IscGridInfeed

The IscGridInfeed class provides access to an IPSA grid infeed, to set and get data values and to retrieve load flow and fault level results.

Field Values

.. tabularcolumns:: |\Y{0.15}|\Y{0.25}|\Y{0.6}|
IscGridInfeed Field Values
Type Field Name Description
Integer FromUID Gets the unique ID for busbar.
String BusName Gets the busbar name.
String Name Gets the grid infeed name.
Integer Status

Status:

  • 0 = Switched in
  • -1 = Switched out
Float VoltPU Per unit voltage target.
Float GenMW Generated real power.
Float GenMVAr Generated reactive power.
Integer ProfileUID Gets or sets the profile, ProfileUID, to be applied to the universal machine.
Float PeakLLL Peak asymmetric three phase fault contribution in MVA.
Float RMSLLL RMS three phase fault contribution in MVA at the break time specified by Tbreak.
Float X2RLLL Three phase X / R ratio determining the DC decay. A single exponential decay is modelled.
Float PeakLG Peak asymmetric single phase to ground fault contribution in MVA.
Float RMSLG RMS single phase to ground contribution in MVA at the break time specified by Tbreak.
Float Tac AC decay time constant for three phase faults, in seconds.
Float Tbreak RMS fault time in seconds.
Integer GridPlanningStage

The stage the load is currently at:

  • 0 = Proposed
  • 1 = Accepted
  • 2 = Completed
  • 3 = Energised (default, in service)

IscGridInfeed Class

.. autoclass:: ipsa.IscGridInfeed
   :members: