(two_winding_transformer_model)=
Input and Result Attributes and Units are defined at PowerSystemDataModel. Please refer to:
- Input: {doc}
PowerSystemDataModel - Two Winding Transformer Model <psdm:models/input/grid/transformer2w>
- Result: {doc}
PowerSystemDataModel - Two Winding Transformer Model <psdm:models/result/grid/transformer2w>
Calculation of basic equivalent circuit elements
... based on derived values. All values are given with regard to the high voltage side.
- Reference Impedance: $Z_{Ref}=\frac{V^{2}{Ref}}{S{Ref}},Z_{Ref}=\Omega$ based on externally given reference voltage
$V_{Ref}$ and reference apparent power$S_{Ref}$ - Reference Impedance regarding the transformer's reference system: $Z_{Ref,Transf} = \frac{V^{2}{HV}}{S{Rated}}, [Z_{Ref,Transf}] = \Omega$
- Reference Current:$I_{Ref,Transf} = \frac{S_Ref,Transf}{\sqrt{3} \cdot V_{HV}}, [I_{Ref,Tranf}] = A$
- Short circuit impedance:
$Z_{SC} = v_{SC} \cdot Z_{Ref,Transf}, [Z_{SC}] = \Omega$ with$[v_{SC}] = %$ - Short circuit resistance:$R_{SC} = \frac{P_{C_{u}}}{3 \cdot I^{2}{Ref,Transf}}, [R{SC}] = \Omega$
- Short circuit reactance: $X_{SC} = \sqrt{Z^{2}{SC} - R^{2}{SC}}, [X_{SC}] = \Omega$
- Main field impedance:
$Z_{M} = \frac{V_{HV}}{\sqrt{3} \cdot i_{noLoad \cdot I_{Ref,Transf}}}, Z_{M} = \Omega$ - Main field resistance: $R_{M} = \frac{V^{2}{HV}}{P{F_{e}}}, [R_{M}] = \Omega$
- Main field reactance: $X_{M} = \frac{1}{\sqrt{\frac{1}{Z^{2}{M}} - \frac{1}{R^{2}{M}}}}, [R_{M}] = \Omega$
When the load flow calculation asks for the values with regard to the low voltage side, each Impedance has to be divided by square of the transformers default transmission ration
- Short circuit resistance:
$R_{SC,LV} = \frac{R_{SC}}{\gamma^{2}}$ - Short circuit reactance:
$X_{SC,LV} = \frac{X_{SC}}{\gamma^{2}}$ - Main field resistance:
$R_{M,LV} = \frac{R_{M}}{\gamma^{2}}$ - Main field reactance:
$X_{M,LV} = \frac{X_{M}}{\gamma^{2}}$
Finally all values are delivered as per unit-values and ready to use in the fundamental $\pi$circuit:
- Short circuit conductance:
$g_{ij} = \frac{Z_{Ref}}{R_{SC}}$ - Short circuit susceptance:
$b_{ij} = \frac{Z_{Ref}}{X_{SC}}$ - Phase to ground conductance:
$g_{0} = \frac{Z_{Ref}}{2 \cdot R_{M}}$ - Phase to ground susceptance:
$B_{0} = \frac{Z_{Ref}}{2 \cdot X_{M}}$
If there is a tap changer, this has to be taken into account as well:
- Tap ratio:$\tau = 1 - (t_{actual}-t_{neutral}) \cdot \frac{dV}{100}$
- Tap changer is on low voltage side:
- Short circuit conductance:
$g_{ij} = \frac{Z_{Ref}}{R_{SC}} \cdot \tau$ - Short circuit susceptance:
$b_{ij} = \frac{Z_{Ref}}{X_{SC}} \cdot \tau$ - Phase to ground conductance:
$g_{0} = \frac{Z_{Ref}}{2 \cdot R_{M}}$ - Phase to ground susceptance:
$b_{0} = \frac{Z_{Ref}}{2 \cdot X_{M}} \cdot \tau^{2}$ - Tap changer is on highvoltage side:
- Short circuit conductance:$g_{ij} = \frac{Z_{Ref}}{R_{SC} \cdot \tau}$
- Short circuit susceptance:$b_{ij} = \frac{Z_{Ref}}{X_{SC} \cdot \tau}$
- Phase to ground conductance:$g_{0} = \frac{Z_{Ref}}{2 \cdot R_{M}}$
- Phase to ground susceptance:$b_{0} = \frac{Z_{Ref}}{2 \cdot X_{M} \cdot \tau^{2}}$