PowerWalker VI 1200 SHL #1270

Closed
blazzakrajsek opened this issue Jan 22, 2022 · 0 comments
Closed

PowerWalker VI 1200 SHL #1270

blazzakrajsek opened this issue Jan 22, 2022 · 0 comments
Labels
DDL HCL PowerWalker PowerWalker and BlueWalker branded devices

Comments

@blazzakrajsek
Copy link
Contributor

I don't see the PowerWalker VI 1200 SHL to be officially supported, so I provide some diagnostic data which could be of help to someone supporting this device officially in NUT.

ups.conf:

[ups0]  
        driver = usbhid-ups
        port = auto
        vendorid = 06da
        productid = ffff
        desc = "PowerWalker VI 1200 SHL"

/lib/nut/usbhid-ups -a ups0 -DDDDDD:

Network UPS Tools - Generic HID driver 0.41 (2.7.4)
USB communication driver 0.33
   0.000000	debug level is '6'
   0.000485	upsdrv_initups...
   ...
   2.917997	Checking device (06DA/FFFF) (001/002)
   2.941520	- VendorID: 06da
   2.941524	- ProductID: ffff
   2.941525	- Manufacturer: PPC
   2.941526	- Product: Offline UPS
   2.941527	- Serial Number: 000000000   
   2.941528	- Bus: 001
   2.941529	- Device release number: 0003
   2.941530	Trying to match device
   2.941546	Device matches
   2.941556	nut_usb_set_altinterface: skipped usb_set_altinterface(udev, 0)
   2.945522	HID descriptor, method 1: (9 bytes) => 09 21 00 01 00 01 22 ef 01
   2.945525	HID descriptor length (method 1) 495
   2.945526	i=0, extra[i]=09, extra[i+1]=21
   2.945528	HID descriptor, method 2: (9 bytes) => 09 21 00 01 00 01 22 ef 01
   2.945529	HID descriptor length (method 2) 495
   2.945530	HID descriptor length 495
   3.009521	Report Descriptor size = 495
   3.009527	Report Descriptor: (495 bytes) => 05 84 09 04 a1 01 09 10 a1 00 09 12 a1 00
   3.009530	 05 84 09 58 85 24 75 08 95 01 65 00 15 00 26 ff 00 55 00 b1 82 c0 c0 09 1e
   3.009533	 a1 84 09 43 85 74 75 10 95 01 15 00 27 ff ff 00 00 66 21 d1 55 07 b1 83 09
   3.009536	 42 85 36 75 08 26 ff 00 66 01 f0 55 00 b1 82 09 40 85 72 67 21 d1 f0 00 55
   3.009539	 07 b1 82 c0 09 16 a1 00 06 ff ff 09 41 85 4a 65 00 55 00 b1 03 05 84 09 1a
   3.009541	 a1 81 05 84 09 30 85 31 75 10 27 ff ff 00 00 67 21 d1 f0 00 55 07 b1 83 09
   3.009544	 02 a1 02 09 6e 85 2d 75 08 26 ff 00 65 00 55 00 b1 83 09 6e 81 83 09 6f b1
   3.009547	 83 09 6f 81 83 c0 c0 05 84 09 1c a1 00 05 84 09 32 85 42 75 10 27 ff ff 00
   3.009549	 00 66 01 f0 55 0f b1 83 05 84 09 30 85 42 75 10 27 ff ff 00 00 67 21 d1 f0
   3.009552	 00 55 07 b1 83 c0 c0 09 24 a1 00 09 5a 85 13 75 08 15 00 26 ff 00 65 00 55
   3.009555	 00 b1 82 05 84 09 57 85 09 75 20 15 ff 27 ff ff ff 7f 66 01 10 b1 82 09 56
   3.009557	 85 0a b1 82 05 85 09 89 85 10 75 08 15 00 26 ff 00 65 00 b1 03 05 84 09 fd
   3.009560	 b1 03 06 ff ff 09 f0 b1 03 05 84 09 fe b1 03 05 84 09 ff b1 03 06 ff ff 09
   3.009563	 e2 85 e2 b1 83 05 84 09 35 85 07 15 00 26 ff 00 65 00 b1 83 05 84 09 02 a1
   3.009565	 02 05 85 09 d0 85 01 75 08 b1 83 09 d0 81 83 09 42 b1 83 09 42 81 83 09 44
   3.009568	 b1 83 09 44 81 83 05 85 09 45 b1 83 09 45 81 83 05 84 09 61 b1 83 09 61 81
   3.009570	 83 09 62 b1 83 09 62 81 83 05 84 09 65 b1 83 09 65 81 83 c0 05 85 85 0b 75
   3.009573	 08 95 01 15 00 25 64 09 83 b1 03 09 8d b1 03 09 67 65 00 b1 03 09 2c 65 00
   3.009576	 b1 03 09 66 85 06 65 00 b1 83 09 66 81 83 05 85 09 68 85 06 75 10 26 ff 7f
   3.009578	 66 01 10 b1 83 09 68 81 83 05 84 09 30 85 07 75 10 26 ff 7f 67 21 d1 f0 00
   3.009580	 55 06 b1 83 c0 c0
   3.009608	Using subdriver: MGE HID 1.40
   3.009610	45 HID objects found
   3.009611	Entering libusb_get_report
   3.012521	Report[get]: (2 bytes) => 24 06
   3.012524	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.012526	Unit = 00000000, UnitExp = 0
   3.012527	Exponent = 0
   3.012529	hid_lookup_path: 00840004 -> UPS
   3.012531	hid_lookup_path: 00840010 -> BatterySystem
   3.012532	hid_lookup_path: 00840012 -> Battery
   3.012534	hid_lookup_path: 00840058 -> Test
   3.012536	Path: UPS.BatterySystem.Battery.Test, Type: Feature, ReportID: 0x24, Offset: 0, Size: 8, Value: 6
   3.012537	Entering libusb_get_report
   3.015519	Report[get]: (3 bytes) => 74 05 00
   3.015522	PhyMax = 0, PhyMin = 0, LogMax = 65535, LogMin = 0
   3.015523	Unit = 0000d121, UnitExp = 7
   3.015524	Exponent = 0
   3.015525	hid_lookup_path: 00840004 -> UPS
   3.015526	hid_lookup_path: 0084001e -> Flow
   3.015528	hid_lookup_path: 00ff0004 -> not found in lookup table
   3.015529	hid_lookup_path: 00840043 -> ConfigApparentPower
   3.015531	Path: UPS.Flow.[4].ConfigApparentPower, Type: Feature, ReportID: 0x74, Offset: 0, Size: 16, Value: 5
   3.015532	Entering libusb_get_report
   3.018520	Report[get]: (2 bytes) => 36 32
   3.018523	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.018524	Unit = 0000f001, UnitExp = 0
   3.018525	Exponent = 0
   3.018526	hid_lookup_path: 00840004 -> UPS
   3.018527	hid_lookup_path: 0084001e -> Flow
   3.018529	hid_lookup_path: 00ff0004 -> not found in lookup table
   3.018530	hid_lookup_path: 00840042 -> ConfigFrequency
   3.018532	Path: UPS.Flow.[4].ConfigFrequency, Type: Feature, ReportID: 0x36, Offset: 0, Size: 8, Value: 50
   3.018533	Entering libusb_get_report
   3.021520	Report[get]: (2 bytes) => 72 e6
   3.021524	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.021526	Unit = 00f0d121, UnitExp = 7
   3.021527	Exponent = 0
   3.021528	hid_lookup_path: 00840004 -> UPS
   3.021529	hid_lookup_path: 0084001e -> Flow
   3.021531	hid_lookup_path: 00ff0004 -> not found in lookup table
   3.021532	hid_lookup_path: 00840040 -> ConfigVoltage
   3.021534	Path: UPS.Flow.[4].ConfigVoltage, Type: Feature, ReportID: 0x72, Offset: 0, Size: 8, Value: 230
   3.021535	Entering libusb_get_report
   3.024521	Report[get]: (2 bytes) => 4a 01
   3.024524	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.024525	Unit = 00000000, UnitExp = 0
   3.024526	Exponent = 0
   3.024528	hid_lookup_path: 00840004 -> UPS
   3.024529	hid_lookup_path: 00840016 -> PowerConverter
   3.024530	hid_lookup_path: ffff0041 -> ConverterType
   3.024532	Path: UPS.PowerConverter.ConverterType, Type: Feature, ReportID: 0x4a, Offset: 0, Size: 8, Value: 1
   3.024533	Entering libusb_get_report
   3.027519	Report[get]: (3 bytes) => 31 ea 00
   3.027521	PhyMax = 0, PhyMin = 0, LogMax = 65535, LogMin = 0
   3.027522	Unit = 00f0d121, UnitExp = 7
   3.027523	Exponent = 0
   3.027525	hid_lookup_path: 00840004 -> UPS
   3.027526	hid_lookup_path: 00840016 -> PowerConverter
   3.027527	hid_lookup_path: 0084001a -> Input
   3.027529	hid_lookup_path: 00ff0001 -> not found in lookup table
   3.027530	hid_lookup_path: 00840030 -> Voltage
   3.027532	Path: UPS.PowerConverter.Input.[1].Voltage, Type: Feature, ReportID: 0x31, Offset: 0, Size: 16, Value: 234
   3.027533	Entering libusb_get_report
   3.030519	Report[get]: (3 bytes) => 2d 00 00
   3.030521	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.030522	Unit = 00000000, UnitExp = 0
   3.030523	Exponent = 0
   3.030524	hid_lookup_path: 00840004 -> UPS
   3.030526	hid_lookup_path: 00840016 -> PowerConverter
   3.030527	hid_lookup_path: 0084001a -> Input
   3.030528	hid_lookup_path: 00ff0001 -> not found in lookup table
   3.030529	hid_lookup_path: 00840002 -> PresentStatus
   3.030531	hid_lookup_path: 0084006e -> Boost
   3.030532	Path: UPS.PowerConverter.Input.[1].PresentStatus.Boost, Type: Feature, ReportID: 0x2d, Offset: 0, Size: 8, Value: 0
   3.030534	Report[buf]: (3 bytes) => 2d 00 00
   3.030535	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.030535	Unit = 00000000, UnitExp = 0
   3.030536	Exponent = 0
   3.030537	hid_lookup_path: 00840004 -> UPS
   3.030539	hid_lookup_path: 00840016 -> PowerConverter
   3.030540	hid_lookup_path: 0084001a -> Input
   3.030541	hid_lookup_path: 00ff0001 -> not found in lookup table
   3.030542	hid_lookup_path: 00840002 -> PresentStatus
   3.030543	hid_lookup_path: 0084006e -> Boost
   3.030545	Path: UPS.PowerConverter.Input.[1].PresentStatus.Boost, Type: Input, ReportID: 0x2d, Offset: 0, Size: 8, Value: 0
   3.030546	Report[buf]: (3 bytes) => 2d 00 00
   3.030547	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.030548	Unit = 00000000, UnitExp = 0
   3.030549	Exponent = 0
   3.030550	hid_lookup_path: 00840004 -> UPS
   3.030551	hid_lookup_path: 00840016 -> PowerConverter
   3.030552	hid_lookup_path: 0084001a -> Input
   3.030553	hid_lookup_path: 00ff0001 -> not found in lookup table
   3.030554	hid_lookup_path: 00840002 -> PresentStatus
   3.030555	hid_lookup_path: 0084006f -> Buck
   3.030557	Path: UPS.PowerConverter.Input.[1].PresentStatus.Buck, Type: Feature, ReportID: 0x2d, Offset: 8, Size: 8, Value: 0
   3.030558	Report[buf]: (3 bytes) => 2d 00 00
   3.030559	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.030560	Unit = 00000000, UnitExp = 0
   3.030561	Exponent = 0
   3.030562	hid_lookup_path: 00840004 -> UPS
   3.030563	hid_lookup_path: 00840016 -> PowerConverter
   3.030564	hid_lookup_path: 0084001a -> Input
   3.030565	hid_lookup_path: 00ff0001 -> not found in lookup table
   3.030567	hid_lookup_path: 00840002 -> PresentStatus
   3.030568	hid_lookup_path: 0084006f -> Buck
   3.030569	Path: UPS.PowerConverter.Input.[1].PresentStatus.Buck, Type: Input, ReportID: 0x2d, Offset: 8, Size: 8, Value: 0
   3.030570	Entering libusb_get_report
   3.033520	Report[get]: (5 bytes) => 42 f2 01 ea 00
   3.033524	PhyMax = 0, PhyMin = 0, LogMax = 65535, LogMin = 0
   3.033525	Unit = 0000f001, UnitExp = -1
   3.033526	Exponent = -1
   3.033527	hid_lookup_path: 00840004 -> UPS
   3.033529	hid_lookup_path: 00840016 -> PowerConverter
   3.033530	hid_lookup_path: 0084001c -> Output
   3.033531	hid_lookup_path: 00840032 -> Frequency
   3.033533	Path: UPS.PowerConverter.Output.Frequency, Type: Feature, ReportID: 0x42, Offset: 0, Size: 16, Value: 49.8
   3.033535	Report[buf]: (5 bytes) => 42 f2 01 ea 00
   3.033536	PhyMax = 0, PhyMin = 0, LogMax = 65535, LogMin = 0
   3.033537	Unit = 00f0d121, UnitExp = 7
   3.033538	Exponent = 0
   3.033539	hid_lookup_path: 00840004 -> UPS
   3.033540	hid_lookup_path: 00840016 -> PowerConverter
   3.033541	hid_lookup_path: 0084001c -> Output
   3.033543	hid_lookup_path: 00840030 -> Voltage
   3.033544	Path: UPS.PowerConverter.Output.Voltage, Type: Feature, ReportID: 0x42, Offset: 16, Size: 16, Value: 234
   3.033545	Entering libusb_get_report
   3.036519	Report[get]: (2 bytes) => 13 02
   3.036522	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.036523	Unit = 00000000, UnitExp = 0
   3.036524	Exponent = 0
   3.036525	hid_lookup_path: 00840004 -> UPS
   3.036526	hid_lookup_path: 00840024 -> PowerSummary
   3.036528	hid_lookup_path: 0084005a -> AudibleAlarmControl
   3.036529	Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, ReportID: 0x13, Offset: 0, Size: 8, Value: 2
   3.036530	Entering libusb_get_report
   3.039518	Report[get]: (5 bytes) => 09 ff ff ff ff
   3.039521	PhyMax = 0, PhyMin = 0, LogMax = 2147483647, LogMin = -1
   3.039522	Unit = 00001001, UnitExp = 0
   3.039523	Exponent = 0
   3.039525	hid_lookup_path: 00840004 -> UPS
   3.039526	hid_lookup_path: 00840024 -> PowerSummary
   3.039527	hid_lookup_path: 00840057 -> DelayBeforeShutdown
   3.039529	Path: UPS.PowerSummary.DelayBeforeShutdown, Type: Feature, ReportID: 0x09, Offset: 0, Size: 32, Value: 0
   3.039530	Entering libusb_get_report
   3.042519	Report[get]: (5 bytes) => 0a ff ff ff ff
   3.042522	PhyMax = 0, PhyMin = 0, LogMax = 2147483647, LogMin = -1
   3.042523	Unit = 00001001, UnitExp = 0
   3.042524	Exponent = 0
   3.042526	hid_lookup_path: 00840004 -> UPS
   3.042527	hid_lookup_path: 00840024 -> PowerSummary
   3.042528	hid_lookup_path: 00840056 -> DelayBeforeStartup
   3.042529	Path: UPS.PowerSummary.DelayBeforeStartup, Type: Feature, ReportID: 0x0a, Offset: 0, Size: 32, Value: 0
   3.042530	Entering libusb_get_report
   3.045521	Report[get]: (6 bytes) => 10 05 01 03 02 04
   3.045523	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.045524	Unit = 00000000, UnitExp = 0
   3.045525	Exponent = 0
   3.045526	hid_lookup_path: 00840004 -> UPS
   3.045527	hid_lookup_path: 00840024 -> PowerSummary
   3.045529	hid_lookup_path: 00850089 -> iDeviceChemistry
   3.045530	Path: UPS.PowerSummary.iDeviceChemistry, Type: Feature, ReportID: 0x10, Offset: 0, Size: 8, Value: 5
   3.045532	Report[buf]: (6 bytes) => 10 05 01 03 02 04
   3.045533	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.045534	Unit = 00000000, UnitExp = 0
   3.045535	Exponent = 0
   3.045536	hid_lookup_path: 00840004 -> UPS
   3.045537	hid_lookup_path: 00840024 -> PowerSummary
   3.045538	hid_lookup_path: 008400fd -> iManufacturer
   3.045540	Path: UPS.PowerSummary.iManufacturer, Type: Feature, ReportID: 0x10, Offset: 8, Size: 8, Value: 1
   3.045541	Report[buf]: (6 bytes) => 10 05 01 03 02 04
   3.045542	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.045543	Unit = 00000000, UnitExp = 0
   3.045544	Exponent = 0
   3.045545	hid_lookup_path: 00840004 -> UPS
   3.045546	hid_lookup_path: 00840024 -> PowerSummary
   3.045547	hid_lookup_path: ffff00f0 -> iModel
   3.045548	Path: UPS.PowerSummary.iModel, Type: Feature, ReportID: 0x10, Offset: 16, Size: 8, Value: 3
   3.045550	Report[buf]: (6 bytes) => 10 05 01 03 02 04
   3.045551	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.045552	Unit = 00000000, UnitExp = 0
   3.045552	Exponent = 0
   3.045553	hid_lookup_path: 00840004 -> UPS
   3.045555	hid_lookup_path: 00840024 -> PowerSummary
   3.045556	hid_lookup_path: 008400fe -> iProduct
   3.045557	Path: UPS.PowerSummary.iProduct, Type: Feature, ReportID: 0x10, Offset: 24, Size: 8, Value: 2
   3.045558	Report[buf]: (6 bytes) => 10 05 01 03 02 04
   3.045559	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.045560	Unit = 00000000, UnitExp = 0
   3.045561	Exponent = 0
   3.045562	hid_lookup_path: 00840004 -> UPS
   3.045563	hid_lookup_path: 00840024 -> PowerSummary
   3.045565	hid_lookup_path: 008400ff -> iSerialNumber
   3.045566	Path: UPS.PowerSummary.iSerialNumber, Type: Feature, ReportID: 0x10, Offset: 32, Size: 8, Value: 4
   3.045567	Entering libusb_get_report
   3.048520	Report[get]: (2 bytes) => e2 04
   3.048524	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.048525	Unit = 00000000, UnitExp = 0
   3.048526	Exponent = 0
   3.048528	hid_lookup_path: 00840004 -> UPS
   3.048529	hid_lookup_path: 00840024 -> PowerSummary
   3.048530	hid_lookup_path: ffff00e2 -> not found in lookup table
   3.048532	Path: UPS.PowerSummary.ffff00e2, Type: Feature, ReportID: 0xe2, Offset: 0, Size: 8, Value: 4
   3.048533	Entering libusb_get_report
   3.051519	Report[get]: (4 bytes) => 07 08 10 01
   3.051522	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.051523	Unit = 00000000, UnitExp = 0
   3.051524	Exponent = 0
   3.051525	hid_lookup_path: 00840004 -> UPS
   3.051526	hid_lookup_path: 00840024 -> PowerSummary
   3.051527	hid_lookup_path: 00840035 -> PercentLoad
   3.051529	Path: UPS.PowerSummary.PercentLoad, Type: Feature, ReportID: 0x07, Offset: 0, Size: 8, Value: 8
   3.051530	Entering libusb_get_report
   3.054520	Report[get]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.054523	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.054524	Unit = 00000000, UnitExp = 0
   3.054525	Exponent = 0
   3.054526	hid_lookup_path: 00840004 -> UPS
   3.054527	hid_lookup_path: 00840024 -> PowerSummary
   3.054528	hid_lookup_path: 00840002 -> PresentStatus
   3.054530	hid_lookup_path: 008500d0 -> ACPresent
   3.054531	Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 1
   3.054533	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.054534	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.054535	Unit = 00000000, UnitExp = 0
   3.054535	Exponent = 0
   3.054536	hid_lookup_path: 00840004 -> UPS
   3.054538	hid_lookup_path: 00840024 -> PowerSummary
   3.054539	hid_lookup_path: 00840002 -> PresentStatus
   3.054540	hid_lookup_path: 008500d0 -> ACPresent
   3.054541	Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Input, ReportID: 0x01, Offset: 0, Size: 8, Value: 1
   3.054543	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.054544	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.054545	Unit = 00000000, UnitExp = 0
   3.054546	Exponent = 0
   3.054547	hid_lookup_path: 00840004 -> UPS
   3.054548	hid_lookup_path: 00840024 -> PowerSummary
   3.054549	hid_lookup_path: 00840002 -> PresentStatus
   3.054550	hid_lookup_path: 00850042 -> BelowRemainingCapacityLimit
   3.054551	Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x01, Offset: 8, Size: 8, Value: 0
   3.054553	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.054554	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.054555	Unit = 00000000, UnitExp = 0
   3.054556	Exponent = 0
   3.054557	hid_lookup_path: 00840004 -> UPS
   3.054558	hid_lookup_path: 00840024 -> PowerSummary
   3.054559	hid_lookup_path: 00840002 -> PresentStatus
   3.054561	hid_lookup_path: 00850042 -> BelowRemainingCapacityLimit
   3.054562	Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Input, ReportID: 0x01, Offset: 8, Size: 8, Value: 0
   3.054563	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.054564	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.054565	Unit = 00000000, UnitExp = 0
   3.054566	Exponent = 0
   3.054567	hid_lookup_path: 00840004 -> UPS
   3.054568	hid_lookup_path: 00840024 -> PowerSummary
   3.054570	hid_lookup_path: 00840002 -> PresentStatus
   3.054571	hid_lookup_path: 00850044 -> Charging
   3.054572	Path: UPS.PowerSummary.PresentStatus.Charging, Type: Feature, ReportID: 0x01, Offset: 16, Size: 8, Value: 1
   3.054574	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.054575	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.054576	Unit = 00000000, UnitExp = 0
   3.054577	Exponent = 0
   3.054578	hid_lookup_path: 00840004 -> UPS
   3.054579	hid_lookup_path: 00840024 -> PowerSummary
   3.054580	hid_lookup_path: 00840002 -> PresentStatus
   3.054581	hid_lookup_path: 00850044 -> Charging
   3.054582	Path: UPS.PowerSummary.PresentStatus.Charging, Type: Input, ReportID: 0x01, Offset: 16, Size: 8, Value: 1
   3.054584	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.054585	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.054586	Unit = 00000000, UnitExp = 0
   3.054587	Exponent = 0
   3.054588	hid_lookup_path: 00840004 -> UPS
   3.054589	hid_lookup_path: 00840024 -> PowerSummary
   3.054590	hid_lookup_path: 00840002 -> PresentStatus
   3.054591	hid_lookup_path: 00850045 -> Discharging
   3.054593	Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Feature, ReportID: 0x01, Offset: 24, Size: 8, Value: 0
   3.054594	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.054595	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.054596	Unit = 00000000, UnitExp = 0
   3.054597	Exponent = 0
   3.054598	hid_lookup_path: 00840004 -> UPS
   3.054599	hid_lookup_path: 00840024 -> PowerSummary
   3.054600	hid_lookup_path: 00840002 -> PresentStatus
   3.054601	hid_lookup_path: 00850045 -> Discharging
   3.054603	Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Input, ReportID: 0x01, Offset: 24, Size: 8, Value: 0
   3.054604	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.054605	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.054606	Unit = 00000000, UnitExp = 0
   3.054607	Exponent = 0
   3.054608	hid_lookup_path: 00840004 -> UPS
   3.054609	hid_lookup_path: 00840024 -> PowerSummary
   3.054610	hid_lookup_path: 00840002 -> PresentStatus
   3.054611	hid_lookup_path: 00840061 -> Good
   3.054613	Path: UPS.PowerSummary.PresentStatus.Good, Type: Feature, ReportID: 0x01, Offset: 32, Size: 8, Value: 1
   3.054614	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.054615	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.054616	Unit = 00000000, UnitExp = 0
   3.054617	Exponent = 0
   3.054618	hid_lookup_path: 00840004 -> UPS
   3.054619	hid_lookup_path: 00840024 -> PowerSummary
   3.054620	hid_lookup_path: 00840002 -> PresentStatus
   3.054621	hid_lookup_path: 00840061 -> Good
   3.054622	Path: UPS.PowerSummary.PresentStatus.Good, Type: Input, ReportID: 0x01, Offset: 32, Size: 8, Value: 1
   3.054624	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.054625	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.054626	Unit = 00000000, UnitExp = 0
   3.054627	Exponent = 0
   3.054628	hid_lookup_path: 00840004 -> UPS
   3.054629	hid_lookup_path: 00840024 -> PowerSummary
   3.054630	hid_lookup_path: 00840002 -> PresentStatus
   3.054631	hid_lookup_path: 00840062 -> InternalFailure
   3.054632	Path: UPS.PowerSummary.PresentStatus.InternalFailure, Type: Feature, ReportID: 0x01, Offset: 40, Size: 8, Value: 0
   3.054634	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.054635	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.054636	Unit = 00000000, UnitExp = 0
   3.054637	Exponent = 0
   3.054638	hid_lookup_path: 00840004 -> UPS
   3.054639	hid_lookup_path: 00840024 -> PowerSummary
   3.054640	hid_lookup_path: 00840002 -> PresentStatus
   3.054641	hid_lookup_path: 00840062 -> InternalFailure
   3.054642	Path: UPS.PowerSummary.PresentStatus.InternalFailure, Type: Input, ReportID: 0x01, Offset: 40, Size: 8, Value: 0
   3.054644	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.054645	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.054646	Unit = 00000000, UnitExp = 0
   3.054646	Exponent = 0
   3.054648	hid_lookup_path: 00840004 -> UPS
   3.054649	hid_lookup_path: 00840024 -> PowerSummary
   3.054650	hid_lookup_path: 00840002 -> PresentStatus
   3.054651	hid_lookup_path: 00840065 -> Overload
   3.054652	Path: UPS.PowerSummary.PresentStatus.Overload, Type: Feature, ReportID: 0x01, Offset: 48, Size: 8, Value: 0
   3.054654	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.054655	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.054656	Unit = 00000000, UnitExp = 0
   3.054656	Exponent = 0
   3.054658	hid_lookup_path: 00840004 -> UPS
   3.054659	hid_lookup_path: 00840024 -> PowerSummary
   3.054660	hid_lookup_path: 00840002 -> PresentStatus
   3.054661	hid_lookup_path: 00840065 -> Overload
   3.054662	Path: UPS.PowerSummary.PresentStatus.Overload, Type: Input, ReportID: 0x01, Offset: 48, Size: 8, Value: 0
   3.054663	Entering libusb_get_report
   3.057520	Report[get]: (5 bytes) => 0b 64 01 64 02
   3.057524	PhyMax = 0, PhyMin = 0, LogMax = 100, LogMin = 0
   3.057525	Unit = 00000000, UnitExp = 0
   3.057526	Exponent = 0
   3.057527	hid_lookup_path: 00840004 -> UPS
   3.057529	hid_lookup_path: 00840024 -> PowerSummary
   3.057530	hid_lookup_path: 00850083 -> DesignCapacity
   3.057532	Path: UPS.PowerSummary.DesignCapacity, Type: Feature, ReportID: 0x0b, Offset: 0, Size: 8, Value: 100
   3.057534	Report[buf]: (5 bytes) => 0b 64 01 64 02
   3.057535	PhyMax = 0, PhyMin = 0, LogMax = 100, LogMin = 0
   3.057536	Unit = 00000000, UnitExp = 0
   3.057537	Exponent = 0
   3.057538	hid_lookup_path: 00840004 -> UPS
   3.057539	hid_lookup_path: 00840024 -> PowerSummary
   3.057540	hid_lookup_path: 0085008d -> CapacityGranularity1
   3.057542	Path: UPS.PowerSummary.CapacityGranularity1, Type: Feature, ReportID: 0x0b, Offset: 8, Size: 8, Value: 1
   3.057543	Report[buf]: (5 bytes) => 0b 64 01 64 02
   3.057544	PhyMax = 0, PhyMin = 0, LogMax = 100, LogMin = 0
   3.057545	Unit = 00000000, UnitExp = 0
   3.057546	Exponent = 0
   3.057547	hid_lookup_path: 00840004 -> UPS
   3.057548	hid_lookup_path: 00840024 -> PowerSummary
   3.057550	hid_lookup_path: 00850067 -> FullChargeCapacity
   3.057552	Path: UPS.PowerSummary.FullChargeCapacity, Type: Feature, ReportID: 0x0b, Offset: 16, Size: 8, Value: 100
   3.057553	Report[buf]: (5 bytes) => 0b 64 01 64 02
   3.057554	PhyMax = 0, PhyMin = 0, LogMax = 100, LogMin = 0
   3.057555	Unit = 00000000, UnitExp = 0
   3.057556	Exponent = 0
   3.057557	hid_lookup_path: 00840004 -> UPS
   3.057558	hid_lookup_path: 00840024 -> PowerSummary
   3.057559	hid_lookup_path: 0085002c -> CapacityMode
   3.057561	Path: UPS.PowerSummary.CapacityMode, Type: Feature, ReportID: 0x0b, Offset: 24, Size: 8, Value: 2
   3.057562	Entering libusb_get_report
   3.060520	Report[get]: (4 bytes) => 06 64 7d 14
   3.060523	PhyMax = 0, PhyMin = 0, LogMax = 100, LogMin = 0
   3.060524	Unit = 00000000, UnitExp = 0
   3.060525	Exponent = 0
   3.060526	hid_lookup_path: 00840004 -> UPS
   3.060527	hid_lookup_path: 00840024 -> PowerSummary
   3.060528	hid_lookup_path: 00850066 -> RemainingCapacity
   3.060530	Path: UPS.PowerSummary.RemainingCapacity, Type: Feature, ReportID: 0x06, Offset: 0, Size: 8, Value: 100
   3.060531	Report[buf]: (4 bytes) => 06 64 7d 14
   3.060533	PhyMax = 0, PhyMin = 0, LogMax = 100, LogMin = 0
   3.060533	Unit = 00000000, UnitExp = 0
   3.060534	Exponent = 0
   3.060535	hid_lookup_path: 00840004 -> UPS
   3.060536	hid_lookup_path: 00840024 -> PowerSummary
   3.060538	hid_lookup_path: 00850066 -> RemainingCapacity
   3.060539	Path: UPS.PowerSummary.RemainingCapacity, Type: Input, ReportID: 0x06, Offset: 0, Size: 8, Value: 100
   3.060540	Report[buf]: (4 bytes) => 06 64 7d 14
   3.060541	PhyMax = 0, PhyMin = 0, LogMax = 32767, LogMin = 0
   3.060542	Unit = 00001001, UnitExp = 0
   3.060543	Exponent = 0
   3.060544	hid_lookup_path: 00840004 -> UPS
   3.060546	hid_lookup_path: 00840024 -> PowerSummary
   3.060547	hid_lookup_path: 00850068 -> RunTimeToEmpty
   3.060548	Path: UPS.PowerSummary.RunTimeToEmpty, Type: Feature, ReportID: 0x06, Offset: 8, Size: 16, Value: 5245
   3.060550	Report[buf]: (4 bytes) => 06 64 7d 14
   3.060551	PhyMax = 0, PhyMin = 0, LogMax = 32767, LogMin = 0
   3.060552	Unit = 00001001, UnitExp = 0
   3.060552	Exponent = 0
   3.060554	hid_lookup_path: 00840004 -> UPS
   3.060555	hid_lookup_path: 00840024 -> PowerSummary
   3.060556	hid_lookup_path: 00850068 -> RunTimeToEmpty
   3.060557	Path: UPS.PowerSummary.RunTimeToEmpty, Type: Input, ReportID: 0x06, Offset: 8, Size: 16, Value: 5245
   3.060559	Report[buf]: (4 bytes) => 07 08 10 01
   3.060560	PhyMax = 0, PhyMin = 0, LogMax = 32767, LogMin = 0
   3.060561	Unit = 00f0d121, UnitExp = 6
   3.060562	Exponent = -1
   3.060563	hid_lookup_path: 00840004 -> UPS
   3.060564	hid_lookup_path: 00840024 -> PowerSummary
   3.060565	hid_lookup_path: 00840030 -> Voltage
   3.060567	Path: UPS.PowerSummary.Voltage, Type: Feature, ReportID: 0x07, Offset: 8, Size: 16, Value: 27.2
   3.060572	hid_lookup_usage: UPS -> 00840004
   3.060575	hid_lookup_usage: PowerSummary -> 00840024
   3.060579	hid_lookup_usage: iModel -> ffff00f0
   3.060580	string_to_path: depth = 3
   3.060582	Report[buf]: (6 bytes) => 10 05 01 03 02 04
   3.060583	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.060584	Unit = 00000000, UnitExp = 0
   3.060585	Exponent = 0
   3.068519	get_model_name(Offline UPS, HID UPS)
   3.068522	comparing with: ellipse 300
   3.068523	comparing with: ellipse 500
   3.068524	comparing with: ellipse 650
   3.068524	comparing with: ellipse 800
   3.068526	comparing with: ellipse 1200
   3.068526	comparing with: ellipse premium 500
   3.068527	comparing with: ellipse premium 650
   3.068528	comparing with: ellipse premium 800
   3.068529	comparing with: ellipse premium 1200
   3.068530	comparing with: Ellipse 600
   3.068531	comparing with: Ellipse 750
   3.068532	comparing with: Ellipse 1000
   3.068533	comparing with: Ellipse 1500
   3.068534	comparing with: Ellipse MAX 600
   3.068535	comparing with: Ellipse MAX 850
   3.068535	comparing with: Ellipse MAX 1100
   3.068536	comparing with: Ellipse MAX 1500
   3.068537	comparing with: Protection Center 420
   3.068538	comparing with: Protection Center 500
   3.068539	comparing with: Protection Center 675
   3.068540	comparing with: Protection Station 500
   3.068541	comparing with: Protection Station 650
   3.068542	comparing with: Protection Station 800
   3.068543	comparing with: Ellipse ECO 650
   3.068543	comparing with: Ellipse ECO 800
   3.068544	comparing with: Ellipse ECO 1200
   3.068545	comparing with: Ellipse ECO 1600
   3.068546	comparing with: 3S 450
   3.068547	comparing with: 3S 550
   3.068548	comparing with: 3S 700
   3.068549	comparing with: 3S 750
   3.068550	comparing with: Pulsar Evolution 500
   3.068550	comparing with: Pulsar Evolution 800
   3.068551	comparing with: Pulsar Evolution 1100
   3.068552	comparing with: Pulsar Evolution 1500
   3.068553	comparing with: Pulsar Evolution 2200
   3.068554	comparing with: Pulsar Evolution 3000
   3.068555	comparing with: Pulsar Evolution 3000 XL
   3.068556	comparing with: Evolution 650
   3.068557	comparing with: Evolution 850
   3.068558	comparing with: Evolution 1150
   3.068559	comparing with: Evolution S 1250
   3.068560	comparing with: Evolution 1550
   3.068560	comparing with: Evolution S 1750
   3.068561	comparing with: Evolution 2000
   3.068562	comparing with: Evolution S 2500
   3.068563	comparing with: Evolution S 3000
   3.068564	comparing with: 5P 650
   3.068565	comparing with: 5P 850
   3.068566	comparing with: 5P 1150
   3.068567	comparing with: 5P 1550
   3.068568	comparing with: PULSAR M 2200
   3.068569	comparing with: PULSAR M 3000
   3.068569	comparing with: PULSAR M 3000 XL
   3.068570	comparing with: EX 2200
   3.068571	comparing with: EX 3000
   3.068572	comparing with: EX 3000 XL
   3.068573	comparing with: Pulsar MX 4000 RT
   3.068574	comparing with: Pulsar MX 5000 RT
   3.068575	comparing with: Nova 500 AVR
   3.068576	comparing with: Nova 600 AVR
   3.068576	comparing with: Nova 625 AVR
   3.068577	comparing with: Nova 1100 AVR
   3.068578	comparing with: Nova 1250 AVR
   3.068579	comparing with: Pulsar EXtreme 700C
   3.068580	comparing with: Pulsar EXtreme 1000C
   3.068581	comparing with: Pulsar EXtreme 1500C
   3.068582	comparing with: Pulsar EXtreme 1500C CLA
   3.068583	comparing with: Pulsar EXtreme 2200C
   3.068583	comparing with: Pulsar EXtreme 3200C
   3.068584	comparing with: Pulsar EX 700 RT
   3.068585	comparing with: Pulsar EX 1000 RT
   3.068586	comparing with: Pulsar EX 1500 RT
   3.068587	comparing with: Pulsar EX 2200 RT
   3.068588	comparing with: Pulsar EX 3200 RT
   3.068589	comparing with: EX 5 RT 3:1
   3.068589	comparing with: EX 7 RT 3:1
   3.068590	comparing with: EX 11 RT 3:1
   3.068591	comparing with: EX 5 RT
   3.068592	comparing with: EX 7 RT
   3.068593	comparing with: EX 11 RT
   3.068594	comparing with: Galaxy 3000 10 kVA
   3.068595	comparing with: Galaxy 3000 15 kVA
   3.068596	comparing with: Galaxy 3000 20 kVA
   3.068597	comparing with: Galaxy 3000 30 kVA
   3.068600	send_to_all: SETINFO ups.mfr "PPC"
   3.068604	send_to_all: SETINFO ups.model "Offline UPS HID UPS"
   3.068606	send_to_all: SETINFO ups.serial "000000000   "
   3.068607	send_to_all: SETINFO ups.vendorid "06da"
   3.068608	send_to_all: SETINFO ups.productid "ffff"
   3.068610	Report descriptor retrieved (Reportlen = 495)
   3.068610	Found HID device
   3.068612	Detected a UPS: PPC/Offline UPS HID UPS
   3.068616	hid_lookup_usage: UPS -> 00840004
   3.068619	hid_lookup_usage: PowerSummary -> 00840024
   3.068621	hid_lookup_usage: Country -> ffff0095
   3.068622	string_to_path: depth = 3
   3.068625	hid_lookup_usage: UPS -> 00840004
   3.068628	hid_lookup_usage: PowerSummary -> 00840024
   3.068631	hid_lookup_usage: RemainingCapacity -> 00850066
   3.068632	string_to_path: depth = 3
   3.068634	Report[buf]: (4 bytes) => 06 64 7d 14
   3.068636	PhyMax = 0, PhyMin = 0, LogMax = 100, LogMin = 0
   3.068637	Unit = 00000000, UnitExp = 0
   3.068638	Exponent = 0
   3.068639	Path: UPS.PowerSummary.RemainingCapacity, Type: Feature, ReportID: 0x06, Offset: 0, Size: 8, Value: 100
   3.068641	send_to_all: SETINFO battery.charge "100"
   3.068644	hid_lookup_usage: UPS -> 00840004
   3.068646	hid_lookup_usage: PowerSummary -> 00840024
   3.068647	hid_lookup_usage: RemainingCapacityLimitSetting -> ffff004d
   3.068648	string_to_path: depth = 3
   3.068650	hid_lookup_usage: UPS -> 00840004
   3.068653	hid_lookup_usage: PowerSummary -> 00840024
   3.068655	hid_lookup_usage: RemainingCapacityLimit -> 00850029
   3.068656	string_to_path: depth = 3
   3.068659	hid_lookup_usage: UPS -> 00840004
   3.068661	hid_lookup_usage: PowerSummary -> 00840024
   3.068663	hid_lookup_usage: RestartLevel -> ffff005f
   3.068663	string_to_path: depth = 3
   3.068666	hid_lookup_usage: UPS -> 00840004
   3.068668	hid_lookup_usage: BatterySystem -> 00840010
   3.068670	hid_lookup_usage: Battery -> 00840012
   3.068675	hid_lookup_usage: DesignCapacity -> 00850083
   3.068675	string_to_path: depth = 4
   3.068678	hid_lookup_usage: UPS -> 00840004
   3.068680	hid_lookup_usage: PowerSummary -> 00840024
   3.068684	hid_lookup_usage: RunTimeToEmpty -> 00850068
   3.068685	string_to_path: depth = 3
   3.068686	Report[buf]: (4 bytes) => 06 64 7d 14
   3.068688	PhyMax = 0, PhyMin = 0, LogMax = 32767, LogMin = 0
   3.068689	Unit = 00001001, UnitExp = 0
   3.068689	Exponent = 0
   3.068691	Path: UPS.PowerSummary.RunTimeToEmpty, Type: Feature, ReportID: 0x06, Offset: 8, Size: 16, Value: 5245
   3.068693	send_to_all: SETINFO battery.runtime "5245"
   3.068695	hid_lookup_usage: UPS -> 00840004
   3.068697	hid_lookup_usage: PowerSummary -> 00840024
   3.068700	hid_lookup_usage: RemainingTimeLimit -> 0085002a
   3.068701	string_to_path: depth = 3
   3.068703	hid_lookup_usage: UPS -> 00840004
   3.068705	hid_lookup_usage: StatisticSystem -> ffff0004
   3.068707	hid_lookup_usage: Input -> 0084001a
   3.068711	hid_lookup_usage: [1] -> not found in lookup table
   3.068712	hid_lookup_usage: Statistic -> ffff0003
   3.068719	hid_lookup_usage: [1] -> not found in lookup table
   3.068724	hid_lookup_usage: Time -> ffff0097
   3.068725	string_to_path: depth = 7
   3.068727	hid_lookup_usage: UPS -> 00840004
   3.068730	hid_lookup_usage: PowerSummary -> 00840024
   3.068733	hid_lookup_usage: RemainingTimeLimit -> 0085002a
   3.068733	string_to_path: depth = 3
   3.068736	hid_lookup_usage: UPS -> 00840004
   3.068738	hid_lookup_usage: BatterySystem -> 00840010
   3.068740	hid_lookup_usage: Battery -> 00840012
   3.068743	hid_lookup_usage: Temperature -> 00840036
   3.068744	string_to_path: depth = 4
   3.068746	hid_lookup_usage: UPS -> 00840004
   3.068748	hid_lookup_usage: PowerSummary -> 00840024
   3.068752	hid_lookup_usage: iDeviceChemistry -> 00850089
   3.068753	string_to_path: depth = 3
   3.068754	Report[buf]: (6 bytes) => 10 05 01 03 02 04
   3.068755	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.068756	Unit = 00000000, UnitExp = 0
   3.068757	Exponent = 0
   3.068759	Path: UPS.PowerSummary.iDeviceChemistry, Type: Feature, ReportID: 0x10, Offset: 0, Size: 8, Value: 5
   3.075521	send_to_all: SETINFO battery.type "PbAc"
   3.075527	hid_lookup_usage: UPS -> 00840004
   3.075530	hid_lookup_usage: BatterySystem -> 00840010
   3.075532	hid_lookup_usage: Voltage -> 00840030
   3.075533	string_to_path: depth = 3
   3.075536	hid_lookup_usage: UPS -> 00840004
   3.075538	hid_lookup_usage: PowerSummary -> 00840024
   3.075541	hid_lookup_usage: Voltage -> 00840030
   3.075542	string_to_path: depth = 3
   3.075544	Report[buf]: (4 bytes) => 07 08 10 01
   3.075545	PhyMax = 0, PhyMin = 0, LogMax = 32767, LogMin = 0
   3.075546	Unit = 00f0d121, UnitExp = 6
   3.075547	Exponent = -1
   3.075549	Path: UPS.PowerSummary.Voltage, Type: Feature, ReportID: 0x07, Offset: 8, Size: 16, Value: 27.2
   3.075551	Lookup [27.2] failed for [battery.voltage]
   3.075553	hid_lookup_usage: UPS -> 00840004
   3.075555	hid_lookup_usage: BatterySystem -> 00840010
   3.075557	hid_lookup_usage: ConfigVoltage -> 00840040
   3.075558	string_to_path: depth = 3
   3.075561	hid_lookup_usage: UPS -> 00840004
   3.075563	hid_lookup_usage: PowerSummary -> 00840024
   3.075565	hid_lookup_usage: ConfigVoltage -> 00840040
   3.075566	string_to_path: depth = 3
   3.075568	hid_lookup_usage: UPS -> 00840004
   3.075570	hid_lookup_usage: BatterySystem -> 00840010
   3.075572	hid_lookup_usage: Battery -> 00840012
   3.075574	hid_lookup_usage: DeepDischargeProtection -> ffff0049
   3.075575	string_to_path: depth = 4
   3.075577	hid_lookup_usage: UPS -> 00840004
   3.075579	hid_lookup_usage: PowerConverter -> 00840016
   3.075582	hid_lookup_usage: Input -> 0084001a
   3.075586	hid_lookup_usage: [3] -> not found in lookup table
   3.075588	hid_lookup_usage: EnergySaving -> ffff0046
   3.075588	string_to_path: depth = 5
   3.075591	hid_lookup_usage: UPS -> 00840004
   3.075593	hid_lookup_usage: PowerConverter -> 00840016
   3.075595	hid_lookup_usage: Input -> 0084001a
   3.075598	hid_lookup_usage: [3] -> not found in lookup table
   3.075601	hid_lookup_usage: ConfigPercentLoad -> 00840045
   3.075602	string_to_path: depth = 5
   3.075605	hid_lookup_usage: UPS -> 00840004
   3.075607	hid_lookup_usage: PowerConverter -> 00840016
   3.075609	hid_lookup_usage: Input -> 0084001a
   3.075612	hid_lookup_usage: [3] -> not found in lookup table
   3.075614	hid_lookup_usage: EnergySaving -> ffff0046
   3.075616	hid_lookup_usage: ShutdownTimer -> ffff005d
   3.075617	string_to_path: depth = 6
   3.075619	hid_lookup_usage: UPS -> 00840004
   3.075621	hid_lookup_usage: PowerConverter -> 00840016
   3.075623	hid_lookup_usage: Input -> 0084001a
   3.075626	hid_lookup_usage: [3] -> not found in lookup table
   3.075628	hid_lookup_usage: ShutdownTimer -> ffff005d
   3.075629	string_to_path: depth = 5
   3.075631	hid_lookup_usage: UPS -> 00840004
   3.075633	hid_lookup_usage: PowerConverter -> 00840016
   3.075635	hid_lookup_usage: Input -> 0084001a
   3.075638	hid_lookup_usage: [3] -> not found in lookup table
   3.075641	hid_lookup_usage: ConfigActivePower -> 00840044
   3.075642	string_to_path: depth = 5
   3.075644	hid_lookup_usage: UPS -> 00840004
   3.075646	hid_lookup_usage: BatterySystem -> 00840010
   3.075649	hid_lookup_usage: Charger -> 00840014
   3.075650	hid_lookup_usage: ABMEnable -> ffff0087
   3.075652	string_to_path: depth = 4
   3.075654	hid_lookup_usage: UPS -> 00840004
   3.075656	hid_lookup_usage: BatterySystem -> 00840010
   3.075658	hid_lookup_usage: Charger -> 00840014
   3.075660	hid_lookup_usage: Mode -> ffff0094
   3.075661	string_to_path: depth = 4
   3.075663	hid_lookup_usage: UPS -> 00840004
   3.075665	hid_lookup_usage: PowerConverter -> 00840016
   3.075668	hid_lookup_usage: Output -> 0084001c
   3.075669	hid_lookup_usage: Efficiency -> ffff0086
   3.075670	string_to_path: depth = 4
   3.075672	hid_lookup_usage: UPS -> 00840004
   3.075675	hid_lookup_usage: PowerSummary -> 00840024
   3.075677	hid_lookup_usage: iVersion -> ffff00f1
   3.075678	string_to_path: depth = 3
   3.075683	hid_lookup_usage: UPS -> 00840004
   3.075685	hid_lookup_usage: PowerSummary -> 00840024
   3.075687	hid_lookup_usage: PercentLoad -> 00840035
   3.075688	string_to_path: depth = 3
   3.075690	Report[buf]: (4 bytes) => 07 08 10 01
   3.075691	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.075692	Unit = 00000000, UnitExp = 0
   3.075693	Exponent = 0
   3.075695	Path: UPS.PowerSummary.PercentLoad, Type: Feature, ReportID: 0x07, Offset: 0, Size: 8, Value: 8
   3.075697	send_to_all: SETINFO ups.load "8"
   3.075699	hid_lookup_usage: UPS -> 00840004
   3.075701	hid_lookup_usage: Flow -> 0084001e
   3.075705	hid_lookup_usage: [4] -> not found in lookup table
   3.075707	hid_lookup_usage: ConfigPercentLoad -> 00840045
   3.075708	string_to_path: depth = 4
   3.075711	hid_lookup_usage: UPS -> 00840004
   3.075713	hid_lookup_usage: PowerSummary -> 00840024
   3.075715	hid_lookup_usage: DelayBeforeStartup -> 00840056
   3.075716	string_to_path: depth = 3
   3.075718	send_to_all: SETINFO ups.delay.start "30"
   3.075720	send_to_all: SETFLAGS ups.delay.start RW STRING
   3.075721	send_to_all: SETAUX ups.delay.start 10
   3.075723	hid_lookup_usage: UPS -> 00840004
   3.075725	hid_lookup_usage: PowerSummary -> 00840024
   3.075728	hid_lookup_usage: DelayBeforeShutdown -> 00840057
   3.075729	string_to_path: depth = 3
   3.075730	send_to_all: SETINFO ups.delay.shutdown "20"
   3.075732	send_to_all: SETFLAGS ups.delay.shutdown RW STRING
   3.075733	send_to_all: SETAUX ups.delay.shutdown 10
   3.075735	hid_lookup_usage: UPS -> 00840004
   3.075737	hid_lookup_usage: PowerSummary -> 00840024
   3.075740	hid_lookup_usage: DelayBeforeStartup -> 00840056
   3.075741	string_to_path: depth = 3
   3.075742	Report[buf]: (5 bytes) => 0a ff ff ff ff
   3.075744	PhyMax = 0, PhyMin = 0, LogMax = 2147483647, LogMin = -1
   3.075745	Unit = 00001001, UnitExp = 0
   3.075746	Exponent = 0
   3.075747	Path: UPS.PowerSummary.DelayBeforeStartup, Type: Feature, ReportID: 0x0a, Offset: 0, Size: 32, Value: 0
   3.075748	send_to_all: SETINFO ups.timer.start "0"
   3.075751	hid_lookup_usage: UPS -> 00840004
   3.075753	hid_lookup_usage: PowerSummary -> 00840024
   3.075755	hid_lookup_usage: DelayBeforeShutdown -> 00840057
   3.075756	string_to_path: depth = 3
   3.075758	Report[buf]: (5 bytes) => 09 ff ff ff ff
   3.075759	PhyMax = 0, PhyMin = 0, LogMax = 2147483647, LogMin = -1
   3.075760	Unit = 00001001, UnitExp = 0
   3.075761	Exponent = 0
   3.075762	Path: UPS.PowerSummary.DelayBeforeShutdown, Type: Feature, ReportID: 0x09, Offset: 0, Size: 32, Value: 0
   3.075763	send_to_all: SETINFO ups.timer.shutdown "0"
   3.075766	hid_lookup_usage: UPS -> 00840004
   3.075768	hid_lookup_usage: PowerSummary -> 00840024
   3.075770	hid_lookup_usage: DelayBeforeReboot -> 00840055
   3.075771	string_to_path: depth = 3
   3.075773	hid_lookup_usage: UPS -> 00840004
   3.075775	hid_lookup_usage: BatterySystem -> 00840010
   3.075778	hid_lookup_usage: Battery -> 00840012
   3.075780	hid_lookup_usage: Test -> 00840058
   3.075781	string_to_path: depth = 4
   3.075783	Report[buf]: (2 bytes) => 24 06
   3.075784	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.075785	Unit = 00000000, UnitExp = 0
   3.075786	Exponent = 0
   3.075787	Path: UPS.BatterySystem.Battery.Test, Type: Feature, ReportID: 0x24, Offset: 0, Size: 8, Value: 6
   3.075788	hu_find_infoval: found No test initiated (value: 6)
   3.075790	send_to_all: SETINFO ups.test.result "No test initiated"
   3.075792	hid_lookup_usage: UPS -> 00840004
   3.075794	hid_lookup_usage: BatterySystem -> 00840010
   3.075796	hid_lookup_usage: Battery -> 00840012
   3.075797	hid_lookup_usage: TestPeriod -> ffff0045
   3.075798	string_to_path: depth = 4
   3.075801	hid_lookup_usage: UPS -> 00840004
   3.075803	hid_lookup_usage: PowerSummary -> 00840024
   3.075805	hid_lookup_usage: AudibleAlarmControl -> 0084005a
   3.075806	string_to_path: depth = 3
   3.075808	Report[buf]: (2 bytes) => 13 02
   3.075809	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.075810	Unit = 00000000, UnitExp = 0
   3.075810	Exponent = 0
   3.075812	Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, ReportID: 0x13, Offset: 0, Size: 8, Value: 2
   3.075813	hu_find_infoval: found enabled (value: 2)
   3.075814	send_to_all: SETINFO ups.beeper.status "enabled"
   3.075817	hid_lookup_usage: UPS -> 00840004
   3.075819	hid_lookup_usage: PowerSummary -> 00840024
   3.075821	hid_lookup_usage: Temperature -> 00840036
   3.075823	string_to_path: depth = 3
   3.075826	hid_lookup_usage: UPS -> 00840004
   3.075830	hid_lookup_usage: PowerConverter -> 00840016
   3.075834	hid_lookup_usage: Output -> 0084001c
   3.075839	hid_lookup_usage: ApparentPower -> 00840033
   3.075841	string_to_path: depth = 4
   3.075845	hid_lookup_usage: UPS -> 00840004
   3.075847	hid_lookup_usage: PowerConverter -> 00840016
   3.075849	hid_lookup_usage: Output -> 0084001c
   3.075850	hid_lookup_usage: Phase -> ffff0010
   3.075854	hid_lookup_usage: [1] -> not found in lookup table
   3.075859	hid_lookup_usage: ApparentPower -> 00840033
   3.075860	string_to_path: depth = 6
   3.075862	hid_lookup_usage: UPS -> 00840004
   3.075864	hid_lookup_usage: PowerConverter -> 00840016
   3.075867	hid_lookup_usage: Output -> 0084001c
   3.075868	hid_lookup_usage: Phase -> ffff0010
   3.075871	hid_lookup_usage: [2] -> not found in lookup table
   3.075874	hid_lookup_usage: ApparentPower -> 00840033
   3.075875	string_to_path: depth = 6
   3.075878	hid_lookup_usage: UPS -> 00840004
   3.075880	hid_lookup_usage: PowerConverter -> 00840016
   3.075882	hid_lookup_usage: Output -> 0084001c
   3.075883	hid_lookup_usage: Phase -> ffff0010
   3.075886	hid_lookup_usage: [3] -> not found in lookup table
   3.075889	hid_lookup_usage: ApparentPower -> 00840033
   3.075890	string_to_path: depth = 6
   3.075893	hid_lookup_usage: UPS -> 00840004
   3.075895	hid_lookup_usage: Flow -> 0084001e
   3.075898	hid_lookup_usage: [4] -> not found in lookup table
   3.075901	hid_lookup_usage: ConfigApparentPower -> 00840043
   3.075902	string_to_path: depth = 4
   3.075903	Report[buf]: (3 bytes) => 74 05 00
   3.075905	PhyMax = 0, PhyMin = 0, LogMax = 65535, LogMin = 0
   3.075905	Unit = 0000d121, UnitExp = 7
   3.075906	Exponent = 0
   3.075908	Path: UPS.Flow.[4].ConfigApparentPower, Type: Feature, ReportID: 0x74, Offset: 0, Size: 16, Value: 5
   3.075909	send_to_all: SETINFO ups.power.nominal "5"
   3.075912	hid_lookup_usage: UPS -> 00840004
   3.075914	hid_lookup_usage: PowerConverter -> 00840016
   3.075916	hid_lookup_usage: Output -> 0084001c
   3.075918	hid_lookup_usage: ActivePower -> 00840034
   3.075919	string_to_path: depth = 4
   3.075922	hid_lookup_usage: UPS -> 00840004
   3.075924	hid_lookup_usage: PowerConverter -> 00840016
   3.075926	hid_lookup_usage: Output -> 0084001c
   3.075927	hid_lookup_usage: Phase -> ffff0010
   3.075930	hid_lookup_usage: [1] -> not found in lookup table
   3.075933	hid_lookup_usage: ActivePower -> 00840034
   3.075934	string_to_path: depth = 6
   3.075936	hid_lookup_usage: UPS -> 00840004
   3.075938	hid_lookup_usage: PowerConverter -> 00840016
   3.075941	hid_lookup_usage: Output -> 0084001c
   3.075942	hid_lookup_usage: Phase -> ffff0010
   3.075945	hid_lookup_usage: [2] -> not found in lookup table
   3.075948	hid_lookup_usage: ActivePower -> 00840034
   3.075949	string_to_path: depth = 6
   3.075951	hid_lookup_usage: UPS -> 00840004
   3.075953	hid_lookup_usage: PowerConverter -> 00840016
   3.075955	hid_lookup_usage: Output -> 0084001c
   3.075956	hid_lookup_usage: Phase -> ffff0010
   3.075960	hid_lookup_usage: [3] -> not found in lookup table
   3.075962	hid_lookup_usage: ActivePower -> 00840034
   3.075963	string_to_path: depth = 6
   3.075966	hid_lookup_usage: UPS -> 00840004
   3.075968	hid_lookup_usage: Flow -> 0084001e
   3.075971	hid_lookup_usage: [4] -> not found in lookup table
   3.075974	hid_lookup_usage: ConfigActivePower -> 00840044
   3.075975	string_to_path: depth = 4
   3.075977	hid_lookup_usage: UPS -> 00840004
   3.075979	hid_lookup_usage: PowerConverter -> 00840016
   3.075981	hid_lookup_usage: Input -> 0084001a
   3.075984	hid_lookup_usage: [1] -> not found in lookup table
   3.075986	hid_lookup_usage: AutomaticRestart -> ffff0043
   3.075987	string_to_path: depth = 5
   3.075989	hid_lookup_usage: UPS -> 00840004
   3.075992	hid_lookup_usage: PowerConverter -> 00840016
   3.075994	hid_lookup_usage: Input -> 0084001a
   3.075997	hid_lookup_usage: [3] -> not found in lookup table
   3.075998	hid_lookup_usage: StartOnBattery -> ffff0047
   3.075999	string_to_path: depth = 5
   3.076002	hid_lookup_usage: UPS -> 00840004
   3.076004	hid_lookup_usage: PowerConverter -> 00840016
   3.076006	hid_lookup_usage: Output -> 0084001c
   3.076007	hid_lookup_usage: ForcedReboot -> ffff0044
   3.076008	string_to_path: depth = 4
   3.076010	hid_lookup_usage: UPS -> 00840004
   3.076012	hid_lookup_usage: PowerSummary -> 00840024
   3.076014	hid_lookup_usage: PresentStatus -> 00840002
   3.076018	hid_lookup_usage: Switchable -> 0084006c
   3.076019	string_to_path: depth = 4
   3.076021	hid_lookup_usage: UPS -> 00840004
   3.076024	hid_lookup_usage: PowerSummary -> 00840024
   3.076026	hid_lookup_usage: Time -> ffff0097
   3.076027	string_to_path: depth = 3
   3.076029	hid_lookup_usage: UPS -> 00840004
   3.076031	hid_lookup_usage: PowerSummary -> 00840024
   3.076033	hid_lookup_usage: Time -> ffff0097
   3.076034	string_to_path: depth = 3
   3.076036	hid_lookup_usage: UPS -> 00840004
   3.076038	hid_lookup_usage: PowerConverter -> 00840016
   3.076039	hid_lookup_usage: ConverterType -> ffff0041
   3.076040	string_to_path: depth = 3
   3.076042	Report[buf]: (2 bytes) => 4a 01
   3.076043	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.076044	Unit = 00000000, UnitExp = 0
   3.076044	Exponent = 0
   3.076046	Path: UPS.PowerConverter.ConverterType, Type: Feature, ReportID: 0x4a, Offset: 0, Size: 8, Value: 1
   3.076047	hu_find_infoval: found offline / line interactive (value: 1)
   3.076048	send_to_all: SETINFO ups.type "offline / line interactive"
   3.076051	hid_lookup_usage: UPS -> 00840004
   3.076053	hid_lookup_usage: PowerSummary -> 00840024
   3.076055	hid_lookup_usage: PresentStatus -> 00840002
   3.076059	hid_lookup_usage: ACPresent -> 008500d0
   3.076060	string_to_path: depth = 4
   3.076062	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.076063	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.076064	Unit = 00000000, UnitExp = 0
   3.076065	Exponent = 0
   3.076066	Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 1
   3.076067	hu_find_infoval: found online (value: 1)
   3.076068	process_boolean_info: online
   3.076070	hid_lookup_usage: UPS -> 00840004
   3.076073	hid_lookup_usage: PowerConverter -> 00840016
   3.076075	hid_lookup_usage: Input -> 0084001a
   3.076078	hid_lookup_usage: [3] -> not found in lookup table
   3.076081	hid_lookup_usage: PresentStatus -> 00840002
   3.076086	hid_lookup_usage: Used -> 0084006d
   3.076087	string_to_path: depth = 6
   3.076090	hid_lookup_usage: UPS -> 00840004
   3.076092	hid_lookup_usage: PowerConverter -> 00840016
   3.076094	hid_lookup_usage: Input -> 0084001a
   3.076097	hid_lookup_usage: [1] -> not found in lookup table
   3.076099	hid_lookup_usage: PresentStatus -> 00840002
   3.076103	hid_lookup_usage: Used -> 0084006d
   3.076104	string_to_path: depth = 6
   3.076107	hid_lookup_usage: UPS -> 00840004
   3.076109	hid_lookup_usage: PowerSummary -> 00840024
   3.076111	hid_lookup_usage: PresentStatus -> 00840002
   3.076114	hid_lookup_usage: Discharging -> 00850045
   3.076115	string_to_path: depth = 4
   3.076117	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.076118	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.076119	Unit = 00000000, UnitExp = 0
   3.076120	Exponent = 0
   3.076121	Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Feature, ReportID: 0x01, Offset: 24, Size: 8, Value: 0
   3.076123	process_boolean_info: !dischrg
   3.076125	hid_lookup_usage: UPS -> 00840004
   3.076127	hid_lookup_usage: PowerSummary -> 00840024
   3.076129	hid_lookup_usage: PresentStatus -> 00840002
   3.076133	hid_lookup_usage: Charging -> 00850044
   3.076134	string_to_path: depth = 4
   3.076135	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.076136	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.076137	Unit = 00000000, UnitExp = 0
   3.076138	Exponent = 0
   3.076139	Path: UPS.PowerSummary.PresentStatus.Charging, Type: Feature, ReportID: 0x01, Offset: 16, Size: 8, Value: 1
   3.076140	process_boolean_info: !chrg
   3.076143	hid_lookup_usage: UPS -> 00840004
   3.076145	hid_lookup_usage: BatterySystem -> 00840010
   3.076147	hid_lookup_usage: Charger -> 00840014
   3.076149	hid_lookup_usage: Mode -> ffff0094
   3.076150	string_to_path: depth = 4
   3.076152	hid_lookup_usage: UPS -> 00840004
   3.076154	hid_lookup_usage: PowerSummary -> 00840024
   3.076156	hid_lookup_usage: PresentStatus -> 00840002
   3.076160	hid_lookup_usage: BelowRemainingCapacityLimit -> 00850042
   3.076161	string_to_path: depth = 4
   3.076163	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.076164	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.076165	Unit = 00000000, UnitExp = 0
   3.076165	Exponent = 0
   3.076167	Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x01, Offset: 8, Size: 8, Value: 0
   3.076168	hu_find_infoval: found !lowbatt (value: 0)
   3.076169	process_boolean_info: !lowbatt
   3.076171	hid_lookup_usage: UPS -> 00840004
   3.076173	hid_lookup_usage: PowerConverter -> 00840016
   3.076175	hid_lookup_usage: Output -> 0084001c
   3.076178	hid_lookup_usage: Overload -> 00840065
   3.076185	hid_lookup_usage: [1] -> not found in lookup table
   3.076189	hid_lookup_usage: PresentStatus -> 00840002
   3.076191	hid_lookup_usage: OverThreshold -> ffff007e
   3.076192	string_to_path: depth = 7
   3.076195	hid_lookup_usage: UPS -> 00840004
   3.076197	hid_lookup_usage: PowerConverter -> 00840016
   3.076199	hid_lookup_usage: Output -> 0084001c
   3.076201	hid_lookup_usage: Overload -> 00840065
   3.076207	hid_lookup_usage: [2] -> not found in lookup table
   3.076211	hid_lookup_usage: PresentStatus -> 00840002
   3.076213	hid_lookup_usage: OverThreshold -> ffff007e
   3.076214	string_to_path: depth = 7
   3.076216	hid_lookup_usage: UPS -> 00840004
   3.076219	hid_lookup_usage: PowerSummary -> 00840024
   3.076221	hid_lookup_usage: PresentStatus -> 00840002
   3.076224	hid_lookup_usage: Overload -> 00840065
   3.076225	string_to_path: depth = 4
   3.076226	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.076227	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.076228	Unit = 00000000, UnitExp = 0
   3.076229	Exponent = 0
   3.076231	Path: UPS.PowerSummary.PresentStatus.Overload, Type: Feature, ReportID: 0x01, Offset: 48, Size: 8, Value: 0
   3.076232	hu_find_infoval: found !overload (value: 0)
   3.076233	process_boolean_info: !overload
   3.076235	hid_lookup_usage: UPS -> 00840004
   3.076237	hid_lookup_usage: PowerSummary -> 00840024
   3.076239	hid_lookup_usage: PresentStatus -> 00840002
   3.076242	hid_lookup_usage: NeedReplacement -> 0085004b
   3.076243	string_to_path: depth = 4
   3.076245	hid_lookup_usage: UPS -> 00840004
   3.076246	hid_lookup_usage: LCMSystem -> ffff0018
   3.076248	hid_lookup_usage: LCMAlarm -> ffff001a
   3.076251	hid_lookup_usage: [2] -> not found in lookup table
   3.076254	hid_lookup_usage: PresentStatus -> 00840002
   3.076257	hid_lookup_usage: TimerExpired -> ffff0093
   3.076258	string_to_path: depth = 6
   3.076260	hid_lookup_usage: UPS -> 00840004
   3.076263	hid_lookup_usage: PowerConverter -> 00840016
   3.076265	hid_lookup_usage: Input -> 0084001a
   3.076268	hid_lookup_usage: [1] -> not found in lookup table
   3.076271	hid_lookup_usage: PresentStatus -> 00840002
   3.076275	hid_lookup_usage: Buck -> 0084006f
   3.076277	string_to_path: depth = 6
   3.076278	Report[buf]: (3 bytes) => 2d 00 00
   3.076279	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.076280	Unit = 00000000, UnitExp = 0
   3.076281	Exponent = 0
   3.076282	Path: UPS.PowerConverter.Input.[1].PresentStatus.Buck, Type: Feature, ReportID: 0x2d, Offset: 8, Size: 8, Value: 0
   3.076283	hu_find_infoval: found !trim (value: 0)
   3.076284	process_boolean_info: !trim
   3.076287	hid_lookup_usage: UPS -> 00840004
   3.076289	hid_lookup_usage: PowerConverter -> 00840016
   3.076291	hid_lookup_usage: Input -> 0084001a
   3.076294	hid_lookup_usage: [1] -> not found in lookup table
   3.076296	hid_lookup_usage: PresentStatus -> 00840002
   3.076300	hid_lookup_usage: Boost -> 0084006e
   3.076301	string_to_path: depth = 6
   3.076303	Report[buf]: (3 bytes) => 2d 00 00
   3.076304	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.076305	Unit = 00000000, UnitExp = 0
   3.076306	Exponent = 0
   3.076307	Path: UPS.PowerConverter.Input.[1].PresentStatus.Boost, Type: Feature, ReportID: 0x2d, Offset: 0, Size: 8, Value: 0
   3.076308	hu_find_infoval: found !boost (value: 0)
   3.076309	process_boolean_info: !boost
   3.076311	hid_lookup_usage: UPS -> 00840004
   3.076313	hid_lookup_usage: PowerConverter -> 00840016
   3.076315	hid_lookup_usage: Input -> 0084001a
   3.076318	hid_lookup_usage: [1] -> not found in lookup table
   3.076321	hid_lookup_usage: PresentStatus -> 00840002
   3.076325	hid_lookup_usage: VoltageOutOfRange -> 00840063
   3.076326	string_to_path: depth = 6
   3.076328	hid_lookup_usage: UPS -> 00840004
   3.076330	hid_lookup_usage: PowerConverter -> 00840016
   3.076332	hid_lookup_usage: Input -> 0084001a
   3.076335	hid_lookup_usage: [1] -> not found in lookup table
   3.076338	hid_lookup_usage: PresentStatus -> 00840002
   3.076342	hid_lookup_usage: FrequencyOutOfRange -> 00840064
   3.076343	string_to_path: depth = 6
   3.076345	hid_lookup_usage: UPS -> 00840004
   3.076347	hid_lookup_usage: PowerSummary -> 00840024
   3.076350	hid_lookup_usage: PresentStatus -> 00840002
   3.076352	hid_lookup_usage: Good -> 00840061
   3.076354	string_to_path: depth = 4
   3.076355	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.076356	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.076357	Unit = 00000000, UnitExp = 0
   3.076358	Exponent = 0
   3.076359	Path: UPS.PowerSummary.PresentStatus.Good, Type: Feature, ReportID: 0x01, Offset: 32, Size: 8, Value: 1
   3.076360	hu_find_infoval: found !off (value: 1)
   3.076361	process_boolean_info: !off
   3.076364	hid_lookup_usage: UPS -> 00840004
   3.076366	hid_lookup_usage: PowerConverter -> 00840016
   3.076368	hid_lookup_usage: Input -> 0084001a
   3.076371	hid_lookup_usage: [2] -> not found in lookup table
   3.076373	hid_lookup_usage: PresentStatus -> 00840002
   3.076378	hid_lookup_usage: Used -> 0084006d
   3.076378	string_to_path: depth = 6
   3.076381	hid_lookup_usage: UPS -> 00840004
   3.076383	hid_lookup_usage: PowerConverter -> 00840016
   3.076385	hid_lookup_usage: Input -> 0084001a
   3.076388	hid_lookup_usage: [4] -> not found in lookup table
   3.076390	hid_lookup_usage: PresentStatus -> 00840002
   3.076394	hid_lookup_usage: Used -> 0084006d
   3.076395	string_to_path: depth = 6
   3.076398	hid_lookup_usage: UPS -> 00840004
   3.076400	hid_lookup_usage: PowerSummary -> 00840024
   3.076402	hid_lookup_usage: PresentStatus -> 00840002
   3.076404	hid_lookup_usage: FanFailure -> ffff0077
   3.076405	string_to_path: depth = 4
   3.076407	hid_lookup_usage: UPS -> 00840004
   3.076410	hid_lookup_usage: BatterySystem -> 00840010
   3.076412	hid_lookup_usage: Battery -> 00840012
   3.076414	hid_lookup_usage: PresentStatus -> 00840002
   3.076419	hid_lookup_usage: Present -> 00840060
   3.076420	string_to_path: depth = 5
   3.076423	hid_lookup_usage: UPS -> 00840004
   3.076425	hid_lookup_usage: BatterySystem -> 00840010
   3.076427	hid_lookup_usage: Charger -> 00840014
   3.076429	hid_lookup_usage: PresentStatus -> 00840002
   3.076433	hid_lookup_usage: InternalFailure -> 00840062
   3.076434	string_to_path: depth = 5
   3.076436	hid_lookup_usage: UPS -> 00840004
   3.076438	hid_lookup_usage: BatterySystem -> 00840010
   3.076440	hid_lookup_usage: Charger -> 00840014
   3.076442	hid_lookup_usage: PresentStatus -> 00840002
   3.076445	hid_lookup_usage: VoltageTooHigh -> ffff0074
   3.076445	string_to_path: depth = 5
   3.076448	hid_lookup_usage: UPS -> 00840004
   3.076450	hid_lookup_usage: PowerConverter -> 00840016
   3.076452	hid_lookup_usage: Input -> 0084001a
   3.076456	hid_lookup_usage: [1] -> not found in lookup table
   3.076458	hid_lookup_usage: PresentStatus -> 00840002
   3.076460	hid_lookup_usage: VoltageTooHigh -> ffff0074
   3.076461	string_to_path: depth = 6
   3.076463	hid_lookup_usage: UPS -> 00840004
   3.076465	hid_lookup_usage: BatterySystem -> 00840010
   3.076468	hid_lookup_usage: Battery -> 00840012
   3.076470	hid_lookup_usage: PresentStatus -> 00840002
   3.076472	hid_lookup_usage: VoltageTooHigh -> ffff0074
   3.076473	string_to_path: depth = 5
   3.076475	hid_lookup_usage: UPS -> 00840004
   3.076477	hid_lookup_usage: BatterySystem -> 00840010
   3.076479	hid_lookup_usage: Charger -> 00840014
   3.076481	hid_lookup_usage: PresentStatus -> 00840002
   3.076483	hid_lookup_usage: VoltageTooLow -> ffff0075
   3.076484	string_to_path: depth = 5
   3.076487	hid_lookup_usage: UPS -> 00840004
   3.076489	hid_lookup_usage: PowerConverter -> 00840016
   3.076491	hid_lookup_usage: Input -> 0084001a
   3.076494	hid_lookup_usage: [1] -> not found in lookup table
   3.076496	hid_lookup_usage: PresentStatus -> 00840002
   3.076499	hid_lookup_usage: VoltageTooLow -> ffff0075
   3.076499	string_to_path: depth = 6
   3.076502	hid_lookup_usage: UPS -> 00840004
   3.076504	hid_lookup_usage: PowerSummary -> 00840024
   3.076507	hid_lookup_usage: PresentStatus -> 00840002
   3.076511	hid_lookup_usage: InternalFailure -> 00840062
   3.076514	string_to_path: depth = 4
   3.076517	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.076519	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.076521	Unit = 00000000, UnitExp = 0
   3.076523	Exponent = 0
   3.076525	Path: UPS.PowerSummary.PresentStatus.InternalFailure, Type: Feature, ReportID: 0x01, Offset: 40, Size: 8, Value: 0
   3.076526	hu_find_infoval: found !commfault (value: 0)
   3.076528	process_boolean_info: !commfault
   3.076532	hid_lookup_usage: UPS -> 00840004
   3.076536	hid_lookup_usage: PowerSummary -> 00840024
   3.076540	hid_lookup_usage: PresentStatus -> 00840002
   3.076544	hid_lookup_usage: OverTemperature -> 00840067
   3.076545	string_to_path: depth = 4
   3.076550	hid_lookup_usage: UPS -> 00840004
   3.076554	hid_lookup_usage: PowerSummary -> 00840024
   3.076557	hid_lookup_usage: PresentStatus -> 00840002
   3.076562	hid_lookup_usage: ShutdownImminent -> 00840069
   3.076564	string_to_path: depth = 4
   3.076569	hid_lookup_usage: UPS -> 00840004
   3.076571	hid_lookup_usage: PowerSummary -> 00840024
   3.076574	hid_lookup_usage: PresentStatus -> 00840002
   3.076575	hid_lookup_usage: EmergencyStop -> ffff0068
   3.076576	string_to_path: depth = 4
   3.076579	hid_lookup_usage: UPS -> 00840004
   3.076581	hid_lookup_usage: PowerConverter -> 00840016
   3.076583	hid_lookup_usage: Input -> 0084001a
   3.076586	hid_lookup_usage: [1] -> not found in lookup table
   3.076589	hid_lookup_usage: PresentStatus -> 00840002
   3.076591	hid_lookup_usage: WiringFault -> ffff0078
   3.076592	string_to_path: depth = 6
   3.076594	hid_lookup_usage: UPS -> 00840004
   3.076596	hid_lookup_usage: PowerSummary -> 00840024
   3.076598	hid_lookup_usage: PresentStatus -> 00840002
   3.076600	hid_lookup_usage: ConfigurationFailure -> ffff002d
   3.076601	string_to_path: depth = 4
   3.076603	hid_lookup_usage: UPS -> 00840004
   3.076605	hid_lookup_usage: PowerConverter -> 00840016
   3.076607	hid_lookup_usage: Inverter -> ffff0014
   3.076609	hid_lookup_usage: PresentStatus -> 00840002
   3.076611	hid_lookup_usage: VoltageTooHigh -> ffff0074
   3.076612	string_to_path: depth = 5
   3.076615	hid_lookup_usage: UPS -> 00840004
   3.076617	hid_lookup_usage: PowerConverter -> 00840016
   3.076618	hid_lookup_usage: Inverter -> ffff0014
   3.076620	hid_lookup_usage: PresentStatus -> 00840002
   3.076622	hid_lookup_usage: VoltageTooLow -> ffff0075
   3.076623	string_to_path: depth = 5
   3.076625	hid_lookup_usage: UPS -> 00840004
   3.076627	hid_lookup_usage: PowerConverter -> 00840016
   3.076629	hid_lookup_usage: Output -> 0084001c
   3.076632	hid_lookup_usage: PresentStatus -> 00840002
   3.076634	hid_lookup_usage: ShortCircuit -> ffff004a
   3.076635	string_to_path: depth = 5
   3.076637	hid_lookup_usage: UPS -> 00840004
   3.076639	hid_lookup_usage: PowerConverter -> 00840016
   3.076641	hid_lookup_usage: Input -> 0084001a
   3.076644	hid_lookup_usage: [1] -> not found in lookup table
   3.076647	hid_lookup_usage: Voltage -> 00840030
   3.076648	string_to_path: depth = 5
   3.076649	Report[buf]: (3 bytes) => 31 ea 00
   3.076650	PhyMax = 0, PhyMin = 0, LogMax = 65535, LogMin = 0
   3.076651	Unit = 00f0d121, UnitExp = 7
   3.076652	Exponent = 0
   3.076654	Path: UPS.PowerConverter.Input.[1].Voltage, Type: Feature, ReportID: 0x31, Offset: 0, Size: 16, Value: 234
   3.076656	send_to_all: SETINFO input.voltage "234.0"
   3.076658	hid_lookup_usage: UPS -> 00840004
   3.076660	hid_lookup_usage: PowerConverter -> 00840016
   3.076663	hid_lookup_usage: Input -> 0084001a
   3.076666	hid_lookup_usage: [1] -> not found in lookup table
   3.076667	hid_lookup_usage: Phase -> ffff0010
   3.076673	hid_lookup_usage: [1] -> not found in lookup table
   3.076678	hid_lookup_usage: Voltage -> 00840030
   3.076679	string_to_path: depth = 7
   3.076682	hid_lookup_usage: UPS -> 00840004
   3.076684	hid_lookup_usage: PowerConverter -> 00840016
   3.076686	hid_lookup_usage: Input -> 0084001a
   3.076689	hid_lookup_usage: [1] -> not found in lookup table
   3.076690	hid_lookup_usage: Phase -> ffff0010
   3.076695	hid_lookup_usage: [2] -> not found in lookup table
   3.076699	hid_lookup_usage: Voltage -> 00840030
   3.076700	string_to_path: depth = 7
   3.076702	hid_lookup_usage: UPS -> 00840004
   3.076704	hid_lookup_usage: PowerConverter -> 00840016
   3.076707	hid_lookup_usage: Input -> 0084001a
   3.076710	hid_lookup_usage: [1] -> not found in lookup table
   3.076711	hid_lookup_usage: Phase -> ffff0010
   3.076716	hid_lookup_usage: [3] -> not found in lookup table
   3.076720	hid_lookup_usage: Voltage -> 00840030
   3.076721	string_to_path: depth = 7
   3.076723	hid_lookup_usage: UPS -> 00840004
   3.076726	hid_lookup_usage: PowerConverter -> 00840016
   3.076728	hid_lookup_usage: Input -> 0084001a
   3.076731	hid_lookup_usage: [1] -> not found in lookup table
   3.076732	hid_lookup_usage: Phase -> ffff0010
   3.076737	hid_lookup_usage: [12] -> not found in lookup table
   3.076742	hid_lookup_usage: Voltage -> 00840030
   3.076743	string_to_path: depth = 7
   3.076745	hid_lookup_usage: UPS -> 00840004
   3.076747	hid_lookup_usage: PowerConverter -> 00840016
   3.076749	hid_lookup_usage: Input -> 0084001a
   3.076753	hid_lookup_usage: [1] -> not found in lookup table
   3.076754	hid_lookup_usage: Phase -> ffff0010
   3.076759	hid_lookup_usage: [23] -> not found in lookup table
   3.076763	hid_lookup_usage: Voltage -> 00840030
   3.076763	string_to_path: depth = 7
   3.076766	hid_lookup_usage: UPS -> 00840004
   3.076768	hid_lookup_usage: PowerConverter -> 00840016
   3.076770	hid_lookup_usage: Input -> 0084001a
   3.076773	hid_lookup_usage: [1] -> not found in lookup table
   3.076775	hid_lookup_usage: Phase -> ffff0010
   3.076780	hid_lookup_usage: [31] -> not found in lookup table
   3.076783	hid_lookup_usage: Voltage -> 00840030
   3.076784	string_to_path: depth = 7
   3.076787	hid_lookup_usage: UPS -> 00840004
   3.076789	hid_lookup_usage: Flow -> 0084001e
   3.076792	hid_lookup_usage: [1] -> not found in lookup table
   3.076795	hid_lookup_usage: ConfigVoltage -> 00840040
   3.076796	string_to_path: depth = 4
   3.076798	hid_lookup_usage: UPS -> 00840004
   3.076800	hid_lookup_usage: PowerConverter -> 00840016
   3.076802	hid_lookup_usage: Input -> 0084001a
   3.076805	hid_lookup_usage: [1] -> not found in lookup table
   3.076808	hid_lookup_usage: Current -> 00840031
   3.076809	string_to_path: depth = 5
   3.076811	hid_lookup_usage: UPS -> 00840004
   3.076813	hid_lookup_usage: PowerConverter -> 00840016
   3.076815	hid_lookup_usage: Input -> 0084001a
   3.076818	hid_lookup_usage: [1] -> not found in lookup table
   3.076820	hid_lookup_usage: Phase -> ffff0010
   3.076825	hid_lookup_usage: [1] -> not found in lookup table
   3.076829	hid_lookup_usage: Current -> 00840031
   3.076830	string_to_path: depth = 7
   3.076832	hid_lookup_usage: UPS -> 00840004
   3.076835	hid_lookup_usage: PowerConverter -> 00840016
   3.076837	hid_lookup_usage: Input -> 0084001a
   3.076840	hid_lookup_usage: [1] -> not found in lookup table
   3.076841	hid_lookup_usage: Phase -> ffff0010
   3.076847	hid_lookup_usage: [2] -> not found in lookup table
   3.076850	hid_lookup_usage: Current -> 00840031
   3.076851	string_to_path: depth = 7
   3.076853	hid_lookup_usage: UPS -> 00840004
   3.076855	hid_lookup_usage: PowerConverter -> 00840016
   3.076857	hid_lookup_usage: Input -> 0084001a
   3.076860	hid_lookup_usage: [1] -> not found in lookup table
   3.076862	hid_lookup_usage: Phase -> ffff0010
   3.076867	hid_lookup_usage: [3] -> not found in lookup table
   3.076871	hid_lookup_usage: Current -> 00840031
   3.076872	string_to_path: depth = 7
   3.076874	hid_lookup_usage: UPS -> 00840004
   3.076876	hid_lookup_usage: Flow -> 0084001e
   3.076879	hid_lookup_usage: [1] -> not found in lookup table
   3.076882	hid_lookup_usage: ConfigCurrent -> 00840041
   3.076883	string_to_path: depth = 4
   3.076885	hid_lookup_usage: UPS -> 00840004
   3.076887	hid_lookup_usage: PowerConverter -> 00840016
   3.076889	hid_lookup_usage: Input -> 0084001a
   3.076892	hid_lookup_usage: [1] -> not found in lookup table
   3.076895	hid_lookup_usage: Frequency -> 00840032
   3.076896	string_to_path: depth = 5
   3.076898	hid_lookup_usage: UPS -> 00840004
   3.076900	hid_lookup_usage: Flow -> 0084001e
   3.076902	hid_lookup_usage: [1] -> not found in lookup table
   3.076904	hid_lookup_usage: ConfigFrequency -> 00840042
   3.076904	string_to_path: depth = 4
   3.076906	hid_lookup_usage: UPS -> 00840004
   3.076908	hid_lookup_usage: PowerConverter -> 00840016
   3.076909	hid_lookup_usage: Output -> 0084001c
   3.076911	hid_lookup_usage: LowVoltageTransfer -> 00840053
   3.076912	string_to_path: depth = 4
   3.076914	hid_lookup_usage: UPS -> 00840004
   3.076915	hid_lookup_usage: PowerConverter -> 00840016
   3.076917	hid_lookup_usage: Output -> 0084001c
   3.076918	hid_lookup_usage: LowVoltageBoostTransfer -> ffff0050
   3.076918	string_to_path: depth = 4
   3.076920	hid_lookup_usage: UPS -> 00840004
   3.076921	hid_lookup_usage: PowerConverter -> 00840016
   3.076923	hid_lookup_usage: Output -> 0084001c
   3.076924	hid_lookup_usage: HighVoltageBoostTransfer -> ffff0051
   3.076924	string_to_path: depth = 4
   3.076926	hid_lookup_usage: UPS -> 00840004
   3.076928	hid_lookup_usage: PowerConverter -> 00840016
   3.076929	hid_lookup_usage: Output -> 0084001c
   3.076930	hid_lookup_usage: LowVoltageBuckTransfer -> ffff0052
   3.076931	string_to_path: depth = 4
   3.076933	hid_lookup_usage: UPS -> 00840004
   3.076934	hid_lookup_usage: PowerConverter -> 00840016
   3.076936	hid_lookup_usage: Output -> 0084001c
   3.076938	hid_lookup_usage: HighVoltageTransfer -> 00840054
   3.076938	string_to_path: depth = 4
   3.076940	hid_lookup_usage: UPS -> 00840004
   3.076941	hid_lookup_usage: PowerConverter -> 00840016
   3.076943	hid_lookup_usage: Output -> 0084001c
   3.076944	hid_lookup_usage: HighVoltageBuckTransfer -> ffff0053
   3.076945	string_to_path: depth = 4
   3.076946	hid_lookup_usage: UPS -> 00840004
   3.076948	hid_lookup_usage: PowerConverter -> 00840016
   3.076949	hid_lookup_usage: Output -> 0084001c
   3.076950	hid_lookup_usage: SensitivityMode -> ffff004c
   3.076951	string_to_path: depth = 4
   3.076952	hid_lookup_usage: UPS -> 00840004
   3.076954	hid_lookup_usage: PowerConverter -> 00840016
   3.076955	hid_lookup_usage: Output -> 0084001c
   3.076956	hid_lookup_usage: ExtendedVoltageMode -> ffff004b
   3.076957	string_to_path: depth = 4
   3.076959	hid_lookup_usage: UPS -> 00840004
   3.076960	hid_lookup_usage: PowerConverter -> 00840016
   3.076962	hid_lookup_usage: Output -> 0084001c
   3.076963	hid_lookup_usage: ExtendedFrequencyMode -> ffff004e
   3.076963	string_to_path: depth = 4
   3.076965	hid_lookup_usage: UPS -> 00840004
   3.076966	hid_lookup_usage: PowerConverter -> 00840016
   3.076968	hid_lookup_usage: Input -> 0084001a
   3.076970	hid_lookup_usage: [2] -> not found in lookup table
   3.076972	hid_lookup_usage: Voltage -> 00840030
   3.076973	string_to_path: depth = 5
   3.076974	hid_lookup_usage: UPS -> 00840004
   3.076976	hid_lookup_usage: PowerConverter -> 00840016
   3.076977	hid_lookup_usage: Input -> 0084001a
   3.076979	hid_lookup_usage: [2] -> not found in lookup table
   3.076980	hid_lookup_usage: Phase -> ffff0010
   3.076984	hid_lookup_usage: [1] -> not found in lookup table
   3.076987	hid_lookup_usage: Voltage -> 00840030
   3.076987	string_to_path: depth = 7
   3.076989	hid_lookup_usage: UPS -> 00840004
   3.076990	hid_lookup_usage: PowerConverter -> 00840016
   3.076992	hid_lookup_usage: Input -> 0084001a
   3.076995	hid_lookup_usage: [2] -> not found in lookup table
   3.076995	hid_lookup_usage: Phase -> ffff0010
   3.076999	hid_lookup_usage: [2] -> not found in lookup table
   3.077002	hid_lookup_usage: Voltage -> 00840030
   3.077002	string_to_path: depth = 7
   3.077004	hid_lookup_usage: UPS -> 00840004
   3.077005	hid_lookup_usage: PowerConverter -> 00840016
   3.077007	hid_lookup_usage: Input -> 0084001a
   3.077009	hid_lookup_usage: [2] -> not found in lookup table
   3.077010	hid_lookup_usage: Phase -> ffff0010
   3.077014	hid_lookup_usage: [3] -> not found in lookup table
   3.077016	hid_lookup_usage: Voltage -> 00840030
   3.077017	string_to_path: depth = 7
   3.077019	hid_lookup_usage: UPS -> 00840004
   3.077020	hid_lookup_usage: PowerConverter -> 00840016
   3.077022	hid_lookup_usage: Input -> 0084001a
   3.077024	hid_lookup_usage: [2] -> not found in lookup table
   3.077025	hid_lookup_usage: Phase -> ffff0010
   3.077029	hid_lookup_usage: [12] -> not found in lookup table
   3.077031	hid_lookup_usage: Voltage -> 00840030
   3.077032	string_to_path: depth = 7
   3.077034	hid_lookup_usage: UPS -> 00840004
   3.077035	hid_lookup_usage: PowerConverter -> 00840016
   3.077037	hid_lookup_usage: Input -> 0084001a
   3.077039	hid_lookup_usage: [2] -> not found in lookup table
   3.077040	hid_lookup_usage: Phase -> ffff0010
   3.077044	hid_lookup_usage: [23] -> not found in lookup table
   3.077046	hid_lookup_usage: Voltage -> 00840030
   3.077047	string_to_path: depth = 7
   3.077048	hid_lookup_usage: UPS -> 00840004
   3.077050	hid_lookup_usage: PowerConverter -> 00840016
   3.077051	hid_lookup_usage: Input -> 0084001a
   3.077054	hid_lookup_usage: [2] -> not found in lookup table
   3.077054	hid_lookup_usage: Phase -> ffff0010
   3.077058	hid_lookup_usage: [31] -> not found in lookup table
   3.077061	hid_lookup_usage: Voltage -> 00840030
   3.077061	string_to_path: depth = 7
   3.077063	hid_lookup_usage: UPS -> 00840004
   3.077065	hid_lookup_usage: Flow -> 0084001e
   3.077067	hid_lookup_usage: [2] -> not found in lookup table
   3.077069	hid_lookup_usage: ConfigVoltage -> 00840040
   3.077069	string_to_path: depth = 4
   3.077071	hid_lookup_usage: UPS -> 00840004
   3.077072	hid_lookup_usage: PowerConverter -> 00840016
   3.077074	hid_lookup_usage: Input -> 0084001a
   3.077076	hid_lookup_usage: [2] -> not found in lookup table
   3.077078	hid_lookup_usage: Current -> 00840031
   3.077079	string_to_path: depth = 5
   3.077080	hid_lookup_usage: UPS -> 00840004
   3.077082	hid_lookup_usage: PowerConverter -> 00840016
   3.077083	hid_lookup_usage: Input -> 0084001a
   3.077085	hid_lookup_usage: [2] -> not found in lookup table
   3.077086	hid_lookup_usage: Phase -> ffff0010
   3.077090	hid_lookup_usage: [1] -> not found in lookup table
   3.077093	hid_lookup_usage: Current -> 00840031
   3.077093	string_to_path: depth = 7
   3.077095	hid_lookup_usage: UPS -> 00840004
   3.077096	hid_lookup_usage: PowerConverter -> 00840016
   3.077098	hid_lookup_usage: Input -> 0084001a
   3.077100	hid_lookup_usage: [2] -> not found in lookup table
   3.077101	hid_lookup_usage: Phase -> ffff0010
   3.077105	hid_lookup_usage: [2] -> not found in lookup table
   3.077107	hid_lookup_usage: Current -> 00840031
   3.077108	string_to_path: depth = 7
   3.077110	hid_lookup_usage: UPS -> 00840004
   3.077111	hid_lookup_usage: PowerConverter -> 00840016
   3.077113	hid_lookup_usage: Input -> 0084001a
   3.077115	hid_lookup_usage: [2] -> not found in lookup table
   3.077116	hid_lookup_usage: Phase -> ffff0010
   3.077120	hid_lookup_usage: [3] -> not found in lookup table
   3.077122	hid_lookup_usage: Current -> 00840031
   3.077123	string_to_path: depth = 7
   3.077124	hid_lookup_usage: UPS -> 00840004
   3.077126	hid_lookup_usage: Flow -> 0084001e
   3.077128	hid_lookup_usage: [2] -> not found in lookup table
   3.077130	hid_lookup_usage: ConfigCurrent -> 00840041
   3.077131	string_to_path: depth = 4
   3.077132	hid_lookup_usage: UPS -> 00840004
   3.077134	hid_lookup_usage: PowerConverter -> 00840016
   3.077135	hid_lookup_usage: Input -> 0084001a
   3.077137	hid_lookup_usage: [2] -> not found in lookup table
   3.077139	hid_lookup_usage: Frequency -> 00840032
   3.077140	string_to_path: depth = 5
   3.077142	hid_lookup_usage: UPS -> 00840004
   3.077143	hid_lookup_usage: Flow -> 0084001e
   3.077145	hid_lookup_usage: [2] -> not found in lookup table
   3.077147	hid_lookup_usage: ConfigFrequency -> 00840042
   3.077148	string_to_path: depth = 4
   3.077150	hid_lookup_usage: UPS -> 00840004
   3.077151	hid_lookup_usage: PowerConverter -> 00840016
   3.077153	hid_lookup_usage: Output -> 0084001c
   3.077155	hid_lookup_usage: Voltage -> 00840030
   3.077155	string_to_path: depth = 4
   3.077157	Report[buf]: (5 bytes) => 42 f2 01 ea 00
   3.077158	PhyMax = 0, PhyMin = 0, LogMax = 65535, LogMin = 0
   3.077158	Unit = 00f0d121, UnitExp = 7
   3.077159	Exponent = 0
   3.077160	Path: UPS.PowerConverter.Output.Voltage, Type: Feature, ReportID: 0x42, Offset: 16, Size: 16, Value: 234
   3.077161	send_to_all: SETINFO output.voltage "234.0"
   3.077163	hid_lookup_usage: UPS -> 00840004
   3.077165	hid_lookup_usage: PowerConverter -> 00840016
   3.077166	hid_lookup_usage: Output -> 0084001c
   3.077167	hid_lookup_usage: Phase -> ffff0010
   3.077169	hid_lookup_usage: [1] -> not found in lookup table
   3.077173	hid_lookup_usage: Voltage -> 00840030
   3.077173	string_to_path: depth = 6
   3.077175	hid_lookup_usage: UPS -> 00840004
   3.077176	hid_lookup_usage: PowerConverter -> 00840016
   3.077178	hid_lookup_usage: Output -> 0084001c
   3.077179	hid_lookup_usage: Phase -> ffff0010
   3.077181	hid_lookup_usage: [2] -> not found in lookup table
   3.077183	hid_lookup_usage: Voltage -> 00840030
   3.077184	string_to_path: depth = 6
   3.077186	hid_lookup_usage: UPS -> 00840004
   3.077187	hid_lookup_usage: PowerConverter -> 00840016
   3.077189	hid_lookup_usage: Output -> 0084001c
   3.077189	hid_lookup_usage: Phase -> ffff0010
   3.077192	hid_lookup_usage: [3] -> not found in lookup table
   3.077194	hid_lookup_usage: Voltage -> 00840030
   3.077194	string_to_path: depth = 6
   3.077196	hid_lookup_usage: UPS -> 00840004
   3.077198	hid_lookup_usage: PowerConverter -> 00840016
   3.077199	hid_lookup_usage: Output -> 0084001c
   3.077200	hid_lookup_usage: Phase -> ffff0010
   3.077202	hid_lookup_usage: [12] -> not found in lookup table
   3.077205	hid_lookup_usage: Voltage -> 00840030
   3.077206	string_to_path: depth = 6
   3.077208	hid_lookup_usage: UPS -> 00840004
   3.077209	hid_lookup_usage: PowerConverter -> 00840016
   3.077211	hid_lookup_usage: Output -> 0084001c
   3.077211	hid_lookup_usage: Phase -> ffff0010
   3.077214	hid_lookup_usage: [23] -> not found in lookup table
   3.077216	hid_lookup_usage: Voltage -> 00840030
   3.077217	string_to_path: depth = 6
   3.077218	hid_lookup_usage: UPS -> 00840004
   3.077220	hid_lookup_usage: PowerConverter -> 00840016
   3.077221	hid_lookup_usage: Output -> 0084001c
   3.077222	hid_lookup_usage: Phase -> ffff0010
   3.077224	hid_lookup_usage: [31] -> not found in lookup table
   3.077227	hid_lookup_usage: Voltage -> 00840030
   3.077227	string_to_path: depth = 6
   3.077229	hid_lookup_usage: UPS -> 00840004
   3.077230	hid_lookup_usage: Flow -> 0084001e
   3.077233	hid_lookup_usage: [4] -> not found in lookup table
   3.077236	hid_lookup_usage: ConfigVoltage -> 00840040
   3.077236	string_to_path: depth = 4
   3.077237	Report[buf]: (2 bytes) => 72 e6
   3.077238	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.077239	Unit = 00f0d121, UnitExp = 7
   3.077239	Exponent = 0
   3.077241	Path: UPS.Flow.[4].ConfigVoltage, Type: Feature, ReportID: 0x72, Offset: 0, Size: 8, Value: 230
   3.077242	send_to_all: SETINFO output.voltage.nominal "230"
   3.077243	send_to_all: SETFLAGS output.voltage.nominal RW STRING
   3.077244	send_to_all: SETAUX output.voltage.nominal 3
   3.077245	send_to_all: ADDENUM output.voltage.nominal "200"
   3.077247	send_to_all: ADDENUM output.voltage.nominal "208"
   3.077248	send_to_all: ADDENUM output.voltage.nominal "220"
   3.077249	send_to_all: ADDENUM output.voltage.nominal "230"
   3.077250	send_to_all: ADDENUM output.voltage.nominal "240"
   3.077252	hid_lookup_usage: UPS -> 00840004
   3.077253	hid_lookup_usage: PowerConverter -> 00840016
   3.077255	hid_lookup_usage: Output -> 0084001c
   3.077256	hid_lookup_usage: Current -> 00840031
   3.077257	string_to_path: depth = 4
   3.077259	hid_lookup_usage: UPS -> 00840004
   3.077260	hid_lookup_usage: PowerConverter -> 00840016
   3.077262	hid_lookup_usage: Output -> 0084001c
   3.077263	hid_lookup_usage: Phase -> ffff0010
   3.077265	hid_lookup_usage: [1] -> not found in lookup table
   3.077268	hid_lookup_usage: Current -> 00840031
   3.077268	string_to_path: depth = 6
   3.077270	hid_lookup_usage: UPS -> 00840004
   3.077271	hid_lookup_usage: PowerConverter -> 00840016
   3.077273	hid_lookup_usage: Output -> 0084001c
   3.077274	hid_lookup_usage: Phase -> ffff0010
   3.077276	hid_lookup_usage: [2] -> not found in lookup table
   3.077278	hid_lookup_usage: Current -> 00840031
   3.077279	string_to_path: depth = 6
   3.077280	hid_lookup_usage: UPS -> 00840004
   3.077282	hid_lookup_usage: PowerConverter -> 00840016
   3.077283	hid_lookup_usage: Output -> 0084001c
   3.077284	hid_lookup_usage: Phase -> ffff0010
   3.077287	hid_lookup_usage: [3] -> not found in lookup table
   3.077289	hid_lookup_usage: Current -> 00840031
   3.077289	string_to_path: depth = 6
   3.077291	hid_lookup_usage: UPS -> 00840004
   3.077292	hid_lookup_usage: Flow -> 0084001e
   3.077295	hid_lookup_usage: [4] -> not found in lookup table
   3.077297	hid_lookup_usage: ConfigCurrent -> 00840041
   3.077297	string_to_path: depth = 4
   3.077299	hid_lookup_usage: UPS -> 00840004
   3.077300	hid_lookup_usage: PowerConverter -> 00840016
   3.077302	hid_lookup_usage: Output -> 0084001c
   3.077304	hid_lookup_usage: Frequency -> 00840032
   3.077304	string_to_path: depth = 4
   3.077306	Report[buf]: (5 bytes) => 42 f2 01 ea 00
   3.077306	PhyMax = 0, PhyMin = 0, LogMax = 65535, LogMin = 0
   3.077307	Unit = 0000f001, UnitExp = -1
   3.077308	Exponent = -1
   3.077309	Path: UPS.PowerConverter.Output.Frequency, Type: Feature, ReportID: 0x42, Offset: 0, Size: 16, Value: 49.8
   3.077310	send_to_all: SETINFO output.frequency "49.8"
   3.077312	hid_lookup_usage: UPS -> 00840004
   3.077314	hid_lookup_usage: Flow -> 0084001e
   3.077316	hid_lookup_usage: [4] -> not found in lookup table
   3.077318	hid_lookup_usage: ConfigFrequency -> 00840042
   3.077318	string_to_path: depth = 4
   3.077319	Report[buf]: (2 bytes) => 36 32
   3.077320	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.077321	Unit = 0000f001, UnitExp = 0
   3.077321	Exponent = 0
   3.077322	Path: UPS.Flow.[4].ConfigFrequency, Type: Feature, ReportID: 0x36, Offset: 0, Size: 8, Value: 50
   3.077324	send_to_all: SETINFO output.frequency.nominal "50"
   3.077325	hid_lookup_usage: UPS -> 00840004
   3.077327	hid_lookup_usage: PowerConverter -> 00840016
   3.077328	hid_lookup_usage: Output -> 0084001c
   3.077330	hid_lookup_usage: PowerFactor -> ffff0069
   3.077330	string_to_path: depth = 4
   3.077332	hid_lookup_usage: UPS -> 00840004
   3.077333	hid_lookup_usage: OutletSystem -> 00840018
   3.077335	hid_lookup_usage: Outlet -> 00840020
   3.077338	hid_lookup_usage: [1] -> not found in lookup table
   3.077340	hid_lookup_usage: OutletID -> 00840021
   3.077341	string_to_path: depth = 5
   3.077343	hid_lookup_usage: UPS -> 00840004
   3.077344	hid_lookup_usage: OutletSystem -> 00840018
   3.077346	hid_lookup_usage: Outlet -> 00840020
   3.077348	hid_lookup_usage: [1] -> not found in lookup table
   3.077350	hid_lookup_usage: OutletID -> 00840021
   3.077351	string_to_path: depth = 5
   3.077352	hid_lookup_usage: UPS -> 00840004
   3.077354	hid_lookup_usage: OutletSystem -> 00840018
   3.077355	hid_lookup_usage: Outlet -> 00840020
   3.077358	hid_lookup_usage: [1] -> not found in lookup table
   3.077359	hid_lookup_usage: PresentStatus -> 00840002
   3.077363	hid_lookup_usage: Switchable -> 0084006c
   3.077364	string_to_path: depth = 6
   3.077365	hid_lookup_usage: UPS -> 00840004
   3.077367	hid_lookup_usage: OutletSystem -> 00840018
   3.077369	hid_lookup_usage: Outlet -> 00840020
   3.077371	hid_lookup_usage: [1] -> not found in lookup table
   3.077373	hid_lookup_usage: ConfigApparentPower -> 00840043
   3.077373	string_to_path: depth = 5
   3.077375	hid_lookup_usage: UPS -> 00840004
   3.077377	hid_lookup_usage: OutletSystem -> 00840018
   3.077378	hid_lookup_usage: Outlet -> 00840020
   3.077381	hid_lookup_usage: [1] -> not found in lookup table
   3.077382	hid_lookup_usage: ApparentPower -> 00840033
   3.077383	string_to_path: depth = 5
   3.077385	hid_lookup_usage: UPS -> 00840004
   3.077386	hid_lookup_usage: OutletSystem -> 00840018
   3.077388	hid_lookup_usage: Outlet -> 00840020
   3.077390	hid_lookup_usage: [1] -> not found in lookup table
   3.077392	hid_lookup_usage: ActivePower -> 00840034
   3.077392	string_to_path: depth = 5
   3.077394	hid_lookup_usage: UPS -> 00840004
   3.077396	hid_lookup_usage: OutletSystem -> 00840018
   3.077397	hid_lookup_usage: Outlet -> 00840020
   3.077399	hid_lookup_usage: [1] -> not found in lookup table
   3.077401	hid_lookup_usage: Current -> 00840031
   3.077402	string_to_path: depth = 5
   3.077403	hid_lookup_usage: UPS -> 00840004
   3.077405	hid_lookup_usage: OutletSystem -> 00840018
   3.077407	hid_lookup_usage: Outlet -> 00840020
   3.077409	hid_lookup_usage: [1] -> not found in lookup table
   3.077410	hid_lookup_usage: PowerFactor -> ffff0069
   3.077411	string_to_path: depth = 5
   3.077412	hid_lookup_usage: UPS -> 00840004
   3.077414	hid_lookup_usage: OutletSystem -> 00840018
   3.077415	hid_lookup_usage: Outlet -> 00840020
   3.077418	hid_lookup_usage: [2] -> not found in lookup table
   3.077419	hid_lookup_usage: OutletID -> 00840021
   3.077420	string_to_path: depth = 5
   3.077422	hid_lookup_usage: UPS -> 00840004
   3.077423	hid_lookup_usage: OutletSystem -> 00840018
   3.077425	hid_lookup_usage: Outlet -> 00840020
   3.077427	hid_lookup_usage: [2] -> not found in lookup table
   3.077429	hid_lookup_usage: OutletID -> 00840021
   3.077429	string_to_path: depth = 5
   3.077431	hid_lookup_usage: UPS -> 00840004
   3.077432	hid_lookup_usage: OutletSystem -> 00840018
   3.077434	hid_lookup_usage: Outlet -> 00840020
   3.077436	hid_lookup_usage: [2] -> not found in lookup table
   3.077438	hid_lookup_usage: PresentStatus -> 00840002
   3.077441	hid_lookup_usage: Switchable -> 0084006c
   3.077442	string_to_path: depth = 6
   3.077443	hid_lookup_usage: UPS -> 00840004
   3.077445	hid_lookup_usage: OutletSystem -> 00840018
   3.077446	hid_lookup_usage: Outlet -> 00840020
   3.077449	hid_lookup_usage: [2] -> not found in lookup table
   3.077450	hid_lookup_usage: PresentStatus -> 00840002
   3.077453	hid_lookup_usage: SwitchOn/Off -> 0084006b
   3.077454	string_to_path: depth = 6
   3.077455	hid_lookup_usage: UPS -> 00840004
   3.077457	hid_lookup_usage: PowerSummary -> 00840024
   3.077458	hid_lookup_usage: PresentStatus -> 00840002
   3.077461	hid_lookup_usage: ACPresent -> 008500d0
   3.077462	string_to_path: depth = 4
   3.077463	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.077464	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.077465	Unit = 00000000, UnitExp = 0
   3.077465	Exponent = 0
   3.077466	Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 1
   3.077468	hu_find_infoval: found on (value: 1)
   3.077470	send_to_all: SETINFO outlet.1.status "on"
   3.077473	hid_lookup_usage: UPS -> 00840004
   3.077476	hid_lookup_usage: OutletSystem -> 00840018
   3.077479	hid_lookup_usage: Outlet -> 00840020
   3.077483	hid_lookup_usage: [2] -> not found in lookup table
   3.077488	hid_lookup_usage: RemainingCapacityLimit -> 00850029
   3.077489	string_to_path: depth = 5
   3.077492	hid_lookup_usage: UPS -> 00840004
   3.077495	hid_lookup_usage: OutletSystem -> 00840018
   3.077498	hid_lookup_usage: Outlet -> 00840020
   3.077501	hid_lookup_usage: [2] -> not found in lookup table
   3.077503	hid_lookup_usage: ShutdownTimer -> ffff005d
   3.077505	string_to_path: depth = 5
   3.077508	hid_lookup_usage: UPS -> 00840004
   3.077510	hid_lookup_usage: OutletSystem -> 00840018
   3.077512	hid_lookup_usage: Outlet -> 00840020
   3.077515	hid_lookup_usage: [2] -> not found in lookup table
   3.077517	hid_lookup_usage: StartupTimer -> ffff005e
   3.077519	string_to_path: depth = 5
   3.077522	hid_lookup_usage: UPS -> 00840004
   3.077524	hid_lookup_usage: OutletSystem -> 00840018
   3.077527	hid_lookup_usage: Outlet -> 00840020
   3.077531	hid_lookup_usage: [2] -> not found in lookup table
   3.077534	hid_lookup_usage: ApparentPower -> 00840033
   3.077535	string_to_path: depth = 5
   3.077538	hid_lookup_usage: UPS -> 00840004
   3.077539	hid_lookup_usage: OutletSystem -> 00840018
   3.077541	hid_lookup_usage: Outlet -> 00840020
   3.077544	hid_lookup_usage: [2] -> not found in lookup table
   3.077545	hid_lookup_usage: ActivePower -> 00840034
   3.077546	string_to_path: depth = 5
   3.077548	hid_lookup_usage: UPS -> 00840004
   3.077549	hid_lookup_usage: OutletSystem -> 00840018
   3.077551	hid_lookup_usage: Outlet -> 00840020
   3.077553	hid_lookup_usage: [2] -> not found in lookup table
   3.077555	hid_lookup_usage: Current -> 00840031
   3.077555	string_to_path: depth = 5
   3.077557	hid_lookup_usage: UPS -> 00840004
   3.077559	hid_lookup_usage: OutletSystem -> 00840018
   3.077560	hid_lookup_usage: Outlet -> 00840020
   3.077562	hid_lookup_usage: [2] -> not found in lookup table
   3.077564	hid_lookup_usage: PowerFactor -> ffff0069
   3.077564	string_to_path: depth = 5
   3.077566	hid_lookup_usage: UPS -> 00840004
   3.077567	hid_lookup_usage: OutletSystem -> 00840018
   3.077569	hid_lookup_usage: Outlet -> 00840020
   3.077571	hid_lookup_usage: [3] -> not found in lookup table
   3.077573	hid_lookup_usage: OutletID -> 00840021
   3.077574	string_to_path: depth = 5
   3.077575	hid_lookup_usage: UPS -> 00840004
   3.077577	hid_lookup_usage: OutletSystem -> 00840018
   3.077578	hid_lookup_usage: Outlet -> 00840020
   3.077581	hid_lookup_usage: [3] -> not found in lookup table
   3.077582	hid_lookup_usage: OutletID -> 00840021
   3.077583	string_to_path: depth = 5
   3.077585	hid_lookup_usage: UPS -> 00840004
   3.077586	hid_lookup_usage: OutletSystem -> 00840018
   3.077588	hid_lookup_usage: Outlet -> 00840020
   3.077590	hid_lookup_usage: [3] -> not found in lookup table
   3.077592	hid_lookup_usage: PresentStatus -> 00840002
   3.077594	hid_lookup_usage: Switchable -> 0084006c
   3.077595	string_to_path: depth = 6
   3.077597	hid_lookup_usage: UPS -> 00840004
   3.077598	hid_lookup_usage: OutletSystem -> 00840018
   3.077600	hid_lookup_usage: Outlet -> 00840020
   3.077602	hid_lookup_usage: [3] -> not found in lookup table
   3.077604	hid_lookup_usage: PresentStatus -> 00840002
   3.077606	hid_lookup_usage: Switchable -> 0084006c
   3.077607	string_to_path: depth = 6
   3.077609	hid_lookup_usage: UPS -> 00840004
   3.077610	hid_lookup_usage: OutletSystem -> 00840018
   3.077612	hid_lookup_usage: Outlet -> 00840020
   3.077614	hid_lookup_usage: [3] -> not found in lookup table
   3.077616	hid_lookup_usage: PresentStatus -> 00840002
   3.077618	hid_lookup_usage: SwitchOn/Off -> 0084006b
   3.077619	string_to_path: depth = 6
   3.077621	hid_lookup_usage: UPS -> 00840004
   3.077622	hid_lookup_usage: OutletSystem -> 00840018
   3.077624	hid_lookup_usage: Outlet -> 00840020
   3.077626	hid_lookup_usage: [3] -> not found in lookup table
   3.077629	hid_lookup_usage: RemainingCapacityLimit -> 00850029
   3.077629	string_to_path: depth = 5
   3.077631	hid_lookup_usage: UPS -> 00840004
   3.077632	hid_lookup_usage: OutletSystem -> 00840018
   3.077634	hid_lookup_usage: Outlet -> 00840020
   3.077636	hid_lookup_usage: [3] -> not found in lookup table
   3.077637	hid_lookup_usage: ShutdownTimer -> ffff005d
   3.077638	string_to_path: depth = 5
   3.077640	hid_lookup_usage: UPS -> 00840004
   3.077641	hid_lookup_usage: OutletSystem -> 00840018
   3.077643	hid_lookup_usage: Outlet -> 00840020
   3.077645	hid_lookup_usage: [3] -> not found in lookup table
   3.077646	hid_lookup_usage: StartupTimer -> ffff005e
   3.077647	string_to_path: depth = 5
   3.077649	hid_lookup_usage: UPS -> 00840004
   3.077650	hid_lookup_usage: OutletSystem -> 00840018
   3.077652	hid_lookup_usage: Outlet -> 00840020
   3.077654	hid_lookup_usage: [3] -> not found in lookup table
   3.077656	hid_lookup_usage: ApparentPower -> 00840033
   3.077656	string_to_path: depth = 5
   3.077658	hid_lookup_usage: UPS -> 00840004
   3.077659	hid_lookup_usage: OutletSystem -> 00840018
   3.077661	hid_lookup_usage: Outlet -> 00840020
   3.077663	hid_lookup_usage: [3] -> not found in lookup table
   3.077665	hid_lookup_usage: ActivePower -> 00840034
   3.077666	string_to_path: depth = 5
   3.077667	hid_lookup_usage: UPS -> 00840004
   3.077669	hid_lookup_usage: OutletSystem -> 00840018
   3.077670	hid_lookup_usage: Outlet -> 00840020
   3.077673	hid_lookup_usage: [3] -> not found in lookup table
   3.077674	hid_lookup_usage: Current -> 00840031
   3.077675	string_to_path: depth = 5
   3.077677	hid_lookup_usage: UPS -> 00840004
   3.077678	hid_lookup_usage: OutletSystem -> 00840018
   3.077680	hid_lookup_usage: Outlet -> 00840020
   3.077682	hid_lookup_usage: [3] -> not found in lookup table
   3.077683	hid_lookup_usage: PowerFactor -> ffff0069
   3.077684	string_to_path: depth = 5
   3.077686	hid_lookup_usage: UPS -> 00840004
   3.077687	hid_lookup_usage: BatterySystem -> 00840010
   3.077689	hid_lookup_usage: Battery -> 00840012
   3.077691	hid_lookup_usage: Test -> 00840058
   3.077691	string_to_path: depth = 4
   3.077692	Report[buf]: (2 bytes) => 24 06
   3.077693	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.077694	Unit = 00000000, UnitExp = 0
   3.077695	Exponent = 0
   3.077696	Path: UPS.BatterySystem.Battery.Test, Type: Feature, ReportID: 0x24, Offset: 0, Size: 8, Value: 6
   3.077696	send_to_all: ADDCMD test.battery.start.quick
   3.077698	hid_lookup_usage: UPS -> 00840004
   3.077700	hid_lookup_usage: BatterySystem -> 00840010
   3.077701	hid_lookup_usage: Battery -> 00840012
   3.077703	hid_lookup_usage: Test -> 00840058
   3.077703	string_to_path: depth = 4
   3.077704	Report[buf]: (2 bytes) => 24 06
   3.077705	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.077706	Unit = 00000000, UnitExp = 0
   3.077706	Exponent = 0
   3.077707	Path: UPS.BatterySystem.Battery.Test, Type: Feature, ReportID: 0x24, Offset: 0, Size: 8, Value: 6
   3.077708	send_to_all: ADDCMD test.battery.start.deep
   3.077710	hid_lookup_usage: UPS -> 00840004
   3.077711	hid_lookup_usage: BatterySystem -> 00840010
   3.077713	hid_lookup_usage: Battery -> 00840012
   3.077714	hid_lookup_usage: Test -> 00840058
   3.077715	string_to_path: depth = 4
   3.077716	Report[buf]: (2 bytes) => 24 06
   3.077717	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.077717	Unit = 00000000, UnitExp = 0
   3.077718	Exponent = 0
   3.077719	Path: UPS.BatterySystem.Battery.Test, Type: Feature, ReportID: 0x24, Offset: 0, Size: 8, Value: 6
   3.077720	send_to_all: ADDCMD test.battery.stop
   3.077721	hid_lookup_usage: UPS -> 00840004
   3.077723	hid_lookup_usage: PowerSummary -> 00840024
   3.077725	hid_lookup_usage: DelayBeforeShutdown -> 00840057
   3.077725	string_to_path: depth = 3
   3.077727	Report[buf]: (5 bytes) => 09 ff ff ff ff
   3.077728	PhyMax = 0, PhyMin = 0, LogMax = 2147483647, LogMin = -1
   3.077728	Unit = 00001001, UnitExp = 0
   3.077729	Exponent = 0
   3.077730	Path: UPS.PowerSummary.DelayBeforeShutdown, Type: Feature, ReportID: 0x09, Offset: 0, Size: 32, Value: 0
   3.077731	send_to_all: ADDCMD load.off.delay
   3.077732	hid_lookup_usage: UPS -> 00840004
   3.077734	hid_lookup_usage: PowerSummary -> 00840024
   3.077736	hid_lookup_usage: DelayBeforeStartup -> 00840056
   3.077736	string_to_path: depth = 3
   3.077738	Report[buf]: (5 bytes) => 0a ff ff ff ff
   3.077738	PhyMax = 0, PhyMin = 0, LogMax = 2147483647, LogMin = -1
   3.077739	Unit = 00001001, UnitExp = 0
   3.077740	Exponent = 0
   3.077741	Path: UPS.PowerSummary.DelayBeforeStartup, Type: Feature, ReportID: 0x0a, Offset: 0, Size: 32, Value: 0
   3.077741	send_to_all: ADDCMD load.on.delay
   3.077744	hid_lookup_usage: UPS -> 00840004
   3.077746	hid_lookup_usage: PowerSummary -> 00840024
   3.077749	hid_lookup_usage: DelayBeforeShutdown -> 00840057
   3.077751	string_to_path: depth = 3
   3.077753	Report[buf]: (5 bytes) => 09 ff ff ff ff
   3.077755	PhyMax = 0, PhyMin = 0, LogMax = 2147483647, LogMin = -1
   3.077756	Unit = 00001001, UnitExp = 0
   3.077757	Exponent = 0
   3.077758	Path: UPS.PowerSummary.DelayBeforeShutdown, Type: Feature, ReportID: 0x09, Offset: 0, Size: 32, Value: 0
   3.077759	send_to_all: ADDCMD shutdown.stop
   3.077762	hid_lookup_usage: UPS -> 00840004
   3.077765	hid_lookup_usage: PowerSummary -> 00840024
   3.077769	hid_lookup_usage: DelayBeforeReboot -> 00840055
   3.077770	string_to_path: depth = 3
   3.077773	hid_lookup_usage: UPS -> 00840004
   3.077776	hid_lookup_usage: PowerSummary -> 00840024
   3.077779	hid_lookup_usage: AudibleAlarmControl -> 0084005a
   3.077781	string_to_path: depth = 3
   3.077783	Report[buf]: (2 bytes) => 13 02
   3.077784	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.077785	Unit = 00000000, UnitExp = 0
   3.077787	Exponent = 0
   3.077788	Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, ReportID: 0x13, Offset: 0, Size: 8, Value: 2
   3.077790	send_to_all: ADDCMD beeper.off
   3.077793	hid_lookup_usage: UPS -> 00840004
   3.077795	hid_lookup_usage: PowerSummary -> 00840024
   3.077798	hid_lookup_usage: AudibleAlarmControl -> 0084005a
   3.077800	string_to_path: depth = 3
   3.077801	Report[buf]: (2 bytes) => 13 02
   3.077803	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.077803	Unit = 00000000, UnitExp = 0
   3.077804	Exponent = 0
   3.077806	Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, ReportID: 0x13, Offset: 0, Size: 8, Value: 2
   3.077808	send_to_all: ADDCMD beeper.on
   3.077810	hid_lookup_usage: UPS -> 00840004
   3.077813	hid_lookup_usage: PowerSummary -> 00840024
   3.077816	hid_lookup_usage: AudibleAlarmControl -> 0084005a
   3.077817	string_to_path: depth = 3
   3.077819	Report[buf]: (2 bytes) => 13 02
   3.077821	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.077822	Unit = 00000000, UnitExp = 0
   3.077823	Exponent = 0
   3.077824	Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, ReportID: 0x13, Offset: 0, Size: 8, Value: 2
   3.077825	send_to_all: ADDCMD beeper.mute
   3.077827	hid_lookup_usage: UPS -> 00840004
   3.077828	hid_lookup_usage: PowerSummary -> 00840024
   3.077830	hid_lookup_usage: AudibleAlarmControl -> 0084005a
   3.077831	string_to_path: depth = 3
   3.077832	Report[buf]: (2 bytes) => 13 02
   3.077833	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.077833	Unit = 00000000, UnitExp = 0
   3.077834	Exponent = 0
   3.077835	Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, ReportID: 0x13, Offset: 0, Size: 8, Value: 2
   3.077836	send_to_all: ADDCMD beeper.disable
   3.077837	hid_lookup_usage: UPS -> 00840004
   3.077839	hid_lookup_usage: PowerSummary -> 00840024
   3.077841	hid_lookup_usage: AudibleAlarmControl -> 0084005a
   3.077841	string_to_path: depth = 3
   3.077842	Report[buf]: (2 bytes) => 13 02
   3.077843	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.077843	Unit = 00000000, UnitExp = 0
   3.077845	Exponent = 0
   3.077846	Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, ReportID: 0x13, Offset: 0, Size: 8, Value: 2
   3.077846	send_to_all: ADDCMD beeper.enable
   3.077848	hid_lookup_usage: UPS -> 00840004
   3.077850	hid_lookup_usage: OutletSystem -> 00840018
   3.077851	hid_lookup_usage: Outlet -> 00840020
   3.077854	hid_lookup_usage: [2] -> not found in lookup table
   3.077856	hid_lookup_usage: DelayBeforeShutdown -> 00840057
   3.077856	string_to_path: depth = 5
   3.077858	hid_lookup_usage: UPS -> 00840004
   3.077859	hid_lookup_usage: OutletSystem -> 00840018
   3.077861	hid_lookup_usage: Outlet -> 00840020
   3.077863	hid_lookup_usage: [2] -> not found in lookup table
   3.077865	hid_lookup_usage: DelayBeforeStartup -> 00840056
   3.077866	string_to_path: depth = 5
   3.077867	hid_lookup_usage: UPS -> 00840004
   3.077869	hid_lookup_usage: OutletSystem -> 00840018
   3.077871	hid_lookup_usage: Outlet -> 00840020
   3.077873	hid_lookup_usage: [3] -> not found in lookup table
   3.077875	hid_lookup_usage: DelayBeforeShutdown -> 00840057
   3.077875	string_to_path: depth = 5
   3.077877	hid_lookup_usage: UPS -> 00840004
   3.077878	hid_lookup_usage: OutletSystem -> 00840018
   3.077880	hid_lookup_usage: Outlet -> 00840020
   3.077882	hid_lookup_usage: [3] -> not found in lookup table
   3.077884	hid_lookup_usage: DelayBeforeStartup -> 00840056
   3.077885	string_to_path: depth = 5
   3.077888	send_to_all: ADDCMD load.off
   3.077890	send_to_all: ADDCMD load.on
   3.077893	send_to_all: ADDCMD shutdown.return
   3.077894	send_to_all: ADDCMD shutdown.stayoff
   3.077896	send_to_all: SETINFO device.type "ups"
   3.077897	send_to_all: SETINFO driver.version "2.7.4"
   3.077898	send_to_all: SETINFO driver.version.internal "0.41"
   3.077899	send_to_all: SETINFO driver.name "usbhid-ups"
   3.077900	upsdrv_initinfo...
   3.077901	send_to_all: SETINFO driver.version.data "MGE HID 1.40"
   3.077902	send_to_all: SETINFO driver.parameter.pollfreq "30"
   3.077903	upsdrv_updateinfo...
   3.162546	Report[int]: (4 bytes) => 06 64 89 13
   3.162550	Got 2 HID objects...
   3.162552	Report[buf]: (4 bytes) => 06 64 89 13
   3.162554	PhyMax = 0, PhyMin = 0, LogMax = 100, LogMin = 0
   3.162555	Unit = 00000000, UnitExp = 0
   3.162557	Exponent = 0
   3.162559	hid_lookup_path: 00840004 -> UPS
   3.162562	hid_lookup_path: 00840024 -> PowerSummary
   3.162564	hid_lookup_path: 00850066 -> RemainingCapacity
   3.162566	Path: UPS.PowerSummary.RemainingCapacity, Type: Input, ReportID: 0x06, Offset: 0, Size: 8, Value: 100
   3.162570	Report[buf]: (4 bytes) => 06 64 89 13
   3.162573	PhyMax = 0, PhyMin = 0, LogMax = 32767, LogMin = 0
   3.162575	Unit = 00001001, UnitExp = 0
   3.162576	Exponent = 0
   3.162578	hid_lookup_path: 00840004 -> UPS
   3.162579	hid_lookup_path: 00840024 -> PowerSummary
   3.162581	hid_lookup_path: 00850068 -> RunTimeToEmpty
   3.162584	Path: UPS.PowerSummary.RunTimeToEmpty, Type: Input, ReportID: 0x06, Offset: 8, Size: 16, Value: 5001
   3.162589	send_to_all: SETINFO battery.runtime "5001"
   3.162591	Quick update...
   3.162594	Report[buf]: (5 bytes) => 0a ff ff ff ff
   3.162597	PhyMax = 0, PhyMin = 0, LogMax = 2147483647, LogMin = -1
   3.162599	Unit = 00001001, UnitExp = 0
   3.162601	Exponent = 0
   3.162604	Path: UPS.PowerSummary.DelayBeforeStartup, Type: Feature, ReportID: 0x0a, Offset: 0, Size: 32, Value: 0
   3.162607	Report[buf]: (5 bytes) => 09 ff ff ff ff
   3.162609	PhyMax = 0, PhyMin = 0, LogMax = 2147483647, LogMin = -1
   3.162611	Unit = 00001001, UnitExp = 0
   3.162613	Exponent = 0
   3.162615	Path: UPS.PowerSummary.DelayBeforeShutdown, Type: Feature, ReportID: 0x09, Offset: 0, Size: 32, Value: 0
   3.162619	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.162621	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.162623	Unit = 00000000, UnitExp = 0
   3.162625	Exponent = 0
   3.162628	Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 1
   3.162629	hu_find_infoval: found online (value: 1)
   3.162631	process_boolean_info: online
   3.162634	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.162636	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.162638	Unit = 00000000, UnitExp = 0
   3.162640	Exponent = 0
   3.162642	Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Feature, ReportID: 0x01, Offset: 24, Size: 8, Value: 0
   3.162644	process_boolean_info: !dischrg
   3.162647	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.162650	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.162651	Unit = 00000000, UnitExp = 0
   3.162653	Exponent = 0
   3.162655	Path: UPS.PowerSummary.PresentStatus.Charging, Type: Feature, ReportID: 0x01, Offset: 16, Size: 8, Value: 1
   3.162657	process_boolean_info: !chrg
   3.162660	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.162662	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.162663	Unit = 00000000, UnitExp = 0
   3.162665	Exponent = 0
   3.162667	Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x01, Offset: 8, Size: 8, Value: 0
   3.162668	hu_find_infoval: found !lowbatt (value: 0)
   3.162670	process_boolean_info: !lowbatt
   3.162674	send_to_all: SETINFO ups.status "OL"
   3.162676	send_to_all: DATAOK
   3.162704	dstate_init: sock /run/nut/usbhid-ups-ups0 open on fd 5
   3.162708	send_to_all: SETINFO driver.parameter.pollinterval "2"
   3.162710	send_to_all: SETINFO driver.parameter.synchronous "no"
   3.162712	send_to_all: SETINFO device.mfr "PPC"
   3.162715	send_to_all: SETINFO device.model "Offline UPS HID UPS"
   3.162717	send_to_all: SETINFO device.serial "000000000   "
   3.162718	upsdrv_updateinfo...
   3.354550	Report[int]: (4 bytes) => 06 64 7d 14
   3.354556	Got 2 HID objects...
   3.354558	Report[buf]: (4 bytes) => 06 64 7d 14
   3.354560	PhyMax = 0, PhyMin = 0, LogMax = 100, LogMin = 0
   3.354562	Unit = 00000000, UnitExp = 0
   3.354563	Exponent = 0
   3.354565	hid_lookup_path: 00840004 -> UPS
   3.354567	hid_lookup_path: 00840024 -> PowerSummary
   3.354569	hid_lookup_path: 00850066 -> RemainingCapacity
   3.354572	Path: UPS.PowerSummary.RemainingCapacity, Type: Input, ReportID: 0x06, Offset: 0, Size: 8, Value: 100
   3.354575	Report[buf]: (4 bytes) => 06 64 7d 14
   3.354577	PhyMax = 0, PhyMin = 0, LogMax = 32767, LogMin = 0
   3.354578	Unit = 00001001, UnitExp = 0
   3.354580	Exponent = 0
   3.354581	hid_lookup_path: 00840004 -> UPS
   3.354583	hid_lookup_path: 00840024 -> PowerSummary
   3.354584	hid_lookup_path: 00850068 -> RunTimeToEmpty
   3.354587	Path: UPS.PowerSummary.RunTimeToEmpty, Type: Input, ReportID: 0x06, Offset: 8, Size: 16, Value: 5245
   3.354590	send_to_all: SETINFO battery.runtime "5245"
   3.354593	Quick update...
   3.354597	Report[buf]: (5 bytes) => 0a ff ff ff ff
   3.354600	PhyMax = 0, PhyMin = 0, LogMax = 2147483647, LogMin = -1
   3.354601	Unit = 00001001, UnitExp = 0
   3.354603	Exponent = 0
   3.354606	Path: UPS.PowerSummary.DelayBeforeStartup, Type: Feature, ReportID: 0x0a, Offset: 0, Size: 32, Value: 0
   3.354610	Report[buf]: (5 bytes) => 09 ff ff ff ff
   3.354613	PhyMax = 0, PhyMin = 0, LogMax = 2147483647, LogMin = -1
   3.354615	Unit = 00001001, UnitExp = 0
   3.354617	Exponent = 0
   3.354619	Path: UPS.PowerSummary.DelayBeforeShutdown, Type: Feature, ReportID: 0x09, Offset: 0, Size: 32, Value: 0
   3.354622	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.354623	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.354625	Unit = 00000000, UnitExp = 0
   3.354626	Exponent = 0
   3.354628	Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 1
   3.354629	hu_find_infoval: found online (value: 1)
   3.354631	process_boolean_info: online
   3.354633	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.354634	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.354636	Unit = 00000000, UnitExp = 0
   3.354637	Exponent = 0
   3.354639	Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Feature, ReportID: 0x01, Offset: 24, Size: 8, Value: 0
   3.354640	process_boolean_info: !dischrg
   3.354642	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.354644	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.354646	Unit = 00000000, UnitExp = 0
   3.354648	Exponent = 0
   3.354651	Path: UPS.PowerSummary.PresentStatus.Charging, Type: Feature, ReportID: 0x01, Offset: 16, Size: 8, Value: 1
   3.354653	process_boolean_info: !chrg
   3.354657	Report[buf]: (8 bytes) => 01 01 00 01 00 01 00 00
   3.354658	PhyMax = 0, PhyMin = 0, LogMax = 255, LogMin = 0
   3.354659	Unit = 00000000, UnitExp = 0
   3.354661	Exponent = 0
   3.354663	Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x01, Offset: 8, Size: 8, Value: 0
   3.354666	hu_find_infoval: found !lowbatt (value: 0)
   3.354668	process_boolean_info: !lowbatt
...

lsusb -v -d 06da:ffff:

Bus 001 Device 002: ID 06da:ffff Phoenixtec Power Co., Ltd Offline UPS
Device Descriptor:
  bLength                18
  bDescriptorType         1
  bcdUSB               1.10
  bDeviceClass            0 
  bDeviceSubClass         0 
  bDeviceProtocol         0 
  bMaxPacketSize0         8
  idVendor           0x06da Phoenixtec Power Co., Ltd
  idProduct          0xffff 
  bcdDevice            0.03
  iManufacturer           1 PPC
  iProduct                2 Offline UPS
  iSerial                 4 000000000   
  bNumConfigurations      1
  Configuration Descriptor:
    bLength                 9
    bDescriptorType         2
    wTotalLength       0x0022
    bNumInterfaces          1
    bConfigurationValue     1
    iConfiguration          0 
    bmAttributes         0xa0
      (Bus Powered)
      Remote Wakeup
    MaxPower              100mA
    Interface Descriptor:
      bLength                 9
      bDescriptorType         4
      bInterfaceNumber        0
      bAlternateSetting       0
      bNumEndpoints           1
      bInterfaceClass         3 Human Interface Device
      bInterfaceSubClass      0 
      bInterfaceProtocol      0 
      iInterface              0 
        HID Device Descriptor:
          bLength                 9
          bDescriptorType        33
          bcdHID               1.00
          bCountryCode            0 Not supported
          bNumDescriptors         1
          bDescriptorType        34 Report
          wDescriptorLength     495
          Report Descriptor: (length is 495)
            Item(Global): Usage Page, data= [ 0x84 ] 132
                            Power Device Page
            Item(Local ): Usage, data= [ 0x04 ] 4
                            UPS
            Item(Main  ): Collection, data= [ 0x01 ] 1
                            Application
            Item(Local ): Usage, data= [ 0x10 ] 16
                            Battery System
            Item(Main  ): Collection, data= [ 0x00 ] 0
                            Physical
            Item(Local ): Usage, data= [ 0x12 ] 18
                            Battery
            Item(Main  ): Collection, data= [ 0x00 ] 0
                            Physical
            Item(Global): Usage Page, data= [ 0x84 ] 132
                            Power Device Page
            Item(Local ): Usage, data= [ 0x58 ] 88
                            Test
            Item(Global): Report ID, data= [ 0x24 ] 36
            Item(Global): Report Size, data= [ 0x08 ] 8
            Item(Global): Report Count, data= [ 0x01 ] 1
            Item(Global): Unit, data= [ 0x00 ] 0
                            System: None, Unit: (None)
            Item(Global): Logical Minimum, data= [ 0x00 ] 0
            Item(Global): Logical Maximum, data= [ 0xff 0x00 ] 255
            Item(Global): Unit Exponent, data= [ 0x00 ] 0
                            Unit Exponent: 0
            Item(Main  ): Feature, data= [ 0x82 ] 130
                            Data Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Main  ): End Collection, data=none
            Item(Main  ): End Collection, data=none
            Item(Local ): Usage, data= [ 0x1e ] 30
                            Flow
            Item(Main  ): Collection, data= [ 0x84 ] 132
                            Vendor defined
            Item(Local ): Usage, data= [ 0x43 ] 67
                            Config Apparent Power
            Item(Global): Report ID, data= [ 0x74 ] 116
            Item(Global): Report Size, data= [ 0x10 ] 16
            Item(Global): Report Count, data= [ 0x01 ] 1
            Item(Global): Logical Minimum, data= [ 0x00 ] 0
            Item(Global): Logical Maximum, data= [ 0xff 0xff 0x00 0x00 ] 65535
            Item(Global): Unit, data= [ 0x21 0xd1 ] 53537
                            System: SI Linear, Unit: Centimeter^2*Gram*Seconds^-3
            Item(Global): Unit Exponent, data= [ 0x07 ] 7
                            Unit Exponent: 7
            Item(Main  ): Feature, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Local ): Usage, data= [ 0x42 ] 66
                            Config Frequency
            Item(Global): Report ID, data= [ 0x36 ] 54
            Item(Global): Report Size, data= [ 0x08 ] 8
            Item(Global): Logical Maximum, data= [ 0xff 0x00 ] 255
            Item(Global): Unit, data= [ 0x01 0xf0 ] 61441
                            System: SI Linear, Unit: Seconds^-1
            Item(Global): Unit Exponent, data= [ 0x00 ] 0
                            Unit Exponent: 0
            Item(Main  ): Feature, data= [ 0x82 ] 130
                            Data Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Local ): Usage, data= [ 0x40 ] 64
                            Config Voltage
            Item(Global): Report ID, data= [ 0x72 ] 114
            Item(Global): Unit, data= [ 0x21 0xd1 0xf0 0x00 ] 15782177
                            System: SI Linear, Unit: Centimeter^2*Gram*Seconds^-3*Ampere^-1
            Item(Global): Unit Exponent, data= [ 0x07 ] 7
                            Unit Exponent: 7
            Item(Main  ): Feature, data= [ 0x82 ] 130
                            Data Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Main  ): End Collection, data=none
            Item(Local ): Usage, data= [ 0x16 ] 22
                            Power Converter
            Item(Main  ): Collection, data= [ 0x00 ] 0
                            Physical
            Item(Global): Usage Page, data= [ 0xff 0xff ] 65535
                            (null)
            Item(Local ): Usage, data= [ 0x41 ] 65
                            (null)
            Item(Global): Report ID, data= [ 0x4a ] 74
            Item(Global): Unit, data= [ 0x00 ] 0
                            System: None, Unit: (None)
            Item(Global): Unit Exponent, data= [ 0x00 ] 0
                            Unit Exponent: 0
            Item(Main  ): Feature, data= [ 0x03 ] 3
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Non_Volatile Bitfield
            Item(Global): Usage Page, data= [ 0x84 ] 132
                            Power Device Page
            Item(Local ): Usage, data= [ 0x1a ] 26
                            Input
            Item(Main  ): Collection, data= [ 0x81 ] 129
                            Vendor defined
            Item(Global): Usage Page, data= [ 0x84 ] 132
                            Power Device Page
            Item(Local ): Usage, data= [ 0x30 ] 48
                            Voltage
            Item(Global): Report ID, data= [ 0x31 ] 49
            Item(Global): Report Size, data= [ 0x10 ] 16
            Item(Global): Logical Maximum, data= [ 0xff 0xff 0x00 0x00 ] 65535
            Item(Global): Unit, data= [ 0x21 0xd1 0xf0 0x00 ] 15782177
                            System: SI Linear, Unit: Centimeter^2*Gram*Seconds^-3*Ampere^-1
            Item(Global): Unit Exponent, data= [ 0x07 ] 7
                            Unit Exponent: 7
            Item(Main  ): Feature, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Local ): Usage, data= [ 0x02 ] 2
                            Present Status
            Item(Main  ): Collection, data= [ 0x02 ] 2
                            Logical
            Item(Local ): Usage, data= [ 0x6e ] 110
                            Boost
            Item(Global): Report ID, data= [ 0x2d ] 45
            Item(Global): Report Size, data= [ 0x08 ] 8
            Item(Global): Logical Maximum, data= [ 0xff 0x00 ] 255
            Item(Global): Unit, data= [ 0x00 ] 0
                            System: None, Unit: (None)
            Item(Global): Unit Exponent, data= [ 0x00 ] 0
                            Unit Exponent: 0
            Item(Main  ): Feature, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Local ): Usage, data= [ 0x6e ] 110
                            Boost
            Item(Main  ): Input, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Local ): Usage, data= [ 0x6f ] 111
                            Buck
            Item(Main  ): Feature, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Local ): Usage, data= [ 0x6f ] 111
                            Buck
            Item(Main  ): Input, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Main  ): End Collection, data=none
            Item(Main  ): End Collection, data=none
            Item(Global): Usage Page, data= [ 0x84 ] 132
                            Power Device Page
            Item(Local ): Usage, data= [ 0x1c ] 28
                            Output
            Item(Main  ): Collection, data= [ 0x00 ] 0
                            Physical
            Item(Global): Usage Page, data= [ 0x84 ] 132
                            Power Device Page
            Item(Local ): Usage, data= [ 0x32 ] 50
                            Frequency
            Item(Global): Report ID, data= [ 0x42 ] 66
            Item(Global): Report Size, data= [ 0x10 ] 16
            Item(Global): Logical Maximum, data= [ 0xff 0xff 0x00 0x00 ] 65535
            Item(Global): Unit, data= [ 0x01 0xf0 ] 61441
                            System: SI Linear, Unit: Seconds^-1
            Item(Global): Unit Exponent, data= [ 0x0f ] 15
                            Unit Exponent: 15
            Item(Main  ): Feature, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Global): Usage Page, data= [ 0x84 ] 132
                            Power Device Page
            Item(Local ): Usage, data= [ 0x30 ] 48
                            Voltage
            Item(Global): Report ID, data= [ 0x42 ] 66
            Item(Global): Report Size, data= [ 0x10 ] 16
            Item(Global): Logical Maximum, data= [ 0xff 0xff 0x00 0x00 ] 65535
            Item(Global): Unit, data= [ 0x21 0xd1 0xf0 0x00 ] 15782177
                            System: SI Linear, Unit: Centimeter^2*Gram*Seconds^-3*Ampere^-1
            Item(Global): Unit Exponent, data= [ 0x07 ] 7
                            Unit Exponent: 7
            Item(Main  ): Feature, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Main  ): End Collection, data=none
            Item(Main  ): End Collection, data=none
            Item(Local ): Usage, data= [ 0x24 ] 36
                            Power Summary
            Item(Main  ): Collection, data= [ 0x00 ] 0
                            Physical
            Item(Local ): Usage, data= [ 0x5a ] 90
                            Audible Alarm Control
            Item(Global): Report ID, data= [ 0x13 ] 19
            Item(Global): Report Size, data= [ 0x08 ] 8
            Item(Global): Logical Minimum, data= [ 0x00 ] 0
            Item(Global): Logical Maximum, data= [ 0xff 0x00 ] 255
            Item(Global): Unit, data= [ 0x00 ] 0
                            System: None, Unit: (None)
            Item(Global): Unit Exponent, data= [ 0x00 ] 0
                            Unit Exponent: 0
            Item(Main  ): Feature, data= [ 0x82 ] 130
                            Data Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Global): Usage Page, data= [ 0x84 ] 132
                            Power Device Page
            Item(Local ): Usage, data= [ 0x57 ] 87
                            Delay Before Shutdown
            Item(Global): Report ID, data= [ 0x09 ] 9
            Item(Global): Report Size, data= [ 0x20 ] 32
            Item(Global): Logical Minimum, data= [ 0xff ] 255
            Item(Global): Logical Maximum, data= [ 0xff 0xff 0xff 0x7f ] 2147483647
            Item(Global): Unit, data= [ 0x01 0x10 ] 4097
                            System: SI Linear, Unit: Seconds
            Item(Main  ): Feature, data= [ 0x82 ] 130
                            Data Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Local ): Usage, data= [ 0x56 ] 86
                            Delay Before Startup
            Item(Global): Report ID, data= [ 0x0a ] 10
            Item(Main  ): Feature, data= [ 0x82 ] 130
                            Data Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Global): Usage Page, data= [ 0x85 ] 133
                            Battery System Page
            Item(Local ): Usage, data= [ 0x89 ] 137
                            iDeviceChemistry
            Item(Global): Report ID, data= [ 0x10 ] 16
            Item(Global): Report Size, data= [ 0x08 ] 8
            Item(Global): Logical Minimum, data= [ 0x00 ] 0
            Item(Global): Logical Maximum, data= [ 0xff 0x00 ] 255
            Item(Global): Unit, data= [ 0x00 ] 0
                            System: None, Unit: (None)
            Item(Main  ): Feature, data= [ 0x03 ] 3
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Non_Volatile Bitfield
            Item(Global): Usage Page, data= [ 0x84 ] 132
                            Power Device Page
            Item(Local ): Usage, data= [ 0xfd ] 253
                            iManufacturer
            Item(Main  ): Feature, data= [ 0x03 ] 3
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Non_Volatile Bitfield
            Item(Global): Usage Page, data= [ 0xff 0xff ] 65535
                            (null)
            Item(Local ): Usage, data= [ 0xf0 ] 240
                            (null)
            Item(Main  ): Feature, data= [ 0x03 ] 3
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Non_Volatile Bitfield
            Item(Global): Usage Page, data= [ 0x84 ] 132
                            Power Device Page
            Item(Local ): Usage, data= [ 0xfe ] 254
                            iProduct
            Item(Main  ): Feature, data= [ 0x03 ] 3
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Non_Volatile Bitfield
            Item(Global): Usage Page, data= [ 0x84 ] 132
                            Power Device Page
            Item(Local ): Usage, data= [ 0xff ] 255
                            iSerialNumber
            Item(Main  ): Feature, data= [ 0x03 ] 3
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Non_Volatile Bitfield
            Item(Global): Usage Page, data= [ 0xff 0xff ] 65535
                            (null)
            Item(Local ): Usage, data= [ 0xe2 ] 226
                            (null)
            Item(Global): Report ID, data= [ 0xe2 ] 226
            Item(Main  ): Feature, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Global): Usage Page, data= [ 0x84 ] 132
                            Power Device Page
            Item(Local ): Usage, data= [ 0x35 ] 53
                            Percent Load
            Item(Global): Report ID, data= [ 0x07 ] 7
            Item(Global): Logical Minimum, data= [ 0x00 ] 0
            Item(Global): Logical Maximum, data= [ 0xff 0x00 ] 255
            Item(Global): Unit, data= [ 0x00 ] 0
                            System: None, Unit: (None)
            Item(Main  ): Feature, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Global): Usage Page, data= [ 0x84 ] 132
                            Power Device Page
            Item(Local ): Usage, data= [ 0x02 ] 2
                            Present Status
            Item(Main  ): Collection, data= [ 0x02 ] 2
                            Logical
            Item(Global): Usage Page, data= [ 0x85 ] 133
                            Battery System Page
            Item(Local ): Usage, data= [ 0xd0 ] 208
                            AC Present
            Item(Global): Report ID, data= [ 0x01 ] 1
            Item(Global): Report Size, data= [ 0x08 ] 8
            Item(Main  ): Feature, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Local ): Usage, data= [ 0xd0 ] 208
                            AC Present
            Item(Main  ): Input, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Local ): Usage, data= [ 0x42 ] 66
                            Below Remaining Capacity Limit
            Item(Main  ): Feature, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Local ): Usage, data= [ 0x42 ] 66
                            Below Remaining Capacity Limit
            Item(Main  ): Input, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Local ): Usage, data= [ 0x44 ] 68
                            Charging
            Item(Main  ): Feature, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Local ): Usage, data= [ 0x44 ] 68
                            Charging
            Item(Main  ): Input, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Global): Usage Page, data= [ 0x85 ] 133
                            Battery System Page
            Item(Local ): Usage, data= [ 0x45 ] 69
                            Discharging
            Item(Main  ): Feature, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Local ): Usage, data= [ 0x45 ] 69
                            Discharging
            Item(Main  ): Input, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Global): Usage Page, data= [ 0x84 ] 132
                            Power Device Page
            Item(Local ): Usage, data= [ 0x61 ] 97
                            Good
            Item(Main  ): Feature, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Local ): Usage, data= [ 0x61 ] 97
                            Good
            Item(Main  ): Input, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Local ): Usage, data= [ 0x62 ] 98
                            Internal Failure
            Item(Main  ): Feature, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Local ): Usage, data= [ 0x62 ] 98
                            Internal Failure
            Item(Main  ): Input, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Global): Usage Page, data= [ 0x84 ] 132
                            Power Device Page
            Item(Local ): Usage, data= [ 0x65 ] 101
                            Overload
            Item(Main  ): Feature, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Local ): Usage, data= [ 0x65 ] 101
                            Overload
            Item(Main  ): Input, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Main  ): End Collection, data=none
            Item(Global): Usage Page, data= [ 0x85 ] 133
                            Battery System Page
            Item(Global): Report ID, data= [ 0x0b ] 11
            Item(Global): Report Size, data= [ 0x08 ] 8
            Item(Global): Report Count, data= [ 0x01 ] 1
            Item(Global): Logical Minimum, data= [ 0x00 ] 0
            Item(Global): Logical Maximum, data= [ 0x64 ] 100
            Item(Local ): Usage, data= [ 0x83 ] 131
                            Design Capacity
            Item(Main  ): Feature, data= [ 0x03 ] 3
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Non_Volatile Bitfield
            Item(Local ): Usage, data= [ 0x8d ] 141
                            Capacity Granularity 1
            Item(Main  ): Feature, data= [ 0x03 ] 3
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Non_Volatile Bitfield
            Item(Local ): Usage, data= [ 0x67 ] 103
                            Full Charge Capacity
            Item(Global): Unit, data= [ 0x00 ] 0
                            System: None, Unit: (None)
            Item(Main  ): Feature, data= [ 0x03 ] 3
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Non_Volatile Bitfield
            Item(Local ): Usage, data= [ 0x2c ] 44
                            Capacity Mode
            Item(Global): Unit, data= [ 0x00 ] 0
                            System: None, Unit: (None)
            Item(Main  ): Feature, data= [ 0x03 ] 3
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Non_Volatile Bitfield
            Item(Local ): Usage, data= [ 0x66 ] 102
                            Remaining Capacity
            Item(Global): Report ID, data= [ 0x06 ] 6
            Item(Global): Unit, data= [ 0x00 ] 0
                            System: None, Unit: (None)
            Item(Main  ): Feature, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Local ): Usage, data= [ 0x66 ] 102
                            Remaining Capacity
            Item(Main  ): Input, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Global): Usage Page, data= [ 0x85 ] 133
                            Battery System Page
            Item(Local ): Usage, data= [ 0x68 ] 104
                            Run Time To Empty
            Item(Global): Report ID, data= [ 0x06 ] 6
            Item(Global): Report Size, data= [ 0x10 ] 16
            Item(Global): Logical Maximum, data= [ 0xff 0x7f ] 32767
            Item(Global): Unit, data= [ 0x01 0x10 ] 4097
                            System: SI Linear, Unit: Seconds
            Item(Main  ): Feature, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Local ): Usage, data= [ 0x68 ] 104
                            Run Time To Empty
            Item(Main  ): Input, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Global): Usage Page, data= [ 0x84 ] 132
                            Power Device Page
            Item(Local ): Usage, data= [ 0x30 ] 48
                            Voltage
            Item(Global): Report ID, data= [ 0x07 ] 7
            Item(Global): Report Size, data= [ 0x10 ] 16
            Item(Global): Logical Maximum, data= [ 0xff 0x7f ] 32767
            Item(Global): Unit, data= [ 0x21 0xd1 0xf0 0x00 ] 15782177
                            System: SI Linear, Unit: Centimeter^2*Gram*Seconds^-3*Ampere^-1
            Item(Global): Unit Exponent, data= [ 0x06 ] 6
                            Unit Exponent: 6
            Item(Main  ): Feature, data= [ 0x83 ] 131
                            Constant Variable Absolute No_Wrap Linear
                            Preferred_State No_Null_Position Volatile Bitfield
            Item(Main  ): End Collection, data=none
            Item(Main  ): End Collection, data=none
      Endpoint Descriptor:
        bLength                 7
        bDescriptorType         5
        bEndpointAddress     0x81  EP 1 IN
        bmAttributes            3
          Transfer Type            Interrupt
          Synch Type               None
          Usage Type               Data
        wMaxPacketSize     0x0008  1x 8 bytes
        bInterval             100
Device Status:     0x0000
  (Bus Powered)

upsc ups0:

Init SSL without certificate database
battery.charge: 100
battery.runtime: 5245
battery.type: PbAc
device.mfr: PPC
device.model: Offline UPS HID UPS
device.serial: 000000000   
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.parameter.productid: ffff
driver.parameter.synchronous: no
driver.parameter.vendorid: 06da
driver.version: 2.7.4
driver.version.data: MGE HID 1.40
driver.version.internal: 0.41
input.voltage: 231.0
outlet.1.status: on
output.frequency: 49.6
output.frequency.nominal: 50
output.voltage: 231.0
output.voltage.nominal: 230
ups.beeper.status: enabled
ups.delay.shutdown: 20
ups.delay.start: 30
ups.load: 8
ups.mfr: PPC
ups.model: Offline UPS HID UPS
ups.power.nominal: 5
ups.productid: ffff
ups.serial: 000000000   
ups.status: OL
ups.test.result: No test initiated
ups.timer.shutdown: 0
ups.timer.start: 0
ups.type: offline / line interactive
ups.vendorid: 06da

upsrw ups0:

[output.voltage.nominal]
Nominal output voltage (V)
Type: ENUM
Option: "200"
Option: "208"
Option: "220"
Option: "230" SELECTED
Option: "240"

[ups.delay.shutdown]
Interval to wait after shutdown with delay command (seconds)
Type: STRING
Maximum length: 10
Value: 20

[ups.delay.start]
Interval to wait before (re)starting the load (seconds)
Type: STRING
Maximum length: 10
Value: 30

upscmd -l ups0:

Instant commands supported on UPS [ups0]:

beeper.disable - Disable the UPS beeper
beeper.enable - Enable the UPS beeper
beeper.mute - Temporarily mute the UPS beeper
beeper.off - Obsolete (use beeper.disable or beeper.mute)
beeper.on - Obsolete (use beeper.enable)
load.off - Turn off the load immediately
load.off.delay - Turn off the load with a delay (seconds)
load.on - Turn on the load immediately
load.on.delay - Turn on the load with a delay (seconds)
shutdown.return - Turn off the load and return when power is back
shutdown.stayoff - Turn off the load and remain off
shutdown.stop - Stop a shutdown in progress
test.battery.start.deep - Start a deep battery test
test.battery.start.quick - Start a quick battery test
test.battery.stop - Stop the battery test

cat /etc/os-release:

PRETTY_NAME="Debian GNU/Linux bookworm/sid"
NAME="Debian GNU/Linux"
...

uname -a:

Linux <REDACTED> 5.15.0-2-amd64 #1 SMP Debian 5.15.5-2 (2021-12-18) x86_64 GNU/Linux

dpkg -l | grep nut:

...
ii  nut                                   2.7.4-14                           all          network UPS tools - metapackage
ii  nut-client                            2.7.4-14                           amd64        network UPS tools - clients
ii  nut-server                            2.7.4-14                           amd64        network UPS tools - core system

Let me know if some more information is needed or if I can help in any other way.

@jimklimov jimklimov added the PowerWalker PowerWalker and BlueWalker branded devices label Apr 25, 2022
Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment
Labels
DDL HCL PowerWalker PowerWalker and BlueWalker branded devices
Projects
Status: Done
Development

No branches or pull requests

2 participants