control error of primary pumps in a primary-secondary chilled water system with WSE for data center applications #1080

Closed
YangyangFu opened this issue Nov 24, 2017 · 1 comment · Fixed by #1082

Comments

@YangyangFu
Copy link
Contributor

YangyangFu commented Nov 24, 2017

@mwetter Hi Dr. Wetter, there is an error in the primary-secondary chilled water system with an integrated WSE. In free cooling mode, the primary pumps should be turned off and only the secondary pumps should be used to deliver the chilled water from WSE to AHU.

Can you open a new branch so that I could update the model?

@mwetter
Copy link
Member

mwetter commented Nov 27, 2017

@YangyangFu : Could you please make a pull request against the branch issue1080_chiller_wse. Thanks