Skip to content

Commit

Permalink
Conditionally removed computation of state_a and state_b
Browse files Browse the repository at this point in the history
  • Loading branch information
mwetter committed Apr 1, 2015
1 parent ee3738a commit 7f5e136
Showing 1 changed file with 16 additions and 9 deletions.
25 changes: 16 additions & 9 deletions Buildings/Fluid/Interfaces/PartialTwoPortTransport.mo
Expand Up @@ -55,19 +55,19 @@ partial model PartialTwoPortTransport
m_flow_small) if show_T
"Temperature close to port_b, if show_T = true";
protected
Medium.ThermodynamicState state_a "state for medium inflowing through port_a";
Medium.ThermodynamicState state_b "state for medium inflowing through port_b";
equation
// medium states
state_a = Medium.setState_phX(
Medium.ThermodynamicState state_a = Medium.setState_phX(
port_a.p,
inStream(port_a.h_outflow),
inStream(port_a.Xi_outflow));
state_b = Medium.setState_phX(
inStream(port_a.Xi_outflow)) if
show_T or show_V_flow
"State for medium inflowing through port_a";
Medium.ThermodynamicState state_b = Medium.setState_phX(
port_b.p,
inStream(port_b.h_outflow),
inStream(port_b.Xi_outflow));

inStream(port_b.Xi_outflow)) if
show_T or show_V_flow
"state for medium inflowing through port_b";
equation
// Pressure drop in design flow direction
dp = port_a.p - port_b.p;

Expand Down Expand Up @@ -120,6 +120,13 @@ users have not used this global definition to assign parameters.
</html>", revisions="<html>
<ul>
<li>
April 1, 2015, by Michael Wetter:<br/>
Made computation of <code>state_a</code> and <code>state_p</code>
conditional on <code>show_T</code> or <code>show_V_flow</code>.
This avoids computating temperature from enthalpy if temperature is
a state of the medium, and the result is not used.
</li>
<li>
October 21, 2014, by Michael Wetter:<br/>
Revised implementation.
</li>
Expand Down

0 comments on commit 7f5e136