clear
new circuit.sub phases=3 bus1=sub basekv=138.0 pu=1 angle=0.0
~ isc3=40000 isc1=41000 x1r1=18.5 x0r0=2
new Transformer.sub phases=3 windings=2 buses=(sub,xfbus)
~ kvas=(100000,100000) conns=(delta,wye) kvs=(135.3,13.8)
~ xhl=4.55 %loadloss=1.2 wdg=2 mintap=0.88 maxtap=1.12
new RegControl.ldc transformer=sub winding=2
~ delay=60 ptratio=69.282 ctprim=9200.0 vreg=115.00 band=3.0 r=2.0 x=3.0
// feeder parameters given per kft
new line.feeder phases=3 bus1=xfbus bus2=xfload length=0.1
~ r1=0.0166 x1=0.0314 r0=0.0166 x0=0.0314 c1=148 c0=148
new Transformer.Service phases=3 windings=2 buses=(xfload,network)
~ kvas=(300000,300000) conns=(delta,wye) kvs=(13.8,0.208)
~ xhl=7.00 %loadloss=0.4
new loadshape.ldc_2007 npts=8678 interval=1 csvfile=ldc_2007.dat action=normalize
// new loadshape.ldc_2007 npts=230 interval=0 csvfile=ldc_2007_approx.dat action=normalize
new Load.cust bus1=network kv=0.208 kva=320000 pf=0.88 vminpu=0.9 vmaxpu=1.1 yearly=ldc_2007
new Capacitor.capbank phases=3 bus1=xfbus kvar=200000 numsteps=10 kv=13.8
new capcontrol.var_ctrl capacitor=capbank type=kvar element=transformer.sub terminal=1
~ ptratio=1 ctratio=1 delay=5 delayoff=5 onsetting=15000 offsetting=-15000
new energymeter.feeder element=line.feeder terminal=1
set voltagebases="0.208,13.8,138.0"
calcvoltagebases
set loadmult=0.1
Set MaxControlIter = 100
solve