Notifications
You must be signed in to change notification settings - Fork 152
/
Enable.mo
433 lines (428 loc) · 20.5 KB
/
Enable.mo
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
367
368
369
370
371
372
373
374
375
376
377
378
379
380
381
382
383
384
385
386
387
388
389
390
391
392
393
394
395
396
397
398
399
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421
422
423
424
425
426
427
428
429
430
431
432
433
within Buildings.Controls.OBC.ASHRAE.G36_PR1.AHUs.SingleZone.VAV.Economizers.Subsequences;
block Enable
"Single zone VAV AHU economizer enable/disable switch"
parameter Boolean use_enthalpy = true
"Set to true to evaluate outdoor air (OA) enthalpy in addition to temperature"
annotation(Dialog(group="Conditional", enable=not use_fixed_plus_differential_drybulb));
parameter Boolean use_fixed_plus_differential_drybulb = false
"Set to true to evaluate fixed plus differential dry bulb temperature high limit cutoff;
shall not be used with enthalpy"
annotation(Dialog(group="Conditional", enable=not use_enthalpy));
parameter Real delTOutHis(
final unit="K",
final displayUnit="K",
final quantity="TemperatureDifference")=1
"Delta between the temperature hysteresis high and low limit"
annotation(Dialog(tab="Advanced", group="Hysteresis"));
parameter Real delEntHis(
final unit="J/kg",
final quantity="SpecificEnergy")=1000
"Delta between the enthalpy hysteresis high and low limits"
annotation(Dialog(tab="Advanced", group="Hysteresis", enable = use_enthalpy));
parameter Real retDamPhyPosMax(
final min=0,
final max=1,
final unit="1") = 1
"Physically fixed maximum position of the return air damper"
annotation(Dialog(tab="Commissioning", group="Physical damper position limits"));
parameter Real retDamPhyPosMin(
final min=0,
final max=1,
final unit="1") = 0
"Physically fixed minimum position of the return air damper"
annotation(Dialog(tab="Commissioning", group="Physical damper position limits"));
Buildings.Controls.OBC.CDL.Interfaces.RealInput TOut(
final unit="K",
final displayUnit="degC",
final quantity = "ThermodynamicTemperature")
"Outdoor air temperature"
annotation (Placement(transformation(extent={{-220,250},{-180,290}}),
iconTransformation(extent={{-120,84},{-100,104}})));
Buildings.Controls.OBC.CDL.Interfaces.RealInput hOut(
final unit="J/kg",
final quantity="SpecificEnergy") if use_enthalpy
"Outdoor air enthalpy"
annotation (Placement(transformation(extent={{-220,160},{-180,200}}),
iconTransformation(extent={{-120,30},{-100,50}})));
Buildings.Controls.OBC.CDL.Interfaces.RealInput TCut(
final unit="K",
final displayUnit="degC",
final quantity="ThermodynamicTemperature")
"OA temperature high limit cutoff. For differential dry bulb temeprature condition use return air temperature measurement"
annotation (Placement(transformation(extent={{-220,220},{-180,260}}),
iconTransformation(extent={{-120,68},{-100,88}})));
Buildings.Controls.OBC.CDL.Interfaces.RealInput TRet(
final unit="K",
final displayUnit="degC",
final quantity = "ThermodynamicTemperature") if use_fixed_plus_differential_drybulb
"Used only for fixed plus differential dry bulb temperature high limit cutoff"
annotation (Placement(transformation(extent={{-220,190},{-180,230}}),
iconTransformation(extent={{-120,50},{-100,70}})));
Buildings.Controls.OBC.CDL.Interfaces.RealInput hCut(final unit="J/kg",
final quantity="SpecificEnergy") if use_enthalpy
"OA enthalpy high limit cutoff. For differential enthalpy use return air enthalpy measurement"
annotation (Placement(transformation(extent={{-220,130},{-180,170}}),
iconTransformation(extent={{-120,10},{-100,30}})));
Buildings.Controls.OBC.CDL.Interfaces.RealInput uOutDamPosMin(
final unit="1",
final min=0,
final max=1)
"Minimum outdoor air damper position, get from damper position limits sequence"
annotation (Placement(transformation(extent={{-220,-180},{-180,-140}}),
iconTransformation(extent={{-120,-90},{-100,-70}})));
Buildings.Controls.OBC.CDL.Interfaces.RealInput uOutDamPosMax(
final unit="1",
final min=0,
final max=1)
"Maximum outdoor air damper position, get from damper position limits sequence"
annotation (Placement(transformation(extent={{-220,-150},{-180,-110}}),
iconTransformation(extent={{-120,-70},{-100,-50}})));
Buildings.Controls.OBC.CDL.Interfaces.BooleanInput uSupFan
"Supply fan on/off status signal"
annotation (Placement(transformation(extent={{-220,90},{-180,130}}),
iconTransformation(extent={{-120,-50},{-100,-30}})));
Buildings.Controls.OBC.CDL.Interfaces.IntegerInput uZonSta
"Zone state status signal"
annotation (Placement(transformation(extent={{-220,-30},{-180,10}}),
iconTransformation(extent={{-120,-30},{-100,-10}})));
Buildings.Controls.OBC.CDL.Interfaces.IntegerInput uFreProSta
"Freeze protection stage status signal"
annotation (Placement(transformation(extent={{-220,30},{-180,70}}),
iconTransformation(extent={{-120,-10},{-100,10}})));
Buildings.Controls.OBC.CDL.Interfaces.RealOutput yOutDamPosMax(
final min=0,
final max=1,
final unit="1")
"Maximum outdoor air damper position"
annotation (Placement(transformation(extent={{180,-160},{220,-120}}),
iconTransformation(extent={{100,40},{140,80}})));
Buildings.Controls.OBC.CDL.Interfaces.RealOutput yRetDamPosMin(
final min=retDamPhyPosMin,
final max=retDamPhyPosMax,
final unit="1")
"Minimum return air damper position"
annotation (Placement(transformation(extent={{180,-260},{220,-220}}),
iconTransformation(extent={{100,-80},{140,-40}})));
Buildings.Controls.OBC.CDL.Interfaces.RealOutput yRetDamPosMax(
final min=retDamPhyPosMin,
final max=retDamPhyPosMax,
final unit="1")
"Maximum return air damper position"
annotation (Placement(transformation(extent={{180,-230},{220,-190}}),
iconTransformation(extent={{100,-20},{140,20}})));
Buildings.Controls.OBC.CDL.Logical.And3 andEnaDis
"Logical and that checks freeze protection stage and zone state"
annotation (Placement(transformation(extent={{40,30},{60,50}})));
Buildings.Controls.OBC.CDL.Logical.TrueFalseHold truFalHol(
trueHoldDuration=600) "10 min on/off delay"
annotation (Placement(transformation(extent={{124,214},{144,234}})));
CDL.Logical.Xor xor "Either fixed+differential temperature cutoff or others"
annotation (Placement(transformation(extent={{74,242},{94,262}})));
protected
final parameter Real TOutHigLimCutHig(
final unit="K",
final displayUnit="K",
final quantity="TemperatureDifference") = 0
"Hysteresis high limit cutoff";
final parameter Real TOutHigLimCutLow = TOutHigLimCutHig - delTOutHis
"Hysteresis low limit cutoff";
final parameter Real hOutHigLimCutHig(
final unit="J/kg",
final quantity="SpecificEnergy") = 0
"Hysteresis block high limit cutoff";
final parameter Real hOutHigLimCutLow = hOutHigLimCutHig - delEntHis
"Hysteresis block low limit cutoff";
Buildings.Controls.OBC.CDL.Logical.Sources.Constant entSubst(
final k=false) if not use_enthalpy
"Deactivates outdoor air enthalpy condition if there is no enthalpy sensor"
annotation (Placement(transformation(extent={{-60,170},{-40,190}})));
Buildings.Controls.OBC.CDL.Continuous.Sources.Constant retDamPhyPosMinSig(
final k=retDamPhyPosMin)
"Physically fixed minimum position of the return air damper"
annotation (Placement(transformation(extent={{-140,-258},{-120,-238}})));
Buildings.Controls.OBC.CDL.Continuous.Sources.Constant retDamPhyPosMaxSig(
final k=retDamPhyPosMax)
"Physically fixed maximum position of the return air damper. This is the initial condition of the return air damper"
annotation (Placement(transformation(extent={{-140,-220},{-120,-200}})));
Buildings.Controls.OBC.CDL.Continuous.Hysteresis hysOutTem(
final uHigh=TOutHigLimCutHig,
final uLow=TOutHigLimCutLow)
"Outdoor air temperature hysteresis for fixed or differential dry bulb temperature cutoff conditions"
annotation (Placement(transformation(extent={{-100,244},{-80,264}})));
Buildings.Controls.OBC.CDL.Continuous.Hysteresis hysOutEnt(
final uLow=hOutHigLimCutLow,
final uHigh=hOutHigLimCutHig) if use_enthalpy
"Outdoor air enthalpy hysteresis for fixed or differential enthalpy cutoff conditions"
annotation (Placement(transformation(extent={{-98,150},{-78,170}})));
Buildings.Controls.OBC.CDL.Continuous.Add add2(final k2=-1) if use_enthalpy
"Add block that determines the difference between hOut and hOutCut"
annotation (Placement(transformation(extent={{-140,150},{-120,170}})));
Buildings.Controls.OBC.CDL.Continuous.Add add1(final k2=-1)
"Add block that determines difference the between TOut and TOutCut"
annotation (Placement(transformation(extent={{-140,244},{-120,264}})));
Buildings.Controls.OBC.CDL.Logical.Switch outDamSwitch "Set maximum OA damper position to minimum at disable (after time delay)"
annotation (Placement(transformation(extent={{40,-150},{60,-130}})));
Buildings.Controls.OBC.CDL.Logical.Switch minRetDamSwitch
"Keep minimum RA damper position at physical maximum for a short time period after disable"
annotation (Placement(transformation(extent={{40,-250},{60,-230}})));
Buildings.Controls.OBC.CDL.Logical.Nor nor1 "Logical nor"
annotation (Placement(transformation(extent={{18,178},{38,198}})));
Buildings.Controls.OBC.CDL.Logical.Not not2
"Logical not that starts the timer at disable signal "
annotation (Placement(transformation(extent={{-10,-70},{10,-50}})));
Buildings.Controls.OBC.CDL.Logical.And and1 "Logical and checks supply fan status"
annotation (Placement(transformation(extent={{4,100},{24,120}})));
Buildings.Controls.OBC.CDL.Integers.Sources.Constant conInt(
final k=Buildings.Controls.OBC.ASHRAE.G36_PR1.Types.FreezeProtectionStages.stage0)
"Freeze protection stage 0"
annotation (Placement(transformation(extent={{-120,30},{-100,50}})));
Buildings.Controls.OBC.CDL.Integers.Equal intEqu
"Logical block to check if the freeze protection is deactivated"
annotation (Placement(transformation(extent={{-80,50},{-60,70}})));
Buildings.Controls.OBC.CDL.Integers.Sources.Constant conInt1(
final k=Buildings.Controls.OBC.ASHRAE.G36_PR1.Types.ZoneStates.heating)
"Heating zone state"
annotation (Placement(transformation(extent={{-120,-30},{-100,-10}})));
Buildings.Controls.OBC.CDL.Integers.Equal intEqu1
"Logical block to check if the freeze protection is deactivated"
annotation (Placement(transformation(extent={{-80,-10},{-60,10}})));
Buildings.Controls.OBC.CDL.Logical.Not not3 "Negation for check of freeze protection status"
annotation (Placement(transformation(extent={{-44,-10},{-24,10}})));
Buildings.Controls.OBC.CDL.Continuous.Add add3(final k2=-1) if
use_fixed_plus_differential_drybulb
"Add block that determines difference the between TOut and TOutCut"
annotation (Placement(transformation(extent={{-140,200},{-120,220}})));
Buildings.Controls.OBC.CDL.Continuous.Hysteresis hysCutTem(final uHigh=
TOutHigLimCutHig, final uLow=TOutHigLimCutLow) if use_fixed_plus_differential_drybulb
"Outdoor air temperature hysteresis for both fixed and differential dry bulb temperature cutoff conditions"
annotation (Placement(transformation(extent={{-100,200},{-80,220}})));
Buildings.Controls.OBC.CDL.Logical.Sources.Constant entSubst1(final k=false) if
not use_fixed_plus_differential_drybulb
"Deactivates the option if not using both fixed and differential dry bulb"
annotation (Placement(transformation(extent={{18,212},{38,232}})));
CDL.Logical.Nor nor2 if use_fixed_plus_differential_drybulb "Logical nor"
annotation (Placement(transformation(extent={{18,244},{38,264}})));
equation
connect(outDamSwitch.y, yOutDamPosMax)
annotation (Line(points={{62,-140},{200,-140}}, color={0,0,127}));
connect(TOut, add1.u1)
annotation (Line(points={{-200,270},{-160,270},{-160,260},{-142,260}},color={0,0,127}));
connect(TCut, add1.u2) annotation (Line(points={{-200,240},{-160,240},{-160,248},
{-142,248}}, color={0,0,127}));
connect(add1.y, hysOutTem.u)
annotation (Line(points={{-118,254},{-102,254}}, color={0,0,127}));
connect(hOut, add2.u1)
annotation (Line(points={{-200,180},{-160,180},{-160,166},{-142,166}},color={0,0,127}));
connect(hCut, add2.u2) annotation (Line(points={{-200,150},{-160,150},{-160,154},
{-142,154}}, color={0,0,127}));
connect(add2.y, hysOutEnt.u)
annotation (Line(points={{-118,160},{-100,160}}, color={0,0,127}));
connect(hysOutTem.y, nor1.u1)
annotation (Line(points={{-78,254},{-14,254},{-14,188},{16,188}},
color={255,0,255}));
connect(hysOutEnt.y, nor1.u2)
annotation (Line(points={{-76,160},{-14,160},{-14,180},{16,180}}, color={255,0,255}));
connect(entSubst.y, nor1.u2)
annotation (Line(points={{-38,180},{16,180}},
color={255,0,255}));
connect(uOutDamPosMin, outDamSwitch.u1)
annotation (Line(points={{-200,-160},{-60,-160},{-60,-132},{38,-132}},
color={0,0,127}));
connect(uOutDamPosMax, outDamSwitch.u3)
annotation (Line(points={{-200,-130},{-80,-130},{-80,-148},{38,-148}}, color={0,0,127}));
connect(andEnaDis.y, not2.u)
annotation (Line(points={{62,40},{72,40},{72,-20},{-20,-20},{-20,-60},{-12,-60}},
color={255,0,255}));
connect(minRetDamSwitch.y, yRetDamPosMin)
annotation (Line(points={{62,-240},{200,-240}}, color={0,0,127}));
connect(truFalHol.y, and1.u1)
