Redfish Input Plugin

The redfish plugin gathers metrics and status information about CPU temperature, fanspeed, Powersupply, voltage, hostname and Location details (datacenter, placement, rack and room) of hardware servers for which DMTF's Redfish is enabled.

Telegraf minimum version: Telegraf 1.15.0

Global configuration options

In addition to the plugin-specific configuration settings, plugins support additional global and plugin configuration settings. These settings are used to modify metrics, tags, and field or create aliases and configure ordering, etc. See the CONFIGURATION.md for more details.

Secret-store support

This plugin supports secrets from secret-stores for the username and password options. See the secret-store documentation for more details on how to use them.

Configuration

# Read CPU, Fans, Powersupply and Voltage metrics of hardware server through redfish APIs
[[inputs.redfish]]
  ## Redfish API Base URL.
  address = "https://127.0.0.1:5000"

  ## Credentials for the Redfish API. Can also use secrets.
  username = "root"
  password = "password123456"

  ## System Id to collect data for in Redfish APIs.
  computer_system_id="System.Embedded.1"

  ## Metrics to collect
  ## The metric collects to gather. Choose from "power" and "thermal".
  # include_metrics = ["power", "thermal"]

  ## Tag sets allow you to include redfish OData link parent data
  ## For Example.
  ## Thermal data is an OData link with parent Chassis which has a link of Location.
  ## For more info see the Redfish Resource and Schema Guide at DMTFs website.
  ## Available sets are: "chassis.location" and "chassis"
  # include_tag_sets = ["chassis.location"]

  ## Workarounds
  ## Defines workarounds for certain hardware vendors. Choose from:
  ## * ilo4-thermal - Do not pass 0Data-Version header to Thermal endpoint
  # workarounds = []

  ## Amount of time allowed to complete the HTTP request
  # timeout = "5s"

  ## Optional TLS Config
  # tls_ca = "/etc/telegraf/ca.pem"
  # tls_cert = "/etc/telegraf/cert.pem"
  # tls_key = "/etc/telegraf/key.pem"
  ## Use TLS but skip chain & host verification
  # insecure_skip_verify = false

Metrics

  • redfish_thermal_temperatures

    • tags:
      • source
      • member_id
      • address
      • name
      • state
      • health
    • fields:
      • reading_celsius
      • upper_threshold_critical
      • upper_threshold_fatal
      • lower_threshold_critical
      • lower_threshold_fatal
  • redfish_thermal_fans

    • tags:
      • source
      • member_id
      • address
      • name
      • state
      • health
    • fields:
      • reading_rpm (or) reading_percent
      • upper_threshold_critical
      • upper_threshold_fatal
      • lower_threshold_critical
      • lower_threshold_fatal
  • redfish_power_powersupplies

    • tags:
      • source
      • member_id
      • address
      • name
      • state
      • health
    • fields:
      • last_power_output_watts
      • line_input_voltage
      • power_capacity_watts
      • power_input_watts
      • power_output_watts
  • redfish_power_voltages (available only if voltage data is found)

    • tags:
      • source
      • member_id
      • address
      • name
      • state
      • health
    • fields:
      • reading_volts
      • upper_threshold_critical
      • upper_threshold_fatal
      • lower_threshold_critical
      • lower_threshold_fatal

Tag Sets

  • chassis.location

    • tags:
      • datacenter (available only if location data is found)
      • rack (available only if location data is found)
      • room (available only if location data is found)
      • row (available only if location data is found)
  • chassis

    • tags:
      • chassis_chassistype
      • chassis_manufacturer
      • chassis_model
      • chassis_partnumber
      • chassis_powerstate
      • chassis_sku
      • chassis_serialnumber
      • chassis_state
      • chassis_health

