
553 ID_Einst_SuZIPTg_zeit_3_2
554 ID_Einst_SuZIPTg_zeit_3_3
555 ID_Einst_SuZIPTg_zeit_4_2
556 ID_Einst_SuZIPTg_zeit_4_3
557 ID_Einst_SuZIPTg_zeit_0_4
558 ID_Einst_SuZIPTg_zeit_0_5
559 ID_Einst_SuZIPTg_zeit_1_4
560 ID_Einst_SuZIPTg_zeit_1_5
561 ID_Einst_SuZIPTg_zeit_2_4
562 ID_Einst_SuZIPTg_zeit_2_5
563 ID_Einst_SuZIPTg_zeit_3_4
564 ID_Einst_SuZIPTg_zeit_3_5
565 ID_Einst_SuZIPTg_zeit_4_4
566 ID_Einst_SuZIPTg_zeit_4_5
567 ID_Einst_SuZIPTg_zeit_0_6
568 ID_Einst_SuZIPTg_zeit_0_7
569 ID_Einst_SuZIPTg_zeit_1_6
570 ID_Einst_SuZIPTg_zeit_1_7
571 ID_Einst_SuZIPTg_zeit_2_6
572 ID_Einst_SuZIPTg_zeit_2_7
573 ID_Einst_SuZIPTg_zeit_3_6
574 ID_Einst_SuZIPTg_zeit_3_7
575 ID_Einst_SuZIPTg_zeit_4_6
576 ID_Einst_SuZIPTg_zeit_4_7
577 ID_Einst_SuZIPTg_zeit_0_8
578 ID_Einst_SuZIPTg_zeit_0_9
579 ID_Einst_SuZIPTg_zeit_1_8
580 ID_Einst_SuZIPTg_zeit_1_9
581 ID_Einst_SuZIPTg_zeit_2_8
582 ID_Einst_SuZIPTg_zeit_2_9
583 ID_Einst_SuZIPTg_zeit_3_8
584 ID_Einst_SuZIPTg_zeit_3_9
585 ID_Einst_SuZIPTg_zeit_4_8
586 ID_Einst_SuZIPTg_zeit_4_9
587 ID_Einst_SuZIPTg_zeit_0_10
588 ID_Einst_SuZIPTg_zeit_0_11
589 ID_Einst_SuZIPTg_zeit_1_10
590 ID_Einst_SuZIPTg_zeit_1_11
591 ID_Einst_SuZIPTg_zeit_2_10
592 ID_Einst_SuZIPTg_zeit_2_11
593 ID_Einst_SuZIPTg_zeit_3_10
594 ID_Einst_SuZIPTg_zeit_3_11
595 ID_Einst_SuZIPTg_zeit_4_10
596 ID_Einst_SuZIPTg_zeit_4_11
597 ID_Einst_SuZIPTg_zeit_0_12
598 ID_Einst_SuZIPTg_zeit_0_13
599 ID_Einst_SuZIPTg_zeit_1_12
600 ID_Einst_SuZIPTg_zeit_1_13
601 ID_Einst_SuZIPTg_zeit_2_12
602 ID_Einst_SuZIPTg_zeit_2_13
603 ID_Einst_SuZIPTg_zeit_3_12
604 ID_Einst_SuZIPTg_zeit_3_13
605 ID_Einst_SuZIPTg_zeit_4_12
606 ID_Einst_SuZIPTg_zeit_4_13
607 ID_Einst_SuSwb_akt
608 ID_Einst_SuSwbWo_zeit_0_0
609 ID_Einst_SuSwbWo_zeit_0_1
610 ID_Einst_SuSwbWo_zeit_1_0
611 ID_Einst_SuSwbWo_zeit_1_1
612 ID_Einst_SuSwbWo_zeit_2_0
613 ID_Einst_SuSwbWo_zeit_2_1
614 ID_Einst_SuSwb25_zeit_0_0
615 ID_Einst_SuSwb25_zeit_0_1
616 ID_Einst_SuSwb25_zeit_1_0
617 ID_Einst_SuSwb25_zeit_1_1
618 ID_Einst_SuSwb25_zeit_2_0
619 ID_Einst_SuSwb25_zeit_2_1
620 ID_Einst_SuSwb25_zeit_0_2
621 ID_Einst_SuSwb25_zeit_0_3
622 ID_Einst_SuSwb25_zeit_1_2
623 ID_Einst_SuSwb25_zeit_1_3
624 ID_Einst_SuSwb25_zeit_2_2
625 ID_Einst_SuSwb25_zeit_2_3
626 ID_Einst_SuSwbTg_zeit_0_0
627 ID_Einst_SuSwbTg_zeit_0_1
628 ID_Einst_SuSwbTg_zeit_1_0
629 ID_Einst_SuSwbTg_zeit_1_1
630 ID_Einst_SuSwbTg_zeit_2_0
631 ID_Einst_SuSwbTg_zeit_2_1
632 ID_Einst_SuSwbTg_zeit_0_2
633 ID_Einst_SuSwbTg_zeit_0_3
634 ID_Einst_SuSwbTg_zeit_1_2
635 ID_Einst_SuSwbTg_zeit_1_3
636 ID_Einst_SuSwbTg_zeit_2_2
637 ID_Einst_SuSwbTg_zeit_2_3
638 ID_Einst_SuSwbTg_zeit_0_4
639 ID_Einst_SuSwbTg_zeit_0_5
640 ID_Einst_SuSwbTg_zeit_1_4
641 ID_Einst_SuSwbTg_zeit_1_5
642 ID_Einst_SuSwbTg_zeit_2_4
643 ID_Einst_SuSwbTg_zeit_2_5
644 ID_Einst_SuSwbTg_zeit_0_6
645 ID_Einst_SuSwbTg_zeit_0_7
646 ID_Einst_SuSwbTg_zeit_1_6
647 ID_Einst_SuSwbTg_zeit_1_7
648 ID_Einst_SuSwbTg_zeit_2_6
649 ID_Einst_SuSwbTg_zeit_2_7
650 ID_Einst_SuSwbTg_zeit_0_8
651 ID_Einst_SuSwbTg_zeit_0_9
652 ID_Einst_SuSwbTg_zeit_1_8
653 ID_Einst_SuSwbTg_zeit_1_9
654 ID_Einst_SuSwbTg_zeit_2_8
655 ID_Einst_SuSwbTg_zeit_2_9
656 ID_Einst_SuSwbTg_zeit_0_10
657 ID_Einst_SuSwbTg_zeit_0_11
658 ID_Einst_SuSwbTg_zeit_1_10
659 ID_Einst_SuSwbTg_zeit_1_11
660 ID_Einst_SuSwbTg_zeit_2_10
661 ID_Einst_SuSwbTg_zeit_2_11
662 ID_Einst_SuSwbTg_zeit_0_12
663 ID_Einst_SuSwbTg_zeit_0_13
664 ID_Einst_SuSwbTg_zeit_1_12
665 ID_Einst_SuSwbTg_zeit_1_13
666 ID_Einst_SuSwbTg_zeit_2_12
667 ID_Einst_SuSwbTg_zeit_2_13
668 ID_Zaehler_BetrZeitWP
669 ID_Zaehler_BetrZeitVD1
670 ID_Zaehler_BetrZeitVD2
671 ID_Zaehler_BetrZeitZWE1
672 ID_Zaehler_BetrZeitZWE2
673 ID_Zaehler_BetrZeitZWE3
674 ID_Zaehler_BetrZeitImpVD1
675 ID_Zaehler_BetrZeitImpVD2
676 ID_Zaehler_BetrZeitEZMVD1
677 ID_Zaehler_BetrZeitEZMVD2
678 ID_Einst_Entl_Typ_0
679 ID_Einst_Entl_Typ_1
680 ID_Einst_Entl_Typ_2
681 ID_Einst_Entl_Typ_3
682 ID_Einst_Entl_Typ_4
683 ID_Einst_Entl_Typ_5
684 ID_Einst_Entl_Typ_6
685 ID_Einst_Entl_Typ_7
686 ID_Einst_Entl_Typ_8
687 ID_Einst_Entl_Typ_9
688 ID_Einst_Entl_Typ_10
689 ID_Einst_Entl_Typ_11
690 ID_Einst_Entl_Typ_12
691 ID_Einst_Vorl_max_MK1
692 ID_Einst_Vorl_max_MK2
693 ID_SU_FrkdMK1
694 ID_SU_FrkdMK2
695 ID_Ba_Hz_MK1_akt
696 ID_Ba_Hz_MK2_akt
697 ID_Einst_Zirk_Ein_akt
698 ID_Einst_Zirk_Aus_akt
699 ID_Einst_Heizgrenze
700 ID_Einst_Heizgrenze_Temp
701 ID_VariablenIBNgespeichert
702 ID_SchonIBNAssistant
703 ID_Heizgrenze_0
704 ID_Heizgrenze_1
705 ID_Heizgrenze_2
706 ID_Heizgrenze_3
707 ID_Heizgrenze_4
708 ID_Heizgrenze_5
709 ID_Heizgrenze_6
710 ID_Heizgrenze_7
711 ID_Heizgrenze_8
712 ID_Heizgrenze_9
713 ID_Heizgrenze_10
714 ID_Heizgrenze_11
715 ID_SchemenIBNgewahlt
716 ID_Switchoff_file_0_0
717 ID_Switchoff_file_1_0
718 ID_Switchoff_file_2_0
719 ID_Switchoff_file_3_0
720 ID_Switchoff_file_4_0
721 ID_Switchoff_file_0_1
722 ID_Switchoff_file_1_1
723 ID_Switchoff_file_2_1
724 ID_Switchoff_file_3_1
725 ID_Switchoff_file_4_1
726 ID_DauerDatenLoggerAktiv
727 ID_Laufvar_Heizgrenze
728 ID_Zaehler_BetrZeitHz
729 ID_Zaehler_BetrZeitBW
730 ID_Zaehler_BetrZeitKue
731 ID_SU_FstdHz
732 ID_SU_FstdBw
733 ID_SU_FstdSwb
734 ID_SU_FstdMK1
735 ID_SU_FstdMK2
736 ID_FerienAbsenkungHz
737 ID_FerienAbsenkungMK1
738 ID_FerienAbsenkungMK2
739 ID_FerienModusAktivHz
740 ID_FerienModusAktivBw
741 ID_FerienModusAktivSwb
742 ID_FerienModusAktivMk1
743 ID_FerienModusAktivMk2
744 ID_DisplayContrast_akt
745 ID_Ba_Hz_saved
746 ID_Ba_Bw_saved
747 ID_Ba_Sw_saved
748 ID_Ba_Hz_MK1_saved
749 ID_Ba_Hz_MK2_saved
750 ID_AdresseIP_akt
751 ID_SubNetMask_akt
752 ID_Add_Broadcast_akt
753 ID_Add_StdGateway_akt
754 ID_DHCPServerAktiv_akt
755 ID_WebserverPasswort_1_akt
756 ID_WebserverPasswort_2_akt
757 ID_WebserverPasswort_3_akt
758 ID_WebserverPasswort_4_akt
759 ID_WebserverPasswort_5_akt
760 ID_WebserverPasswort_6_akt
761 ID_WebServerWerteBekommen
762 ID_Einst_ParBetr_akt
763 ID_Einst_WpAnz_akt
764 ID_Einst_PhrTime_akt
765 ID_Einst_HysPar_akt
766 ID_IP_PB_Slave_0
767 ID_IP_PB_Slave_1
768 ID_IP_PB_Slave_2
769 ID_IP_PB_Slave_3
770 ID_IP_PB_Slave_4
771 ID_IP_PB_Slave_5
772 ID_Einst_BwHup_akt_backup
773 ID_Einst_SuMk3_akt
774 ID_Einst_HzMK3E_akt
775 ID_Einst_HzMK3ANH_akt
776 ID_Einst_HzMK3ABS_akt
777 ID_Einst_HzMK3Hgr_akt
778 ID_Einst_HzFtMK3Vl_akt
779 ID_Ba_Hz_MK3_akt
780 ID_Einst_MK3Typ_akt
781 ID_Einst_RTypMK3_akt
782 ID_Einst_MK3LzFaktor_akt
783 ID_Einst_MK3PerFaktor_akt
784 ID_FerienModusAktivMk3
785 ID_SU_FrkdMK3
786 ID_FerienAbsenkungMK3
787 ID_SU_FstdMK3
788 ID_Einst_SuMk3_akt2
789 ID_Einst_SuMk3Wo_zeit_0_0
790 ID_Einst_SuMk3Wo_zeit_0_1
791 ID_Einst_SuMk3Wo_zeit_1_0
792 ID_Einst_SuMk3Wo_zeit_1_1
793 ID_Einst_SuMk3Wo_zeit_2_0
794 ID_Einst_SuMk3Wo_zeit_2_1
795 ID_Einst_SuMk325_zeit_0_0
796 ID_Einst_SuMk325_zeit_0_1
797 ID_Einst_SuMk325_zeit_1_0
798 ID_Einst_SuMk325_zeit_1_1
799 ID_Einst_SuMk325_zeit_2_0
800 ID_Einst_SuMk325_zeit_2_1
801 ID_Einst_SuMk325_zeit_0_2
802 ID_Einst_SuMk325_zeit_0_3
803 ID_Einst_SuMk325_zeit_1_2
804 ID_Einst_SuMk325_zeit_1_3
805 ID_Einst_SuMk325_zeit_2_2
806 ID_Einst_SuMk325_zeit_2_3
807 ID_Einst_SuMk3Tg_zeit_0_0
808 ID_Einst_SuMk3Tg_zeit_0_1
809 ID_Einst_SuMk3Tg_zeit_1_0
810 ID_Einst_SuMk3Tg_zeit_1_1
811 ID_Einst_SuMk3Tg_zeit_2_0
812 ID_Einst_SuMk3Tg_zeit_2_1
813 ID_Einst_SuMk3Tg_zeit_0_2
814 ID_Einst_SuMk3Tg_zeit_0_3
815 ID_Einst_SuMk3Tg_zeit_1_2
816 ID_Einst_SuMk3Tg_zeit_1_3
817 ID_Einst_SuMk3Tg_zeit_2_2
818 ID_Einst_SuMk3Tg_zeit_2_3
819 ID_Einst_SuMk3Tg_zeit_0_4
820 ID_Einst_SuMk3Tg_zeit_0_5
821 ID_Einst_SuMk3Tg_zeit_1_4
822 ID_Einst_SuMk3Tg_zeit_1_5
823 ID_Einst_SuMk3Tg_zeit_2_4
824 ID_Einst_SuMk3Tg_zeit_2_5
825 ID_Einst_SuMk3Tg_zeit_0_6
826 ID_Einst_SuMk3Tg_zeit_0_7
827 ID_Einst_SuMk3Tg_zeit_1_6
828 ID_Einst_SuMk3Tg_zeit_1_7
829 ID_Einst_SuMk3Tg_zeit_2_6
830 ID_Einst_SuMk3Tg_zeit_2_7
831 ID_Einst_SuMk3Tg_zeit_0_8
832 ID_Einst_SuMk3Tg_zeit_0_9
833 ID_Einst_SuMk3Tg_zeit_1_8
834 ID_Einst_SuMk3Tg_zeit_1_9
835 ID_Einst_SuMk3Tg_zeit_2_8
836 ID_Einst_SuMk3Tg_zeit_2_9
837 ID_Einst_SuMk3Tg_zeit_0_10
838 ID_Einst_SuMk3Tg_zeit_0_11
839 ID_Einst_SuMk3Tg_zeit_1_10
840 ID_Einst_SuMk3Tg_zeit_1_11
841 ID_Einst_SuMk3Tg_zeit_2_10
842 ID_Einst_SuMk3Tg_zeit_2_11
843 ID_Einst_SuMk3Tg_zeit_0_12
844 ID_Einst_SuMk3Tg_zeit_0_13
845 ID_Einst_SuMk3Tg_zeit_1_12
846 ID_Einst_SuMk3Tg_zeit_1_13
847 ID_Einst_SuMk3Tg_zeit_2_12
848 ID_Einst_SuMk3Tg_zeit_2_13
849 ID_Ba_Hz_MK3_saved
850 ID_Einst_Kuhl_Zeit_Ein_akt
851 ID_Einst_Kuhl_Zeit_Aus_akt
852 ID_Waermemenge_ab
853 ID_Waermemenge_WQ
854 ID_Waermemenge_Hz
855 ID_Waermemenge_WQ_ges
856 ID_Einst_Entl_Typ_13
857 ID_Einst_Entl_Typ_14
858 ID_Einst_Entl_Typ_15
859 ID_Zaehler_BetrZeitSW
860 ID_Einst_Fernwartung_akt
861 ID_AdresseIPServ_akt
862 ID_Einst_TA_EG_akt
863 ID_Einst_TVLmax_EG_akt
864 ID_Einst_Popt_Nachlauf_akt
865 ID_FernwartungVertrag_akt
866 ID_FernwartungAktuZeit
867 ID_Einst_Effizienzpumpe_Nominal_akt
868 ID_Einst_Effizienzpumpe_Minimal_akt
869 ID_Einst_Effizienzpumpe_akt
870 ID_Einst_Waermemenge_akt
871 ID_Einst_Wm_Versorgung_Korrektur_akt
872 ID_Einst_Wm_Auswertung_Korrektur_akt
873 ID_SoftwareUpdateJetztGemacht_akt
874 ID_WP_SerienNummer_DATUM
875 ID_WP_SerienNummer_HEX
876 ID_WP_SerienNummer_INDEX
877 ID_ProgWerteWebSrvBeobarten
878 ID_Waermemenge_BW
879 ID_Waermemenge_SW
880 ID_Waermemenge_Datum
881 ID_Einst_Solar_akt
882 ID_BSTD_Solar
883 ID_Einst_TDC_Koll_Max_akt
884 ID_Einst_Akt_Kuehlung_akt
885 ID_Einst_Vorlauf_VBO_akt
886 ID_Einst_KRHyst_akt
887 ID_Einst_Akt_Kuehl_Speicher_min_akt
888 ID_Einst_Akt_Kuehl_Freig_WQE_akt
889 ID_NDAB_WW_Anzahl
890 ID_NDS_WW_KD_Quitt
891 ID_Einst_AbtZykMin_akt
892 ID_Einst_VD2_Zeit_Min_akt
893 ID_Einst_Hysterese_HR_verkuerzt_akt
894 ID_Einst_BA_Lueftung_akt
895 ID_Einst_SuLuf_akt
896 ID_Einst_SuLufWo_zeit_0_0_0
897 ID_Einst_SuLufWo_zeit_0_1_0
898 ID_Einst_SuLufWo_zeit_0_2_0
899 ID_Einst_SuLuf25_zeit_0_0_0
900 ID_Einst_SuLuf25_zeit_0_1_0
901 ID_Einst_SuLuf25_zeit_0_2_0
902 ID_Einst_SuLuf25_zeit_0_0_2
903 ID_Einst_SuLuf25_zeit_0_1_2
904 ID_Einst_SuLuf25_zeit_0_2_2
905 ID_Einst_SuLufTg_zeit_0_0_0
906 ID_Einst_SuLufTg_zeit_0_1_0
907 ID_Einst_SuLufTg_zeit_0_2_0
908 ID_Einst_SuLufTg_zeit_0_0_2
909 ID_Einst_SuLufTg_zeit_0_1_2
910 ID_Einst_SuLufTg_zeit_0_2_2
911 ID_Einst_SuLufTg_zeit_0_0_4
912 ID_Einst_SuLufTg_zeit_0_1_4
913 ID_Einst_SuLufTg_zeit_0_2_4
914 ID_Einst_SuLufTg_zeit_0_0_6
915 ID_Einst_SuLufTg_zeit_0_1_6
916 ID_Einst_SuLufTg_zeit_0_2_6
917 ID_Einst_SuLufTg_zeit_0_0_8
918 ID_Einst_SuLufTg_zeit_0_1_8
919 ID_Einst_SuLufTg_zeit_0_2_8
920 ID_Einst_SuLufTg_zeit_0_0_10
921 ID_Einst_SuLufTg_zeit_0_1_10
922 ID_Einst_SuLufTg_zeit_0_2_10
923 ID_Einst_SuLufTg_zeit_0_0_12
924 ID_Einst_SuLufTg_zeit_0_1_12
925 ID_Einst_SuLufTg_zeit_0_2_12
926 ID_Einst_SuLufWo_zeit_1_0_0
927 ID_Einst_SuLufWo_zeit_1_1_0
928 ID_Einst_SuLufWo_zeit_1_2_0
929 ID_Einst_SuLuf25_zeit_1_0_0
930 ID_Einst_SuLuf25_zeit_1_1_0
931 ID_Einst_SuLuf25_zeit_1_2_0
932 ID_Einst_SuLuf25_zeit_1_0_2
933 ID_Einst_SuLuf25_zeit_1_1_2
934 ID_Einst_SuLuf25_zeit_1_2_2
935 ID_Einst_SuLufTg_zeit_1_0_0
936 ID_Einst_SuLufTg_zeit_1_1_0
937 ID_Einst_SuLufTg_zeit_1_2_0
938 ID_Einst_SuLufTg_zeit_1_0_2
939 ID_Einst_SuLufTg_zeit_1_1_2
940 ID_Einst_SuLufTg_zeit_1_2_2
941 ID_Einst_SuLufTg_zeit_1_0_4
942 ID_Einst_SuLufTg_zeit_1_1_4
943 ID_Einst_SuLufTg_zeit_1_2_4
944 ID_Einst_SuLufTg_zeit_1_0_6
945 ID_Einst_SuLufTg_zeit_1_1_6
946 ID_Einst_SuLufTg_zeit_1_2_6
947 ID_Einst_SuLufTg_zeit_1_0_8
948 ID_Einst_SuLufTg_zeit_1_1_8
949 ID_Einst_SuLufTg_zeit_1_2_8
950 ID_Einst_SuLufTg_zeit_1_0_10
951 ID_Einst_SuLufTg_zeit_1_1_10
952 ID_Einst_SuLufTg_zeit_1_2_10
953 ID_Einst_SuLufTg_zeit_1_0_12
954 ID_Einst_SuLufTg_zeit_1_1_12
955 ID_Einst_SuLufTg_zeit_1_2_12
956 ID_FerienModusAktivLueftung
957 ID_Einst_BA_Lueftung_saved
958 ID_SU_FrkdLueftung
959 ID_SU_FstdLueftung
960 ID_Einst_Luf_Feuchteschutz_akt
961 ID_Einst_Luf_Reduziert_akt
962 ID_Einst_Luf_Nennlueftung_akt
963 ID_Einst_Luf_Intensivlueftung_akt
964 ID_Timer_Fil_4Makt
965 ID_Timer_Fil_WoAkt
966 ID_Sollwert_KuCft3_akt
967 ID_Sollwert_AtDif3_akt
968 ID_Bitmaske_0
969 ID_Einst_Lueftungsstufen
970 ID_SysEin_Meldung_TDI
971 ID_SysEin_Typ_WZW
972 ID_Einst_BACnet_aktiviert
973 ID_Einst_BW_max
974 ID_Einst_Sollwert_TRL_Kuehlen
975 ID_Einst_Medium_Waermequelle
976 ID_Einst_Photovoltaik_akt
977 ID_Einst_Multispeicher_akt
978 ID_Einst_PKuehlTime_akt
979 ID_Einst_Minimale_Ruecklaufsolltemperatur
980 ID_RBE_Einflussfaktor_RT_akt
981 ID_RBE_Freigabe_Kuehlung_akt
982 ID_RBE_Waermeverteilsystem_akt
983 ID_RBE_Zeit_Heizstab_aktiv
984 ID_SEC_ND_Alarmgrenze
985 ID_SEC_HD_Alarmgrenze
986 ID_SEC_Abtauendtemperatur
987 ID_Einst_Min_RPM_BW
988 ID_Einst_Luf_Feuchteschutz_Faktor_akt
989 ID_Einst_Luf_Reduziert_Faktor_akt
990 ID_Einst_Luf_Nennlueftung_Faktor_akt
991 ID_Einst_Luf_Intensivlueftung_Faktor_akt
992 ID_Einst_Freigabe_Zeit_ZWE
993 ID_Einst_min_VL_Kuehl
994 ID_Einst_Warmwasser_Nachheizung
995 ID_Switchoff_file_LWD2_0_0
996 ID_Switchoff_file_LWD2_1_0
997 ID_Switchoff_file_LWD2_2_0
998 ID_Switchoff_file_LWD2_3_0
999 ID_Switchoff_file_LWD2_4_0
1000 ID_Switchoff_file_LWD2_0_1
1001 ID_Switchoff_file_LWD2_1_1
1002 ID_Switchoff_file_LWD2_2_1
1003 ID_Switchoff_file_LWD2_3_1
1004 ID_Switchoff_file_LWD2_4_1
1005 ID_Switchoff_index_LWD2
1006 ID_Einst_Effizienzpumpe_Nominal_2
1007 ID_Einst_Effizienzpumpe_Minimal_2
1008 ID_Einst_Wm_Versorgung_Korrektur_2
1009 ID_Einst_Wm_Auswertung_Korrektur_2
1010 ID_Einst_isTwin
1011 ID_Einst_TAmin_2
1012 ID_Einst_TVLmax_2
1013 ID_Einst_TA_EG_2
1014 ID_Einst_TVLmax_EG_2
1015 ID_Waermemenge_Hz_2
1016 ID_Waermemenge_BW_2
1017 ID_Waermemenge_SW_2
1018 ID_Waermemenge_ab_2
1019 ID_Einst_Entl_Typ_15_2
1020 ID_Einst_WW_Nachheizung_max
1021 ID_Einst_Kuhl_Zeit_Ein_RT
1022 ID_Einst_ZWE1_Pos
1023 ID_Einst_ZWE2_Pos
1024 ID_Einst_ZWE3_Pos
1025 ID_Einst_Leistung_ZWE
1026 ID_WP_SN2_DATUM
1027 ID_WP_SN2_HEX
1028 ID_WP_SN2_INDEX
1029 ID_CWP_saved2
1030 ID_Einst_SmartGrid
1031 ID_Einst_P155_HDS
1032 ID_Einst_P155_PumpHeat_Max
1033 ID_Einst_P155_PumpHeatCtrl
1034 ID_Einst_P155_PumpDHWCtrl
1035 ID_Einst_P155_PumpDHW_RPM
1036 ID_Einst_P155_PumpPoolCtrl
1037 ID_Einst_P155_PumpPool_RPM
1038 ID_Einst_P155_PumpCool_RPM
1039 ID_Einst_P155_PumpVBOCtrl
1040 ID_Einst_P155_PumpVBO_RPM_C
1041 ID_Einst_P155_PumpDHW_Max
1042 ID_Einst_P155_PumpPool_Max
1043 ID_Einst_P155_Sperrband_1
1044 ID_Einst_P155_Leistungsfreigabe
1045 ID_Einst_P155_DHW_Freq
1046 ID_Einst_SWHUP
1047 ID_Einst_P155_SWB_Freq
1048 ID_Einst_MK1_Regelung
1049 ID_Einst_MK2_Regelung
1050 ID_Einst_MK3_Regelung
1051 ID_Einst_PV_WW_Sperrzeit
1052 ID_Einst_Warmwasser_extra
1053 ID_Einst_Vorl_akt_Kuehl
1054 ID_WP_SN3_DATUM
1055 ID_WP_SN3_HEX
1056 ID_WP_SN3_INDEX
1057 ID_Einst_Vorlauf_ZUP
1058 ID_Einst_Abtauen_im_Warmwasser
1059 ID_Waermemenge_ZWE
1060 ID_Waermemenge_Reset
1061 ID_Waermemenge_Reset_2

3004

Number Internal ID Internal Text category conversion unit type notes translation
10 ID_WEB_Temperatur_TVL Text_Vorlauf temperature 10 °C Vorlauf
11 ID_WEB_Temperatur_TRL Text_Rucklauf temperature 10 °C Rücklauf
12 ID_WEB_Sollwert_TRL_HZ Text_RL_Soll temperature 10 °C Rückl.-Soll
13 ID_WEB_Temperatur_TRL_ext Text_Ruecklext temperature 10 °C Rückl.-Extern
14 ID_WEB_Temperatur_THG Text_Heissgas temperature 10 °C Heissgas
15 ID_WEB_Temperatur_TA Text_Aussent temperature 10 °C Aussentemperatur
16 ID_WEB_Mitteltemperatur Text_Mitteltemperatur temperature 10 °C Mitteltemperatur
17 ID_WEB_Temperatur_TBW Text_BW_Ist temperature 10 °C Warmwasser-Ist
18 ID_WEB_Einst_BWS_akt Text_BW_Soll temperature 10 °C Warmwasser-Soll
19 ID_WEB_Temperatur_TWE Text_WQ_Ein temperature 10 °C Wärmequelle-Ein
20 ID_WEB_Temperatur_TWA Text_Kaltekreis temperature 10 °C Wärmequelle-Aus
21 ID_WEB_Temperatur_TFB1 Text_MK1_Vorlauf temperature 10 °C Mischkreis1-Vorlauf
22 ID_WEB_Sollwert_TVL_MK1 Text_MK1VL_Soll temperature 10 °C Mischkreis1 VL-Soll
23 ID_WEB_Temperatur_RFV Text_Raumstation temperature 10 °C Raumstation
24 ID_WEB_Temperatur_TFB2 Text_MK2_Vorlauf temperature 10 °C Mischkreis2-Vorlauf
25 ID_WEB_Sollwert_TVL_MK2 Text_MK2VL_Soll temperature 10 °C Mischkreis2 VL-Soll
26 ID_WEB_Temperatur_TSK Text_Solarkoll temperature 10 °C Solarkollektor
27 ID_WEB_Temperatur_TSS Text_Solarsp temperature 10 °C Solarspeicher
28 ID_WEB_Temperatur_TEE Text_Ext_Energ temperature 10 °C Externe Energ.Quelle
29 ID_WEB_ASDin Text_ASD input ASD
30 ID_WEB_BWTin Text_BWT input BWT
31 ID_WEB_EVUin Text_EVU input EVU
32 ID_WEB_HDin Text_HD input HD
33 ID_WEB_MOTin Text_MOT input MOT
34 ID_WEB_NDin Text_ND input ND
35 ID_WEB_PEXin Text_PEX input PEX
36 ID_WEB_SWTin Text_SWT input SWT
37 ID_WEB_AVout Text_Abtauventil output AV-Abtauventil
38 ID_WEB_BUPout Text_BUP output BUP
39 ID_WEB_HUPout Text_HUP output HUP
40 ID_WEB_MA1out Text_Mischer1Auf output Mischer 1 Auf
41 ID_WEB_MZ1out Text_Mischer1Zu output Mischer 1 Zu
42 ID_WEB_VENout Text_Ventilation output Ventilation
43 ID_WEB_VBOout Text_Ventil_BOSUP output Ventil.-BOSUP
44 ID_WEB_VD1out Text_Verdichter1 output Verdichter 1
45 ID_WEB_VD2out Text_Verdichter2 output Verdichter 2
46 ID_WEB_ZIPout Text_ZIP_AUSGANG output ZIP
47 ID_WEB_ZUPout Text_ZUP output ZUP
48 ID_WEB_ZW1out Text_ZWE1 output ZWE 1
49 ID_WEB_ZW2SSTout Text_ZWE2_SST output ZWE 2 - SST
50 ID_WEB_ZW3SSTout Text_ZWE3 output ZWE 3
51 ID_WEB_FP2out Text_FUP2 output FUP 2
52 ID_WEB_SLPout Text_SLP output SLP
53 ID_WEB_SUPout Text_SUP output SUP
54 ID_WEB_MZ2out Text_Mischer2Zu output Mischer 2 Zu
55 ID_WEB_MA2out Text_Mischer2Auf output Mischer 2 Auf
56 ID_WEB_Zaehler_BetrZeitVD1 Text_BStdVD1 operating_hours 3600 h Betriebstund. VD1
57 ID_WEB_Zaehler_BetrZeitImpVD1 Text_ImpVD1 operating_hours 5 Impulse Verdichter 1
58 ID_WEB_Zaehler_BetrZeitVD2 Text_BStdVD2 operating_hours 3600 h Betriebstund. VD2
59 ID_WEB_Zaehler_BetrZeitImpVD2 Text_ImpVD2 operating_hours 5 ImpulseVerdichter 2
60 ID_WEB_Zaehler_BetrZeitZWE1 Text_BStdZWE1 operating_hours 3600 h Betriebstunden ZWE1
61 ID_WEB_Zaehler_BetrZeitZWE2 Text_BStdZWE2 operating_hours 3600 h Betriebstunden ZWE2
62 ID_WEB_Zaehler_BetrZeitZWE3 Text_BStdZWE3 operating_hours 7200 h Betriebstunden ZWE3
63 ID_WEB_Zaehler_BetrZeitWP Text_BStdWP operating_hours 3600 h Betriebstunden WP
64 ID_WEB_Zaehler_BetrZeitHz Text_BStdHz operating_hours 3600 h Betriebstunden Heiz.
65 ID_WEB_Zaehler_BetrZeitBW Text_BStdBW operating_hours 3600 h Betriebstunden WW
66 ID_WEB_Zaehler_BetrZeitKue Text_BStdKue operating_hours 3600 h Betriebstunden Kuehl
67 ID_WEB_Time_WPein_akt Text_WP_Seit error_memory 4 WP Seit
68 ID_WEB_Time_ZWE1_akt Text_ZWE1_seit error_memory 4 ZWE1 seit
69 ID_WEB_Time_ZWE2_akt Text_ZWE2_seit error_memory 4 ZWE2 seit
70 ID_WEB_Timer_EinschVerz Text_Netzeinv error_memory 4 Netzeinschaltv.
71 ID_WEB_Time_SSPAUS_akt Text_SSP_Zeit1 error_memory 4 SSP-Zeit
72 ID_WEB_Time_SSPEIN_akt Text_SSP_Zeit1 error_memory 4 SSP-Zeit
73 ID_WEB_Time_VDStd_akt Text_VD_Stand error_memory 4 VD-Stand
74 ID_WEB_Time_HRM_akt Text_HRM_Zeit error_memory 4 HRM-Zeit
75 ID_WEB_Time_HRW_akt Text_HRW_Zeit error_memory 4 HRW-Zeit
76 ID_WEB_Time_LGS_akt Text_TDI_seit error_memory 4 TDI seit
77 ID_WEB_Time_SBW_akt Text_Sperre_BW error_memory 4 Sperre WW
78 ID_WEB_Code_WP_akt Text_WP_Typ status 3 Wärmepumpen Typ
79 ID_WEB_BIV_Stufe_akt Text_Biv_Sufe status 5 Bivalenz Stufe
80 ID_WEB_WP_BZ_akt Text_Betr_Zust status 7 Betriebszustand
81 ID_WEB_SoftStand1 Text_SW_Stand status 6 Softwarestand
91 ID_WEB_AdresseIP_akt Text_IP_Adresse status 1 IP-Adresse
92 ID_WEB_SubNetMask_akt Text_SubNetzMask status 1 Subntzmsk.
93 ID_WEB_Add_Broadcast Text_Broadcast status 1 Broadcast
94 ID_WEB_Add_StdGateway Text_Gateway status 1 Gateway
116 ID_WEB_Comfort_exists Text_Sim_Confort_Platine status Comfort Platine
136 ID_WEB_Sollwert_TVL_MK3 Text_MK3VL_Soll temperature 10 °C Mischkreis3 VL-Soll
137 ID_WEB_Temperatur_TFB3 Text_MK3_Vorlauf temperature 10 °C Mischkreis3-Vorlauf
138 ID_WEB_MZ3out Text_Mischer3Zu output Mischer 3 Zu
139 ID_WEB_MA3out Text_Mischer3Auf output Mischer 3 Auf
140 ID_WEB_FP3out Text_FUP3 output FUP 3
141 ID_WEB_Time_AbtIn Text_Abtauen error_memory 4 Abtauen
142 ID_WEB_Temperatur_RFV2 Text_Raumstation2 temperature 10 °C Raumstation MK2
143 ID_WEB_Temperatur_RFV3 Text_Raumstation3 temperature 10 °C Raumstation MK3
145 ID_WEB_Zaehler_BetrZeitSW Text_BStdSW operating_hours 7200 h Betriebstunden SW
146 ID_WEB_FreigabKuehl Text_FreigabKuehl input Freigabe Kühlung
147 ID_WEB_AnalogIn Text_AnalogIn input 100 V AIn
156 ID_WEB_AnalogOut1 Text_AnalogOut1 output 100 V AO1
157 ID_WEB_AnalogOut2 Text_AnalogOut2 output 100 V AO2
158 ID_WEB_Time_Heissgas Text_Sperre_2VD_HG error_memory 4 Sperre 2.VD HG
159 ID_WEB_Temp_Lueftung_Zuluft Text_Luft_Zulufttemp temperature 10 °C Zulufttemperatur
160 ID_WEB_Temp_Lueftung_Abluft Text_Luft_Ablufttemp temperature 10 °C Ablufttemperatur
161 ID_WEB_Zaehler_BetrZeitSolar Text_BSTD_Solar operating_hours 3600 h Betriebstunden Solar
162 ID_WEB_AnalogOut3 Text_AnalogOut3 output 100 V AO3
163 ID_WEB_AnalogOut4 Text_AnalogOut4 output 100 V AO4
164 ID_WEB_Out_VZU Text_Out_VZU output 100 V Vent. Zuluft
165 ID_WEB_Out_VAB Text_Out_VAB output 100 V Vent. Abluft
166 ID_WEB_Out_VSK Text_Out_VSK output VSK
167 ID_WEB_Out_FRH Text_Out_FRH output FRH
168 ID_WEB_AnalogIn2 Text_AnalogIn2 input 100 V AIn2
169 ID_WEB_AnalogIn3 Text_AnalogIn3 input 100 V AIn3
170 ID_WEB_SAXin Text_SAX input SAX
171 ID_WEB_SPLin Text_SPL input SPL
172 ID_WEB_Compact_exists Text_Sim_Compact_Platine status Lüftungsplatine
173 ID_WEB_Durchfluss_WQ Text_DurchflussWQ input 1 l/h Durchfluss WQ
175 ID_WEB_LIN_ANSAUG_VERDAMPFER Text_Verdampfungstemp temperature 10 °C Verd.temp. EEV
176 ID_WEB_LIN_ANSAUG_VERDICHTER Text_Ansaug_Verdichter temperature 10 °C Ansaug VD
177 ID_WEB_LIN_VDH Text_VD_Heizung temperature 10 °C VD-Heizung
178 ID_WEB_LIN_UH Text_Ueberhitzung temperature 10 K Überhitzung
179 ID_WEB_LIN_UH_Soll Text_Ueberhitzung_Soll temperature 10 K Überhitzung Soll
180 ID_WEB_LIN_HD Text_HD input 100 bar HD
181 ID_WEB_LIN_ND Text_ND input 100 bar ND
182 ID_WEB_LIN_VDH_out Text_VD_Heizung output VD-Heizung
183 ID_WEB_HZIO_PWM Text_PWM_UWP output 10 % Steuersignal UWP
184 ID_WEB_HZIO_VEN Text_Ven_RPM output 1 RPM Ventilatordrehzahl
185 ID_WEB_HZIO_EVU2 Text_EVU2 input EVU 2
186 ID_WEB_HZIO_STB Text_STB input STB FBH
187 ID_WEB_SEC_Qh_Soll Text_Kap_Soll status 100 kW Leistung Soll
188 ID_WEB_SEC_Qh_Ist Text_Kapazitat status 100 kW Leistung Ist
189 ID_WEB_SEC_TVL_Soll Text_VL_Soll temperature 10 °C Vorlauf Soll
190 ID_WEB_SEC_Software Text_SW_Stand status Softwarestand
191 ID_WEB_SEC_BZ Text_Betr_Zust status 7 Betriebszustand
192 ID_WEB_SEC_VWV Text_FourWayValve output 4-Wege-Ventil
193 ID_WEB_SEC_VD Text_VD_RPM output 1 RPM Verdichterdrehzahl
194 ID_WEB_SEC_VerdEVI Text_EvapTemp_EVI temperature 10 °C Verd.temp. EVI
195 ID_WEB_SEC_AnsEVI Text_Ansaug_EVi temperature 10 °C Ansaug EVi
196 ID_WEB_SEC_UEH_EVI Text_UEH_EVI temperature 10 K Überhitzung EVi
197 ID_WEB_SEC_UEH_EVI_S Text_UEH_EVI_Soll temperature 10 K Überhitzung EVi Soll
198 ID_WEB_SEC_KondTemp Text_Kondtemp temperature 10 °C Kondensationstemp.
199 ID_WEB_SEC_FlussigEx Text_FlussigEx temperature 10 °C Flüssig vor EEV
200 ID_WEB_SEC_UK_EEV Text_UK_Hauptventil temperature 10 °C Unterkühlung EEV
201 ID_WEB_SEC_EVI_Druck Text_EVI_Druck input 100 bar Druck EVI
202 ID_WEB_SEC_U_Inv Text_U_Inverter input 10 V Spannung Inverter
227 ID_WEB_RBE_RT_Ist RBE_RT_Ist temperature 10 °C Raumtemperatur Ist
228 ID_WEB_RBE_RT_Soll RBE_RT_Soll temperature 10 °C Raumtemperatur Soll
229 ID_WEB_Temperatur_BW_oben Text_BW_oben temperature 10 °C Warmwasser oben
231 ID_WEB_Freq_VD Text_Freq_VD status 1 Hz Verdichterfrequenz

3005

Number Internal ID
0 ID_Visi_NieAnzeigen
1 ID_Visi_ImmerAnzeigen
2 ID_Visi_Heizung
3 ID_Visi_Brauwasser
4 ID_Visi_Schwimmbad
5 ID_Visi_Kuhlung
6 ID_Visi_Lueftung
7 ID_Visi_MK1
8 ID_Visi_MK2
9 ID_Visi_ThermDesinfekt
10 ID_Visi_Zirkulation
11 ID_Visi_KuhlTemp_SolltempMK1
12 ID_Visi_KuhlTemp_SolltempMK2
13 ID_Visi_KuhlTemp_ATDiffMK1
14 ID_Visi_KuhlTemp_ATDiffMK2
15 ID_Visi_Service_Information
16 ID_Visi_Service_Einstellung
17 ID_Visi_Service_Sprache
18 ID_Visi_Service_DatumUhrzeit
19 ID_Visi_Service_Ausheiz
20 ID_Visi_Service_Anlagenkonfiguration
21 ID_Visi_Service_IBNAssistant
22 ID_Visi_Service_ParameterIBNZuruck
23 ID_Visi_Temp_Vorlauf
24 ID_Visi_Temp_Rucklauf
25 ID_Visi_Temp_RL_Soll
26 ID_Visi_Temp_Ruecklext
27 ID_Visi_Temp_Heissgas
28 ID_Visi_Temp_Aussent
29 ID_Visi_Temp_BW_Ist
30 ID_Visi_Temp_BW_Soll
31 ID_Visi_Temp_WQ_Ein
32 ID_Visi_Temp_Kaltekreis
33 ID_Visi_Temp_MK1_Vorlauf
34 ID_Visi_Temp_MK1VL_Soll
35 ID_Visi_Temp_Raumstation
36 ID_Visi_Temp_MK2_Vorlauf
37 ID_Visi_Temp_MK2VL_Soll
38 ID_Visi_Temp_Solarkoll
39 ID_Visi_Temp_Solarsp
40 ID_Visi_Temp_Ext_Energ
41 ID_Visi_IN_ASD
42 ID_Visi_IN_BWT
43 ID_Visi_IN_EVU
44 ID_Visi_IN_HD
45 ID_Visi_IN_MOT
46 ID_Visi_IN_ND
47 ID_Visi_IN_PEX
48 ID_Visi_IN_SWT
49 ID_Visi_OUT_Abtauventil
50 ID_Visi_OUT_BUP
51 ID_Visi_OUT_FUP1
52 ID_Visi_OUT_HUP
53 ID_Visi_OUT_Mischer1Auf
54 ID_Visi_OUT_Mischer1Zu
55 ID_Visi_OUT_Ventilation
56 ID_Visi_OUT_Ventil_BOSUP
57 ID_Visi_OUT_Verdichter1
58 ID_Visi_OUT_Verdichter2
59 ID_Visi_OUT_ZIP
60 ID_Visi_OUT_ZUP
61 ID_Visi_OUT_ZWE1
62 ID_Visi_OUT_ZWE2_SST
63 ID_Visi_OUT_ZWE3
64 ID_Visi_OUT_FUP2
65 ID_Visi_OUT_SLP
66 ID_Visi_OUT_SUP
67 ID_Visi_OUT_Mischer2Auf
68 ID_Visi_OUT_Mischer2Zu
69 ID_Visi_AblaufZ_WP_Seit
70 ID_Visi_AblaufZ_ZWE1_seit
71 ID_Visi_AblaufZ_ZWE2_seit
72 ID_Visi_AblaufZ_ZWE3_seit
73 ID_Visi_AblaufZ_Netzeinv
74 ID_Visi_AblaufZ_SSP_Zeit1
75 ID_Visi_AblaufZ_VD_Stand
76 ID_Visi_AblaufZ_HRM_Zeit
77 ID_Visi_AblaufZ_HRW_Zeit
78 ID_Visi_AblaufZ_TDI_seit
79 ID_Visi_AblaufZ_Sperre_BW
80 ID_Visi_Bst_BStdVD1
81 ID_Visi_Bst_ImpVD1
82 ID_Visi_Bst_dEZVD1
83 ID_Visi_Bst_BStdVD2
84 ID_Visi_Bst_ImpVD2
85 ID_Visi_Bst_dEZVD2
86 ID_Visi_Bst_BStdZWE1
87 ID_Visi_Bst_BStdZWE2
88 ID_Visi_Bst_BStdZWE3
89 ID_Visi_Bst_BStdWP
90 ID_Visi_Text_Kurzprogramme
91 ID_Visi_Text_Zwangsheizung
92 ID_Visi_Text_Zwangsbrauchwasser
93 ID_Visi_Text_Abtauen
94 ID_Visi_EinstTemp_RucklBegr
95 ID_Visi_EinstTemp_HystereseHR
96 ID_Visi_EinstTemp_TRErhmax
97 ID_Visi_EinstTemp_Freig2VD
98 ID_Visi_EinstTemp_FreigZWE
99 ID_Visi_EinstTemp_Tluftabt
100 ID_Visi_EinstTemp_TDISolltemp
101 ID_Visi_EinstTemp_HystereseBW
102 ID_Visi_EinstTemp_Vorl2VDBW
103 ID_Visi_EinstTemp_TAussenmax
104 ID_Visi_EinstTemp_TAussenmin
105 ID_Visi_EinstTemp_TWQmin
106 ID_Visi_EinstTemp_THGmax
107 ID_Visi_EinstTemp_TLABTEnde
108 ID_Visi_EinstTemp_Absenkbis
109 ID_Visi_EinstTemp_Vorlaufmax
110 ID_Visi_EinstTemp_TDiffEin
111 ID_Visi_EinstTemp_TDiffAus
112 ID_Visi_EinstTemp_TDiffmax
113 ID_Visi_EinstTemp_TEEHeizung
114 ID_Visi_EinstTemp_TEEBrauchw
115 ID_Visi_EinstTemp_Vorl2VDSW
116 ID_Visi_EinstTemp_VLMaxMk1
117 ID_Visi_EinstTemp_VLMaxMk2
118 ID_Visi_Priori_Brauchwasser
119 ID_Visi_Priori_Heizung
120 ID_Visi_Priori_Schwimmbad
121 ID_Visi_SysEin_EVUSperre
122 ID_Visi_SysEin_Raumstation
123 ID_Visi_SysEin_Einbindung
124 ID_Visi_SysEin_Mischkreis1
125 ID_Visi_SysEin_Mischkreis2
126 ID_Visi_SysEin_ZWE1Art
127 ID_Visi_SysEin_ZWE1Fkt
128 ID_Visi_SysEin_ZWE2Art
129 ID_Visi_SysEin_ZWE2Fkt
130 ID_Visi_SysEin_ZWE3Art
131 ID_Visi_SysEin_ZWE3Fkt
132 ID_Visi_SysEin_Stoerung
133 ID_Visi_SysEin_Brauchwasser1
134 ID_Visi_SysEin_Brauchwasser2
135 ID_Visi_SysEin_Brauchwasser3
136 ID_Visi_SysEin_Brauchwasser4
137 ID_Visi_SysEin_Brauchwasser5
138 ID_Visi_SysEin_BWWPmax
139 ID_Visi_SysEin_Abtzykmax
140 ID_Visi_SysEin_Luftabt
141 ID_Visi_SysEin_LuftAbtmax
142 ID_Visi_SysEin_Abtauen1
143 ID_Visi_SysEin_Abtauen2
144 ID_Visi_SysEin_Pumpenoptim
145 ID_Visi_SysEin_Zusatzpumpe
146 ID_Visi_SysEin_Zugang
147 ID_Visi_SysEin_SoledrDurchf
148 ID_Visi_SysEin_UberwachungVD
149 ID_Visi_SysEin_RegelungHK
150 ID_Visi_SysEin_RegelungMK1
151 ID_Visi_SysEin_RegelungMK2
152 ID_Visi_SysEin_Kuhlung
153 ID_Visi_SysEin_Ausheizen
154 ID_Visi_SysEin_ElektrAnode
155 ID_Visi_SysEin_SWBBer
156 ID_Visi_SysEin_SWBMin
157 ID_Visi_SysEin_Heizung
158 ID_Visi_SysEin_PeriodeMk1
159 ID_Visi_SysEin_LaufzeitMk1
160 ID_Visi_SysEin_PeriodeMk2
161 ID_Visi_SysEin_LaufzeitMk2
162 ID_Visi_SysEin_Heizgrenze
163 ID_Visi_Enlt_HUP
164 ID_Visi_Enlt_ZUP
165 ID_Visi_Enlt_BUP
166 ID_Visi_Enlt_Ventilator_BOSUP
167 ID_Visi_Enlt_MA1
168 ID_Visi_Enlt_MZ1
169 ID_Visi_Enlt_ZIP
170 ID_Visi_Enlt_MA2
171 ID_Visi_Enlt_MZ2
172 ID_Visi_Enlt_SUP
173 ID_Visi_Enlt_SLP
174 ID_Visi_Enlt_FP2
175 ID_Visi_Enlt_Laufzeit
176 ID_Visi_Anlgkonf_Heizung
177 ID_Visi_Anlgkonf_Brauchwarmwasser
178 ID_Visi_Anlgkonf_Schwimmbad
179 ID_Visi_Heizung_Betriebsart
180 ID_Visi_Heizung_TemperaturPlusMinus
181 ID_Visi_Heizung_Heizkurven
182 ID_Visi_Heizung_Zeitschlaltprogramm
183 ID_Visi_Heizung_Heizgrenze
184 ID_Visi_Mitteltemperatur
185 ID_Visi_Dataenlogger
186 ID_Visi_Sprachen_DEUTSCH
187 ID_Visi_Sprachen_ENGLISH
188 ID_Visi_Sprachen_FRANCAIS
189 ID_Visi_Sprachen_NORWAY
190 ID_Visi_Sprachen_TCHECH
191 ID_Visi_Sprachen_ITALIANO
192 ID_Visi_Sprachen_NEDERLANDS
193 ID_Visi_Sprachen_SVENSKA
194 ID_Visi_Sprachen_POLSKI
195 ID_Visi_Sprachen_MAGYARUL
196 ID_Visi_ErrorUSBspeichern
197 ID_Visi_Bst_BStdHz
198 ID_Visi_Bst_BStdBW
199 ID_Visi_Bst_BStdKue
200 ID_Visi_Service_Systemsteuerung
201 ID_Visi_Service_Systemsteuerung_Contrast
202 ID_Visi_Service_Systemsteuerung_Webserver
203 ID_Visi_Service_Systemsteuerung_IPAdresse
204 ID_Visi_Service_Systemsteuerung_Fernwartung
205 ID_Visi_Paralleleschaltung
206 ID_Visi_SysEin_Paralleleschaltung
207 ID_Visi_Sprachen_DANSK
208 ID_Visi_Sprachen_PORTUGES
209 ID_Visi_Heizkurve_Heizung
210 ID_Visi_SysEin_Mischkreis3
211 ID_Visi_MK3
212 ID_Visi_Temp_MK3_Vorlauf
213 ID_Visi_Temp_MK3VL_Soll
214 ID_Visi_OUT_Mischer3Auf
215 ID_Visi_OUT_Mischer3Zu
216 ID_Visi_SysEin_RegelungMK3
217 ID_Visi_SysEin_PeriodeMk3
218 ID_Visi_SysEin_LaufzeitMk3
219 ID_Visi_SysEin_Kuhl_Zeit_Ein
220 ID_Visi_SysEin_Kuhl_Zeit_Aus
221 ID_Visi_AblaufZ_AbtauIn
222 ID_Visi_Waermemenge_WS
223 ID_Visi_Waermemenge_WQ
224 ID_Visi_Enlt_MA3
225 ID_Visi_Enlt_MZ3
226 ID_Visi_Enlt_FP3
227 ID_Visi_OUT_FUP3
228 ID_Visi_Temp_Raumstation2
229 ID_Visi_Temp_Raumstation3
230 ID_Visi_Bst_BStdSW
231 ID_Visi_Sprachen_LITAUISCH
232 ID_Visi_Sprachen_ESTNICH
233 ID_Visi_SysEin_Fernwartung
234 ID_Visi_Sprachen_SLOVENISCH
235 ID_Visi_EinstTemp_TA_EG
236 ID_Visi_Einst_TVLmax_EG
237 ID_Visi_SysEin_PoptNachlauf
238 ID_Visi_RFV_K_Kuehlin
239 ID_Visi_SysEin_EffizienzpumpeNom
240 ID_Visi_SysEin_EffizienzpumpeMin
241 ID_Visi_SysEin_Effizienzpumpe
242 ID_Visi_SysEin_Waermemenge
243 ID_Visi_Service_WMZ_Effizienz
244 ID_Visi_SysEin_Wm_Versorgung_Korrektur
245 ID_Visi_SysEin_Wm_Auswertung_Korrektur
246 ID_Visi_IN_AnalogIn
247 ID_Visi_Eins_SN_Eingabe
248 ID_Visi_OUT_Analog_1
249 ID_Visi_OUT_Analog_2
250 ID_Visi_Solar
251 ID_Visi_SysEin_Solar
252 ID_Visi_EinstTemp_TDiffKollmax
253 ID_Visi_AblaufZ_HG_Sperre
254 ID_Visi_SysEin_Akt_Kuehlung
255 ID_Visi_SysEin_Vorlauf_VBO
256 ID_Visi_Einst_KRHyst
257 ID_Visi_Einst_Akt_Kuehl_Speicher_min
258 ID_Visi_Einst_Akt_Kuehl_Freig_WQE
259 ID_Visi_SysEin_AbtZykMin
260 ID_Visi_SysEin_VD2_Zeit_Min
261 ID_Visi_EinstTemp_Hysterese_HR_verkuerzt
262 ID_Visi_Einst_Luf_Feuchteschutz_akt
263 ID_Visi_Einst_Luf_Reduziert_akt
264 ID_Visi_Einst_Luf_Nennlueftung_akt
265 ID_Visi_Einst_Luf_Intensivlueftung_akt
266 ID_Visi_Temperatur_Lueftung_Zuluft
267 ID_Visi_Temperatur_Lueftung_Abluft
268 ID_Visi_OUT_Analog_3
269 ID_Visi_OUT_Analog_4
270 ID_Visi_IN_Analog_2
271 ID_Visi_IN_Analog_3
272 ID_Visi_IN_SAX
273 ID_Visi_OUT_VZU
274 ID_Visi_OUT_VAB
275 ID_Visi_OUT_VSK
276 ID_Visi_OUT_FRH
277 ID_Visi_KuhlTemp_SolltempMK3
278 ID_Visi_KuhlTemp_ATDiffMK3
279 ID_Visi_IN_SPL
280 ID_Visi_SysEin_Lueftungsstufen
281 ID_Visi_SysEin_Meldung_TDI
282 ID_Visi_SysEin_Typ_WZW
283 ID_Visi_BACnet
284 ID_Visi_Sprachen_SLOWAKISCH
285 ID_Visi_Sprachen_LETTISCH
286 ID_Visi_Sprachen_FINNISCH
287 ID_Visi_Kalibrierung_LWD
288 ID_Visi_IN_Durchfluss
289 ID_Visi_LIN_ANSAUG_VERDICHTER
290 ID_Visi_LIN_VDH
291 ID_Visi_LIN_UH
292 ID_Visi_LIN_Druck
293 ID_Visi_Einst_Sollwert_TRL_Kuehlen
294 ID_Visi_Entl_ExVentil
295 ID_Visi_Einst_Medium_Waermequelle
296 ID_Visi_Einst_Multispeicher
297 ID_Visi_Einst_Minimale_Ruecklaufsolltemperatur
298 ID_Visi_Einst_PKuehlTime
299 ID_Visi_Sprachen_TUERKISCH
300 ID_Visi_RBE
301 ID_Visi_Einst_Luf_Stufen_Faktor
302 ID_Visi_Freigabe_Zeit_ZWE
303 ID_Visi_Einst_min_VL_Kuehl
304 ID_Visi_ZWE1
305 ID_Visi_ZWE2
306 ID_Visi_ZWE3
307 ID_Visi_SEC
308 ID_Visi_HZIO
309 ID_Visi_WPIO
310 ID_Visi_LIN_ANSAUG_VERDAMPFER
311 ID_Visi_LIN_MULTI1
312 ID_Visi_LIN_MULTI2
313 ID_Visi_Einst_Leistung_ZWE
314 ID_Visi_Sprachen_ESPANOL
315 ID_Visi_Temp_BW_oben
316 ID_Visi_MAXIO
317 ID_Visi_OUT_Abtauwunsch
318 ID_Visi_SmartGrid
319 ID_Visi_Drehzahlgeregelt
320 ID_Visi_P155_Inverter
321 ID_Visi_Leistungsfreigabe
322 ID_Visi_Einst_Vorl_akt_Kuehl
323 ID_Visi_Einst_Abtauen_im_Warmwasser
324 ID_Visi_Waermemenge_ZWE
325 NB_Param_Visibility