# example
# request = 37 45 11 01 46 C2 C0 04 C2 40 C5 5C FB FF 0D
# response = 37 45 11 01 46 00 50 29 C2 40 C5 5C 01 01 01 00 01 01 00 01 01 00 02 02 3E 01 A0 00 00 01 5E F9 ED 00 00 00 00 00 00 00 00 00 00 00 00 85 17 AB E1 F7 B5 0D
----------------------------------------------------------------------------------------------
Data Name Unit Result Type
----------------------------------------------------------------------------------------------
37 45 head / /
11 ver / 1.1
01 adr / 1
46 cid1 / /
00 RTN / check RTN table
F0 4D length / /
B0 cid2 / check CID table
00 cid3 / check CID table
C5 5C / / /
01 total pack number / 1
------------------------------------
01 pack adr / 1
01 00 State code / check Inverter State table
01 Parallel number / 1
01 CAN port number / 1
00 01 CAN protocol / check Inverter Protocol table
01 RS485 port number / 1
00 02 RS485 protocol / check Inverter Protocol table
02 3E Max charge voltage 100mV 57400
01 A0 Max discharge voltage 100mV 41600
00 /
00 SOC endoff % 0%
01 5E Max charge current 100mA 35000
F9 ED Max discharge current 100mA -15500 signed
00 /
00 /
00 00 /
00 00 /
00 00 /
00 00 /
00 00 /
85 17 AB E1 crc32
------------------------------------
{#2 pack data}
------------------------------------
F7 B5 chksum
0D end
----------------------------------------------------------------------------------------------