annotation (Line(points={{146,224},{164,224},{164,130},{-26,130},{-26,110},
{2,110}},
color={255,0,255}));
connect(and1.y, andEnaDis.u1)
annotation (Line(points={{26,110},{30,110},{30,48},{38,48}}, color={255,0,255}));
connect(uSupFan, and1.u2)
annotation (Line(points={{-200,110},{-102,110},{-102,102},{2,102}}, color={255,0,255}));
connect(retDamPhyPosMaxSig.y, minRetDamSwitch.u1)
annotation (Line(points={{-118,-210},{-4,-210},{-4,-232},{38,-232}}, color={0,0,127}));
connect(retDamPhyPosMinSig.y, minRetDamSwitch.u3)
annotation (Line(points={{-118,-248},{38,-248}}, color={0,0,127}));
connect(retDamPhyPosMaxSig.y, yRetDamPosMax)
annotation (Line(points={{-118,-210},{200,-210}}, color={0,0,127}));
connect(not2.y, minRetDamSwitch.u2)
annotation (Line(points={{12,-60},{16,-60},{16,-240},{38,-240}}, color={255,0,255}));
connect(not2.y, outDamSwitch.u2)
annotation (Line(points={{12,-60},{28,-60},{28,-140},{38,-140}}, color={255,0,255}));
connect(conInt.y,intEqu. u2)
annotation (Line(points={{-98,40},{-92,40},{-92,52},{-82,52}}, color={255,127,0}));
connect(conInt1.y,intEqu1. u2)
annotation (Line(points={{-98,-20},{-90,-20},{-90,-8},{-82,-8}}, color={255,127,0}));
connect(intEqu1.y,not3. u)
annotation (Line(points={{-58,0},{-46,0}}, color={255,0,255}));
connect(uZonSta, intEqu1.u1)
annotation (Line(points={{-200,-10},{-140,-10},{-140,0},{-82,0}}, color={255,127,0}));
connect(uFreProSta, intEqu.u1)
annotation (Line(points={{-200,50},{-140,50},{-140,60},{-82,60}}, color={255,127,0}));
connect(intEqu.y, andEnaDis.u2)
annotation (Line(points={{-58,60},{-10,60},{-10,40},{38,40}}, color={255,0,255}));
connect(not3.y, andEnaDis.u3)
annotation (Line(points={{-22,0},{8,0},{8,32},{38,32}}, color={255,0,255}));
connect(TRet, add3.u2) annotation (Line(points={{-200,210},{-160,210},{-160,204},
{-142,204}}, color={0,0,127}));
connect(TOut, add3.u1) annotation (Line(points={{-200,270},{-160,270},{-160,260},
{-152,260},{-152,216},{-142,216}}, color={0,0,127}));
connect(add3.y, hysCutTem.u)
annotation (Line(points={{-118,210},{-102,210}}, color={0,0,127}));
connect(hysCutTem.y, nor2.u2) annotation (Line(points={{-78,210},{-38,210},{
-38,246},{16,246}},
color={255,0,255}));
connect(nor2.u1, hysOutTem.y) annotation (Line(points={{16,254},{-78,254}},
color={255,0,255}));
connect(nor2.y, xor.u1) annotation (Line(points={{40,254},{56,254},{56,252},{
72,252}},
color={255,0,255}));
connect(entSubst1.y, xor.u1) annotation (Line(points={{40,222},{54,222},{54,
252},{72,252}},
color={255,0,255}));
connect(nor1.y, xor.u2) annotation (Line(points={{40,188},{62,188},{62,244},{
72,244}},
color={255,0,255}));
connect(xor.y, truFalHol.u) annotation (Line(points={{96,252},{106,252},{106,
224},{122,224}},
color={255,0,255}));
annotation (
Icon(graphics={
Rectangle(
extent={{-100,-100},{100,100}},
lineColor={0,0,127},
fillColor={255,255,255},
fillPattern=FillPattern.Solid),
Line(
points={{0,60},{80,60}},
color={0,0,127},
thickness=0.5),
Line(
points={{-76,-60},{0,-60},{0,60}},
color={0,0,127},
thickness=0.5),
Text(
extent={{-170,142},{158,104}},
lineColor={0,0,127},
textString="%name")}),
Diagram(coordinateSystem(
preserveAspectRatio=false,
extent={{-180,-280},{180,280}}), graphics={
Rectangle(
extent={{-170,-44},{170,-274}},
lineColor={0,0,0},
fillColor={215,215,215},
fillPattern=FillPattern.Solid),
Rectangle(
extent={{-170,16},{170,-36}},
lineColor={0,0,0},
fillColor={215,215,215},
fillPattern=FillPattern.Solid),
Rectangle(
extent={{-170,76},{170,24}},
lineColor={0,0,0},
fillColor={215,215,215},
fillPattern=FillPattern.Solid),
Rectangle(
extent={{-170,136},{170,84}},
lineColor={0,0,0},
fillColor={215,215,215},
fillPattern=FillPattern.Solid),
Rectangle(
extent={{-170,276},{170,146}},
lineColor={0,0,0},
fillColor={215,215,215},
fillPattern=FillPattern.Solid),
Text(
extent={{102,168},{178,156}},
lineColor={0,0,0},
horizontalAlignment=TextAlignment.Left,
textString="Outdoor air
conditions"), Text(
extent={{100,70},{264,48}},
lineColor={0,0,0},
horizontalAlignment=TextAlignment.Left,
textString="Freeze protection -
disable if stage1
and above"), Text(
extent={{100,-34},{214,-86}},
lineColor={0,0,0},
horizontalAlignment=TextAlignment.Left,
textString="Damper position
limit assignments"), Text(
extent={{102,16},{206,-22}},
lineColor={0,0,0},
horizontalAlignment=TextAlignment.Left,
textString="Zone state -
disable if
heating"), Text(
extent={{100,102},{182,92}},
lineColor={0,0,0},
horizontalAlignment=TextAlignment.Left,
textString="Supply fan status")}),
Documentation(info="<html>
<p>
This is a single zone VAV AHU economizer enable/disable sequence
based on ASHRAE G36 PART 5.5 and PART 5.A.17. Additional
conditions included in the sequence are:
</p>
<ul>
<li>
<a href=\"modelica://Buildings.Controls.OBC.ASHRAE.G36_PR1.Types.FreezeProtectionStages\">
Buildings.Controls.OBC.ASHRAE.G36_PR1.Types.FreezeProtectionStages</a> (PART 5.9),
</li>
<li>
Supply fan status <code>TSupFan</code> (PART 5.4.d),
</li>
<li>
<a href=\"modelica://Buildings.Controls.OBC.ASHRAE.G36_PR1.Types.ZoneStates\">
Buildings.Controls.OBC.ASHRAE.G36_PR1.Types.ZoneStates</a> (PART 5.3.b).
</li>
</ul>
<p>
The economizer is disabled whenever the outdoor air conditions
exceed the economizer high limit cutoff setpoint plus the hysteresis low limit parameter
(<code>TOutHigLimCutLow</code> or <code>hOutHigLimCutLow</code>) as shown in the figure.
And the economizer is enabled whenever the outdoor air conditions are below the economizer
high limit cutoff setpoint plus the hysteresis high limit parameter (<code>TOutHigLimCutHig</code> or
<code>hOutHigLimCutHig</code>). This sequence allows for all device types listed in
ASHRAE 90.1-2013 and Title 24-2013.
</p>
<p>
In addition, the economizer is disabled without a delay whenever any of the
following is <code>true</code>:
</p>
<ul>
<li>supply fan is off,
</li>
<li>
zone state is <code>heating</code>,
</li>
<li>
freeze protection stage is not <code>0</code>.
</li>
</ul>
<p>
The following state machine chart illustrates the transitions between enabling and disabling:
</p>
<p align=\"center\">
<img alt=\"Image of economizer enable-disable state machine chart\"
src=\"modelica://Buildings/Resources/Images/Controls/OBC/ASHRAE/G36_PR1/AHUs/SingleZone/VAV/Economizers/Subsequences/Enable.png\"/>
</p>
</html>", revisions="<html>
<ul>
<li>
July 30, 2019, by Kun Zhang:<br/>
Added the option to allow fixed plus differential dry bulb temperature cutoff.
</li>
<li>
July 06, 2017, by Milica Grahovac:<br/>
First implementation.
</li>
</ul>
</html>"));
end Enable;