IscIndMachine

The IscIndMachine class provides access to an IPSA induction machine, to set and get data values and to retrieve load flow and fault level results.

Field Values

.. tabularcolumns:: |\Y{0.15}|\Y{0.25}|\Y{0.6}|
IscIndMachine Field Values
Type Field Name Description
Integer FromUID Gets the unique ID for busbar.
String BusName Gets the busbar name.
String Name Gets the induction machine name.
Integer Status

Status:

  • 0 = Switched in
  • 1 = Switched in, but can be switched out during transient studies
  • -1 = Switched out, but can be switched in during transient studies
Float MechPowerMW Mechanical power output of motor. Use negative values for induction generators.
Float SlipPC Slip in %.
Float MagnetXPU Magnetising reactance.
Float StatorRPU Stator resistance.
Float StatorXPU Stator reactance.
Integer Model

The motor model used:

  • 0 = Running - standstill
  • 1 = Inner - outer
  • 2 = Not used
  • 3 = Not used
  • 4 = Running - standstill DFIG with slip control
  • 5 = Inner - outer DFIG with slip control
  • 6 = Running - standstill DFIG with slip and power factor control
  • 7 = Inner - outer DFIG with slip and power factor control
Float RotorRPU Inner cage or running rotor resistance.
Float RotorXPU Inner cage or running rotor reactance.
Float StandRPU Outer cage or standstill rotor resistance.
Float StartXPU Outer cage or standstill rotor reactance.
Float TSlipB Load torque-speed coefficient B.
Float TSlipC Load torque-speed squared coefficient C.
Float InertiaSec Inertia constant in kWs / kVA.
Float DropoffVPU If the voltage falls below this value disconnection will begin.
Float DropPickUpDelaySec The time taken to disconnect the machine.
Float LockTimeSec If a machine is disconnected for this length of time it will not be reconnected.
Float UnderspeedPU Under speed setting in per unit.
Float OverspeedPU Overspeed setting in per unit.
Float PickUpTimeSec The time taken to reconnect the machine.
Float PickUpVoltagePU If the voltage in per unit rises above this value reconnection will begin.
Float SwitchOut1Sec Time for the first switch-out operation. If the machine is already switched out, leave this entry blank.
Float SwitchIn1Sec Time for first switch-in.
Float SwitchOut2Sec Time for second switch-out.
Float SwitchIn2Sec Time for second switch-in.
Integer MaxSwitchOp Maximum number of automatic switching operations before the machine is locked out.
Integer DFFeedBusbar Feed busbar UID for doubly-fed model.
Float DFPowerFactor Power factor for doubly-fed model.
Boolean DFExportQ If True then reactive power is exported by the machine, else it is imported.
Integer DFRotorReferenceFrame

Rotor reference frame, either:

  • 0 = Direct-Quadrature aligned to stator voltage
  • 1 = Real-Imaginary aligned to stator voltage
Integer DFFaultSwitchMode

How the DFIG behaves when a fault is detected:

  • 0 = Turn off rotor, stator and turbine.
  • 1 = Turn off rotor, switch permanently to induction generator mode.
  • 2 = Turn off rotor, switch to induction generator mode, reset on time.
  • 3 = Turn off rotor, switch to induction generator mode, reset on current.
Float DFFaultRotorCurrentLimit When DFIG rotor current exceeds this value the DFIG alters its behaviour as determined by the fault switch mode.
Float DFFaultCrowbarLimit The effect of this parameter is determined by the fault switch mode. See the online help manual for details.
Float DFFaultCrowbarResPU Crowbar fault resistance (per unit on system base and rotor voltage base).
String DbType Gets the database type.
Integer DbPar Gets the number of motors in parallel.
Integer ControlModelType

Gets the Dynamic Model type.

  • 0 = Built in
  • 1 = Plugin
  • 2 = UDM
Float RatedMW The rated MW power of the machine. Only used in IEC60909 fault analysis.
Float RatedMVA The rated MVA power of the machine. Only used in IEC60909 fault analysis.
Integer PolePairs The number of pole pairs of the machine. Only used in IEC60909 fault analysis.
String ControlPluginID Gets the control plugin ID.

IscIndMachine Class

.. autoclass:: ipsa.IscIndMachine
   :members: