Lower the minimum temperature to 10C (50F) and make it pick up user-defined values. #20628
Add this suggestion to a batch that can be applied as a single commit.
This suggestion is invalid because no changes were made to the code.
Suggestions cannot be applied while the pull request is closed.
Suggestions cannot be applied while viewing a subset of changes.
Only one suggestion per line can be applied in a batch.
Add this suggestion to a batch that can be applied as a single commit.
Applying suggestions on deleted lines is not supported.
You must change the existing code in this line in order to create a valid suggestion.
Outdated suggestions cannot be applied.
This suggestion has been applied or marked resolved.
Suggestions cannot be applied from pending reviews.
Suggestions cannot be applied on multi-line comments.
Suggestions cannot be applied while the pull request is queued to merge.
Suggestion cannot be applied right now. Please check back later.
Description: Lower the MIEL_HVAC_UPDATE_TEMP_MIN from 16C (60.8F) to 10C (50.0F).
Checklist:
NOTE: The code change must pass CI tests. Your PR cannot be merged unless tests pass
I tested this by installing it on several different mini splits: MSZ-GL06NA, MSZ-GL15NA, PEAD-A15AA7 (ducted), MSZ-GS15NA, MSZ-GS09NA, and MSZ-GS06NA. All of them accept 10C HVACSetTemp commands and respond with that value in settings. I also tried sending 8C and they replied with 10C in settings; and tried 38C and they replied with 31C. So I think 10C and 31C are appropriate min/max.