If we want to do Coincident plant sizing for both chilled water loop and condenser water loop, we should choose Coincident for chilled water loop and NonCoincident for condenser water loop. This setting provides Coincident sizing results of cooling towers and condener water pumps.
If we choose "Coincident" for the condenser water loop in Sizing:Plant, the autosized condenser loop (Cooling towers and condenser water pumps) by Coincident sizing is much larger than that by NonCoincident sizing.
Please refer to the Unmethours link below for mroe details on the issue.
Details
Some additional details for this issue (if relevant):
Version of EnergyPlus: My model is V9-6-0, but the latest version should have the same bug.
Issue overview
If we want to do Coincident plant sizing for both chilled water loop and condenser water loop, we should choose Coincident for chilled water loop and NonCoincident for condenser water loop. This setting provides Coincident sizing results of cooling towers and condener water pumps.
If we choose "Coincident" for the condenser water loop in Sizing:Plant, the autosized condenser loop (Cooling towers and condenser water pumps) by Coincident sizing is much larger than that by NonCoincident sizing.
Please refer to the Unmethours link below for mroe details on the issue.
Details
Some additional details for this issue (if relevant):
Checklist
Add to this list or remove from it as applicable. This is a simple templated set of guidelines.
The text was updated successfully, but these errors were encountered: