!Example taken from the IEEE 519 Std (Example 1)
!NEW SYSTEM DEFINITION------------------------------------------------------------
New circuit.IEEE_519
~ bus1=SourceBus.1.2.3 Phases=3 basekv=115 pu=1.0001 Angle=30 Frequency=60 Mvasc3=20000 Mvasc1=21000
set DefaultBaseFreq=60
!REDIRECT TO SPECTRUM CODES--------------------------------------------
redirect Default_Spectrum.DSS
!LOAD DEFINITIONS------------------------------------------------------------
New Load.LD_3 bus1=N_4.1.2.3 Phases=3 Kv=0.4 Kw=12500 Pf=1.0 Model=1 spectrum=spectrum_2
New Load.LD_2 bus1=N_11.1.2.3 Phases=3 Kv=0.4 Kw=12500 Pf=1.0 Model=1 spectrum=spectrum_2
New Load.LD_Linear bus1=N_12.1.2.3 Phases=3 Kv=0.4 Kw=25000 Pf=1.0 Model=1 spectrum=spectrum_1
!SWITCH DEFINITIONS------------------------------------------------------------
New Line.SW_3 bus1=N_3.1.2.3 bus2=N_11.1.2.3 Phases=3 Switch=y r1=1e-4 r0=1e-4 x1=0.000 x0=0.000 c1=0.000 c0=0.000
New Line.SW_2 bus1=N_5.1.2.3 bus2=N_12.1.2.3 Phases=3 Switch=y r1=1e-4 r0=1e-4 x1=0.000 x0=0.000 c1=0.000 c0=0.000
!TRANSFORMER DEFINITIONS------------------------------------------------------------
New Transformer.Tr_3 Phases=3 wdg=1 bus=PCC.1.2.3 Conn=delta KV=13.8 Kva=12500 Sub=No wdg=2 bus=N_4.1.2.3 Conn=delta KV=0.4
New Transformer.Tr_4 Phases=3 wdg=1 bus=PCC.1.2.3 Conn=delta KV=13.8 Kva=25000 Sub=No wdg=2 bus=N_5.1.2.3 Conn=delta KV=0.4
New Transformer.Tr_2 Phases=3 wdg=1 bus=PCC.1.2.3 Conn=delta KV=13.8 Kva=12500 wdg=2 bus=N_3.1.2.3 Conn=wye KV=0.4
New Transformer.Tr_1 Phases=3 wdg=1 bus=SourceBus.1.2.3 Conn=delta KV=115 Kva=50000 wdg=2 bus=N_6.1.2.3 Conn=wye KV=13.8
!LINES DEFINITIONS------------------------------------------------------------
New Line.006-PCC bus1=N_6.1.2.3 bus2=PCC.1.2.3 Length=1 Phases=3 R1=1e-4 X1=0.0 R0=1e-4 X0=0.0 C1=0.0 C0=0.0
!CONTROLS DEFINITION------------------------------------------------------------
New Swtcontrol.SW_3_Ctrl basefreq=60 Delay=0.0 Action=Close SwitchedObj=Line.SW_3 SwitchedTerm=2 lock=open enabled=y
New Swtcontrol.SW_2_Ctrl basefreq=60 Delay=0.0 Action=Close SwitchedObj=Line.SW_2 SwitchedTerm=2 lock=open enabled=y
!MONITORS DEFINITION-------------------------------------------------------------
New monitor.MPCC element=Line.006-pcc mode=0
Set Controlmode=Time
! Initialize harmonics mode
solve
!Set new solution mode
set mode=harmonicT
!Starts the simulation
solve
open Line.SW_3
solve
open Line.SW_2
solve
export monitor MPCC
show monitor MPCC