AirLoopHVAC:DedicatedOutdoorAirSystem does not work with draw through fan placement #9994

Closed
1 of 3 tasks
keigo-nomura opened this issue May 3, 2023 · 12 comments · Fixed by #10042
Closed
1 of 3 tasks
Assignees
Labels
Defect Includes code to repair a defect in EnergyPlus MediumComplexityApproved Used for subcontractor defect complexity requests

Comments

@keigo-nomura
Copy link

Issue overview

AirLoopHVAC:DedicatedOutdoorAirSystem does not work when the fan placement is draw through. Please refer to the Unmethours link below for mroe details on the issue.

Details

Some additional details for this issue (if relevant):

Checklist

Add to this list or remove from it as applicable. This is a simple templated set of guidelines.

  • Defect file added (list location of defect file here)
  • Ticket added to Pivotal for defect (development team task)
  • Pull request created (the pull request will have additional tasks related to reviewing changes that fix this defect)
@eringold
Copy link

eringold commented May 3, 2023

possibly related to #9066

@keigo-nomura
Copy link
Author

Oh, true. For V22-2-0, no severe/fatal errors appear, but the fan supply air flow and the fan power are 0.

@lgu1234 lgu1234 self-assigned this May 17, 2023
@lgu1234
Copy link
Contributor

lgu1234 commented May 22, 2023

@keigo-nomura I tested the bug input file and confirmed zero outputs for fan flow rate and energy. Then I found that when you switched fan placement order from blow through to draw through, you need to change node order also. For example, the inlet node of heating coil should be outdoor air inlet, and the outlet node of fan should be the inlet node of AirLoopHVAC:Splitter.

AirLoopHVAC:DedicatedOutdoorAirSystem,
AirLoopHVAC DOAS, !- Name
AirLoopDOAS OA system, !- AirLoopHVAC:OutdoorAirSystem Name
ALWAYS_ON, !- Availability Schedule Name
AirLoopDOASMixer, !- AirLoopHVAC:Mixer Name
AirLoopDOASSplitter, !- AirLoopHVAC:Splitter Name

When I made node order changes, the outputs are back to normal.

Unfortunately, the err file does not provide node connection error. I am going to add warning messages for connection error.

@keigo-nomura
Copy link
Author

@lgu1234 Thank you for investigating. However, I sitll don't know which Node input was wrong in the idf file SmallOffice_CentralDOAS_DrawThrough.idf. The following Node order looks correct to me. The inlet node of heating coil is already outdoor air inlet, and the outlet node of fan is already the inlet node of AirLoopHVAC:Splitter. Could you please point out exactly which input was wrong?

AirLoopHVAC:OutdoorAirSystem:EquipmentList,
OA Sys 1 Equipment, !- Name
Coil:Heating:Water, !- Component 1 Object Type
OA Heating Coil 1, !- Component 1 Name
Coil:Cooling:Water, !- Component 2 Object Type
OA Cooling Coil 1, !- Component 2 Name
Fan:SystemModel, !- Component 3 Object Type
OA Supply Fan; !- Component 3 Name

OutdoorAir:NodeList,
OutsideAirInletNodes; !- Node or NodeList Name 1

NodeList,
OutsideAirInletNodes, !- Name
Outside Air Inlet Node 1;!- Node 1 Name

Coil:Heating:Water,
OA Heating Coil 1, !- Name
CoolingCoilAvailSched, !- Availability Schedule Name
autosize, !- U-Factor Times Area Value {W/K}
autosize, !- Maximum Water Flow Rate {m3/s}
OA Heating Coil 1 Water Inlet Node, !- Water Inlet Node Name
OA Heating Coil 1 Water Outlet Node, !- Water Outlet Node Name
Outside Air Inlet Node 1,!- Air Inlet Node Name
OA Heating Coil 1 Air Outlet Node, !- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
autosize, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
16.6, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
32.2, !- Rated Outlet Air Temperature {C}
, !- Rated Ratio for Air and Water Convection
11; !- Design Water Temperature Difference {deltaC}

Coil:Cooling:Water,
OA Cooling Coil 1, !- Name
CoolingCoilAvailSched, !- Availability Schedule Name
autosize, !- Design Water Flow Rate {m3/s}
autosize, !- Design Air Flow Rate {m3/s}
autosize, !- Design Inlet Water Temperature {C}
autosize, !- Design Inlet Air Temperature {C}
autosize, !- Design Outlet Air Temperature {C}
autosize, !- Design Inlet Air Humidity Ratio {kgWater/kgDryAir}
autosize, !- Design Outlet Air Humidity Ratio {kgWater/kgDryAir}
OA Cooling Coil 1 Water Inlet Node, !- Water Inlet Node Name
OA Cooling Coil 1 Water Outlet Node, !- Water Outlet Node Name
OA Heating Coil 1 Air Outlet Node, !- Air Inlet Node Name
OA Cooling Coil 1 Air Outlet Node, !- Air Outlet Node Name
SimpleAnalysis, !- Type of Analysis
CrossFlow, !- Heat Exchanger Configuration
, !- Condensate Collection Water Storage Tank Name
4.0; !- Design Water Temperature Difference {deltaC}

Fan:SystemModel,
OA Supply Fan, !- Name
ALWAYS_ON, !- Availability Schedule Name
OA Cooling Coil 1 Air Outlet Node, !- Air Inlet Node Name
AirLoopDOASSplitterInlet,!- Air Outlet Node Name
Autosize, !- Design Maximum Air Flow Rate {m3/s}
Discrete, !- Speed Control Method
0.25, !- Electric Power Minimum Flow Rate Fraction
600.0, !- Design Pressure Rise {Pa}
0.9, !- Motor Efficiency
1.0, !- Motor In Air Stream Fraction
Autosize, !- Design Electric Power Consumption {W}
TotalEfficiencyAndPressure, !- Design Power Sizing Method
, !- Electric Power Per Unit Flow Rate {W/(m3/s)}
, !- Electric Power Per Unit Flow Rate Per Unit Pressure {W/((m3/s)-Pa)}
0.7, !- Fan Total Efficiency
, !- Electric Power Function of Flow Fraction Curve Name
, !- Night Ventilation Mode Pressure Rise {Pa}
, !- Night Ventilation Mode Flow Fraction
, !- Motor Loss Zone Name
, !- Motor Loss Radiative Fraction
General; !- End-Use Subcategory

AirLoopHVAC:Splitter,
AirLoopDOASSplitter, !- Name
AirLoopDOASSplitterInlet,!- Inlet Node Name
PSZ-AC:1_OAInlet Node, !- Outlet 1 Node Name
PSZ-AC:2_OAInlet Node, !- Outlet 2 Node Name
PSZ-AC:3_OAInlet Node, !- Outlet 3 Node Name
PSZ-AC:4_OAInlet Node, !- Outlet 4 Node Name
PSZ-AC:5_OAInlet Node; !- Outlet 5 Node Name

@lgu1234
Copy link
Contributor

lgu1234 commented May 24, 2023

@keigo-nomura

SetpointManager:Scheduled,
OA Air Temp Manager 1, !- Name
Temperature, !- Control Variable
OA Cooling Supply Air Temp Sch, !- Schedule Name
! AirLoopDOASSplitterInlet;!- Setpoint Node or NodeList Name
OA Cooling Coil 1 Air Outlet Node;!- Setpoint Node or NodeList Name

You may also need to change the node name in SetpointManager:Scheduled,

@keigo-nomura
Copy link
Author

@lgu1234 I should change the node name in SetpointManager:Scheduled and add SetpointManager:MixedAir if I want to consider the supply fan air temperature rise, but I don't think that's the cause of this issue.

@lgu1234
Copy link
Contributor

lgu1234 commented May 24, 2023

@keigo-nomura If you want, I can upload the file with correct node connection.

@keigo-nomura
Copy link
Author

@lgu1234 Yes, please. Sorry to bother you, but I would like to compare the difference between your file and my file.

@lgu1234
Copy link
Contributor

lgu1234 commented May 25, 2023

@keigo-nomura Here is the file
SmallOffice_CentralDOAS2.txt

@keigo-nomura
Copy link
Author

@lgu1234 The Node connection of your file is the same as the Node connection of my file SmallOffice_CentralDOAS_DrawThrough.idf

I'm sorry, but I don't know what you have changed. Besides, the OA Supply Fan in your file does not work as well. The issue has not been solved.

@lgu1234
Copy link
Contributor

lgu1234 commented May 25, 2023

@keigo-nomura I am going to take a look.

@lgu1234
Copy link
Contributor

lgu1234 commented Jun 5, 2023

@keigo-nomura You are right. The mass flow rates are not correct in all component nodes, except for the OA inlet node, when the fan is not placed as the first component. The problem is caused by incorrect set up of node MassFlowRateMax and MassFlowRateMaxAvail, when the fan is not placed as the first component.

I need to write a unit test first, then I will upload the fix.