AirLoopHVAC:DedicatedOutdoorAirSystem does not work with draw through fan placement #9994
Comments
possibly related to #9066 |
Oh, true. For V22-2-0, no severe/fatal errors appear, but the fan supply air flow and the fan power are 0. |
@keigo-nomura I tested the bug input file and confirmed zero outputs for fan flow rate and energy. Then I found that when you switched fan placement order from blow through to draw through, you need to change node order also. For example, the inlet node of heating coil should be outdoor air inlet, and the outlet node of fan should be the inlet node of AirLoopHVAC:Splitter. AirLoopHVAC:DedicatedOutdoorAirSystem, When I made node order changes, the outputs are back to normal. Unfortunately, the err file does not provide node connection error. I am going to add warning messages for connection error. |
@lgu1234 Thank you for investigating. However, I sitll don't know which Node input was wrong in the idf file SmallOffice_CentralDOAS_DrawThrough.idf. The following Node order looks correct to me. The inlet node of heating coil is already outdoor air inlet, and the outlet node of fan is already the inlet node of AirLoopHVAC:Splitter. Could you please point out exactly which input was wrong? AirLoopHVAC:OutdoorAirSystem:EquipmentList, OutdoorAir:NodeList, NodeList, Coil:Heating:Water, Coil:Cooling:Water, Fan:SystemModel, AirLoopHVAC:Splitter, |
SetpointManager:Scheduled, You may also need to change the node name in SetpointManager:Scheduled, |
@lgu1234 I should change the node name in SetpointManager:Scheduled and add SetpointManager:MixedAir if I want to consider the supply fan air temperature rise, but I don't think that's the cause of this issue. |
@keigo-nomura If you want, I can upload the file with correct node connection. |
@lgu1234 Yes, please. Sorry to bother you, but I would like to compare the difference between your file and my file. |
@keigo-nomura Here is the file |
@lgu1234 The Node connection of your file is the same as the Node connection of my file SmallOffice_CentralDOAS_DrawThrough.idf I'm sorry, but I don't know what you have changed. Besides, the OA Supply Fan in your file does not work as well. The issue has not been solved. |
@keigo-nomura I am going to take a look. |
@keigo-nomura You are right. The mass flow rates are not correct in all component nodes, except for the OA inlet node, when the fan is not placed as the first component. The problem is caused by incorrect set up of node MassFlowRateMax and MassFlowRateMaxAvail, when the fan is not placed as the first component. I need to write a unit test first, then I will upload the fix. |
Issue overview
AirLoopHVAC:DedicatedOutdoorAirSystem does not work when the fan placement is draw through. Please refer to the Unmethours link below for mroe details on the issue.
Details
Some additional details for this issue (if relevant):
Checklist
Add to this list or remove from it as applicable. This is a simple templated set of guidelines.
The text was updated successfully, but these errors were encountered: