HWP PMX Agent

Configuration File Examples

Below are configuration examples for the ocs config file and for running the Agent in a docker container.

OCS Site Config

An example site-config-file block:

{'agent-class': 'HWPPMXAgent',
 'instance-id': 'hwp-pmx',
 'arguments': [['--ip', '10.10.10.100'],
               ['--port', '5025'],
               ['--sampling-frequency', 1],
               ['--supervisor-id', 'hwp-supervisor']]},

Docker Compose

An example docker-compose configuration:

ocs-hwp-pmx:
  image: simonsobs/socs:latest
  hostname: ocs-docker
  network_mode: "host"
  environment:
    - INSTANCE_ID=hwp-pmx
    - SITE_HUB=ws://127.0.0.1:8001/ws
    - SITE_HTTP=http://127.0.0.1:8001/call
  volumes:
    - ${OCS_CONFIG_DIR}:/config:ro

Note

Since the Agent container needs network_mode: "host", it must be configured to connect to the crossbar server as if it was on the host system. In this example the crossbar server is running on localhost, 127.0.0.1, but on your network this may be different.

Description

The HWP PMX Agent interfaces with the PMX Kikusui power supply and allows control of the current and voltage that drives the CHWP rotation. The PMX provides several connection options for communicating remotely with the hardware. For the HWP PMX Agent we have written the interface for communication via Ethernet cable.

Protection Mode

The PMX enters protection mode and stops outputting when something harmful occurs. The HWP PMX Agent monitors the state of the protection mode and outputs a protection code and message to prot_code and prot_msg for each data acquisition. There are several possible situations that can cause entering the protection mode. