One sample of each list on the Kamstrup ??? meter

For the data parts, I have found they follow a pattern where the first byte dictates the data type and size: 02 - one byte following 06 - long (4 bytes / 32 bits) 12 - int (2 bytes / 16 bit) 09 - string, first byte is length (could it be a byte array?) 0A - string, first byte is length

List #1 (0x19)

No Data Explaination Value
x E6 E7 00 0F 00 00 00 00 Uknown
0 09 0C 07 E1 0A 14 05 03 2B 1E FF 80 00 00 Date and time 2017-10-20 (fre) 03:43:30
1 02 19 List ID 25 (List 1)
2 0A 0E 4B 61 6D 73 74 72 75 70 5F 56 30 30 30 31 OBIS List Version Identifier Kamstrup_V0001
3 09 06 01 01 00 00 05 FF OBIS for Meter ID 1.1.0.0.5.255
4 0A 10 35 37 30 36 35 36 37 32 37 34 33 38 39 37 30 32 Meter ID 5706567274389702
5 09 06 01 01 60 01 01 FF OBIS for Meter Type 1.1.96.1.1.255
6 0A 12 36 38 34 31 31 32 31 42 4E 32 34 33 31 30 31 30 34 30 Meter Type 6841121BN243101040
7 09 06 01 01 01 07 00 FF OBIS for Active Power + 1.1.1.7.0.255
8 06 00 00 05 BC Active Power + 1468 W
9 09 06 01 01 02 07 00 FF OBIS for Active Power - 1.1.2.7.0.255
10 06 00 00 00 00 Active Power - 0 W
11 09 06 01 01 03 07 00 FF OBIS for Reactive Power + 1.1.3.7.0.255
12 06 00 00 00 00 Reactive Power + 0W
13 09 06 01 01 04 07 00 FF OBIS for Reactive Power - 1.1.4.7.0.255
14 06 00 00 01 CE Reactive Power - 462W
15 09 06 01 01 1F 07 00 FF OBIS for L1 Current 1.1.31.7.0.255
16 06 00 00 02 34 L1 Current 5.64 A
17 09 06 01 01 33 07 00 FF OBIS for L2 Current 1.1.51.7.0.255
18 06 00 00 00 CA L2 Current 2.02 A
19 09 06 01 01 47 07 00 FF OBIS for L3 Current 1.1.71.7.0.255
20 06 00 00 01 FF L3 Current 5.11 A
21 09 06 01 01 20 07 00 FF OBIS for L1 Voltage 1.1.32.7.0.255
22 12 00 E8 L1 Voltage 232 V
23 09 06 01 01 34 07 00 FF OBIS for L2 Voltage 1.1.52.7.0.255
24 12 00 E4 L1 Voltage 228 V
25 09 06 01 01 48 07 00 FF OBIS for L3 Voltage 1.1.72.7.0.255
26 12 00 E9 L1 Voltage 233 V