Example Output

redfish_thermal_temperatures,address=127.0.0.1,chassis_chassistype=RackMount,chassis_health=OK,chassis_manufacturer=Contoso,chassis_model=3500RX,chassis_partnumber=224071-J23,chassis_powerstate=On,chassis_serialnumber=437XR1138R2,chassis_sku=8675309,chassis_state=Enabled,health=OK,member_id=0,name=CPU1\ Temp,rack=WEB43,row=North,source=web483,state=Enabled reading_celsius=41,upper_threshold_critical=45,upper_threshold_fatal=48 1691270160000000000
redfish_thermal_temperatures,address=127.0.0.1,chassis_chassistype=RackMount,chassis_health=OK,chassis_manufacturer=Contoso,chassis_model=3500RX,chassis_partnumber=224071-J23,chassis_powerstate=On,chassis_serialnumber=437XR1138R2,chassis_sku=8675309,chassis_state=Enabled,member_id=1,name=CPU2\ Temp,rack=WEB43,row=North,source=web483,state=Disabled upper_threshold_critical=45,upper_threshold_fatal=48 1691270160000000000
redfish_thermal_temperatures,address=127.0.0.1,chassis_chassistype=RackMount,chassis_health=OK,chassis_manufacturer=Contoso,chassis_model=3500RX,chassis_partnumber=224071-J23,chassis_powerstate=On,chassis_serialnumber=437XR1138R2,chassis_sku=8675309,chassis_state=Enabled,health=OK,member_id=2,name=Chassis\ Intake\ Temp,rack=WEB43,row=North,source=web483,state=Enabled upper_threshold_critical=40,upper_threshold_fatal=50,lower_threshold_critical=5,lower_threshold_fatal=0,reading_celsius=25 1691270160000000000
redfish_thermal_fans,address=127.0.0.1,chassis_chassistype=RackMount,chassis_health=OK,chassis_manufacturer=Contoso,chassis_model=3500RX,chassis_partnumber=224071-J23,chassis_powerstate=On,chassis_serialnumber=437XR1138R2,chassis_sku=8675309,chassis_state=Enabled,health=OK,member_id=0,name=BaseBoard\ System\ Fan,rack=WEB43,row=North,source=web483,state=Enabled lower_threshold_fatal=0i,reading_rpm=2100i 1691270160000000000
redfish_thermal_fans,address=127.0.0.1,chassis_chassistype=RackMount,chassis_health=OK,chassis_manufacturer=Contoso,chassis_model=3500RX,chassis_partnumber=224071-J23,chassis_powerstate=On,chassis_serialnumber=437XR1138R2,chassis_sku=8675309,chassis_state=Enabled,health=OK,member_id=1,name=BaseBoard\ System\ Fan\ Backup,rack=WEB43,row=North,source=web483,state=Enabled lower_threshold_fatal=0i,reading_rpm=2050i 1691270160000000000
redfish_power_powersupplies,address=127.0.0.1,chassis_chassistype=RackMount,chassis_health=OK,chassis_manufacturer=Contoso,chassis_model=3500RX,chassis_partnumber=224071-J23,chassis_powerstate=On,chassis_serialnumber=437XR1138R2,chassis_sku=8675309,chassis_state=Enabled,health=Warning,member_id=0,name=Power\ Supply\ Bay,rack=WEB43,row=North,source=web483,state=Enabled line_input_voltage=120,last_power_output_watts=325,power_capacity_watts=800 1691270160000000000
redfish_power_voltages,address=127.0.0.1,chassis_chassistype=RackMount,chassis_health=OK,chassis_manufacturer=Contoso,chassis_model=3500RX,chassis_partnumber=224071-J23,chassis_powerstate=On,chassis_serialnumber=437XR1138R2,chassis_sku=8675309,chassis_state=Enabled,health=OK,member_id=0,name=VRM1\ Voltage,rack=WEB43,row=North,source=web483,state=Enabled upper_threshold_fatal=15,lower_threshold_critical=11,lower_threshold_fatal=10,reading_volts=12,upper_threshold_critical=13 1691270160000000000
redfish_power_voltages,address=127.0.0.1,chassis_chassistype=RackMount,chassis_health=OK,chassis_manufacturer=Contoso,chassis_model=3500RX,chassis_partnumber=224071-J23,chassis_powerstate=On,chassis_serialnumber=437XR1138R2,chassis_sku=8675309,chassis_state=Enabled,health=OK,member_id=1,name=VRM2\ Voltage,rack=WEB43,row=North,source=web483,state=Enabled reading_volts=5,upper_threshold_critical=7,lower_threshold_critical=4.5 1691270160000000000
redfish_thermal_temperatures,address=127.0.0.1,chassis_chassistype=RackMount,chassis_health=OK,chassis_manufacturer=Contoso,chassis_model=3500RX,chassis_partnumber=224071-J23,chassis_powerstate=On,chassis_serialnumber=437XR1138R2,chassis_sku=8675309,chassis_state=Enabled,health=OK,member_id=0,name=CPU1\ Temp,rack=WEB43,row=North,source=web483,state=Enabled upper_threshold_critical=45,upper_threshold_fatal=48,reading_celsius=41 1691270170000000000
redfish_thermal_temperatures,address=127.0.0.1,chassis_chassistype=RackMount,chassis_health=OK,chassis_manufacturer=Contoso,chassis_model=3500RX,chassis_partnumber=224071-J23,chassis_powerstate=On,chassis_serialnumber=437XR1138R2,chassis_sku=8675309,chassis_state=Enabled,member_id=1,name=CPU2\ Temp,rack=WEB43,row=North,source=web483,state=Disabled upper_threshold_critical=45,upper_threshold_fatal=48 1691270170000000000
redfish_thermal_temperatures,address=127.0.0.1,chassis_chassistype=RackMount,chassis_health=OK,chassis_manufacturer=Contoso,chassis_model=3500RX,chassis_partnumber=224071-J23,chassis_powerstate=On,chassis_serialnumber=437XR1138R2,chassis_sku=8675309,chassis_state=Enabled,health=OK,member_id=2,name=Chassis\ Intake\ Temp,rack=WEB43,row=North,source=web483,state=Enabled lower_threshold_critical=5,lower_threshold_fatal=0,reading_celsius=25,upper_threshold_critical=40,upper_threshold_fatal=50 1691270170000000000