Integrated Ultra-Supercritical Power Plant

The Integrated Ultra-Supercritical Power Plant is an example model to determine the optimal operation of a pulverized coal-fired ultra-supercritical power plant integrated with a thermal energy storage system (TES) for a given electricity price. This model integrates a Solar salt charge and discharge heat exchanger in the :ref:`Ultra-Supercritical Power Plant` model. A flowsheet of the integrated power plant is shown in the figure below:

../../images/integrated_ultra_supercritical_powerplant.png

Abbreviations

Acronym Name
RH Reheater (RH_1 and RH_2)
T Turbine (T_1 to T_{11})
BFPT Boiler Feed Water Pump Turbine
ST Storage Turbine
FWH Feed Water Heater (FWH_1 to FWH_9)
CM Condensate Mixer
CP Condenser Pump
BP Booster Pump
BFWP Boiler Feed Water Pump
SP Storage Pump
DA Deaerator
CS Charge Splitter
DS Discharge Splitter
HXC Charge Storage Heat Exchanger
HXD Discharge Storage Heat Exchanger
BFW Boiler Feed Water
F^{boiler} Boiler Flow Inlet (mol/s)
F^{cond} Condenser Flow Outlet (mol/s)
F^{charge}_{steam} Steam Flow to Charge Storage System (mol/s)
F^{charge}_{salt} Salt Flow to Charge Storage System (kg/s)
F^{discharge}_{BFW} Boiler Feed Water Flow to Discharge Storage System (mol/s)
F^{discharge}_{salt} Salt Flow to Discharge Storage System (kg/s)

Model Structure

For the construction of the integrated power plant model, the :ref:`Ultra-Supercritical Power Plant` model is used as the base model to integrate the charge and discharge heat exchangers. The optimal integration point and design of both storage heat excahngers are obtained using the :ref:`Design of Integrated Ultra-Supercritical Power Plant` model. The integrated model is also constructed using the unit models from the power generation unit model library in addition to the IAPWS property package for steam and water, and the Solar salt property package in the storage heat exchangers. The unit models used are shown in the table below:

Unit Model Units in Flowsheet
HelmTurbineStage Turbines (T_1 to T_{11}) and BFPT
HelmSplitter Turbine Splitters
Heater Boiler Components (Boiler, RH_1, and RH_2)
HelmMixer Mixers (CM and DA)
HelmIsentropicCompresssor Pumps (CP, BP, BFWP, and SP)
HeatExchanger Condenser, Feed Water Heaters (FWH_1 to FWH_9), and Storage Systems (HXC and HXD)

Degrees of Freedom

The integrated ultra-supercritical power plant model has a total of 4 degrees of freedom, listed below:

  1. Boiler feed water flow (boiler.inlet.flow_-mol),
  2. Steam flow to charge heat exchanger (HXC.inlet_-1.flow_-mol)
  3. Condensate flow to discharge heat exchanger (HXD.inlet_-2.flow_-mol),
  4. Cooler enthalpy at outlet (cooler.outlet.enth_-mol)

Notable Variables

Variable Name Description
PlantPowerOut Power out from the power plant in MW
Revenue Revenue in $ per hour
SaltInventory Total solar salt inventory in kg
HotSaltInventory Hot solar salt inventory in kg

Notable Constraints

  1. The net power is given by the sum of the power produced by the storage system and the plant as shown in the following equation:
NetPower = PlantPowerOut + ST.mechanical_-work
  1. The revenue is calculated by considering the given electricity price lmp_-signal and the amount of net power NetPower produced by the plant and the storage system. This is shown in the equation below:
Revenue = lmp_-signal * NetPower
  1. The salt inventory SaltInventory is given by the hot salt and total salt material balances, the latter involving a fixed amount of salt total_-salt. The material balances are shown in the following equations:
HotSaltInventory = HotSaltInventory + F^{charge}_{salt, outlet} - F^{discharge}_{salt, inlet}
total_-salt = HotSaltInventory + ColdSaltInventory