where m and n represent the dc and ac part of the thermal load.
Correction Factors m and n
For short-circuit currents far from synchronous generators, the factors are given as:
$$n = 1
m = \frac{1}{2 \cdot f \cdot T_k \cdot ln(\kappa - 1)} [e^{4 \cdot f \cdot T_k \cdot ln(\kappa - 1)} - 1]$$
where κ is the peak factor defined here <kappa> and Tk is the duration of the short-circuit current that can be defined as a parameter when running the short-circuit calculation.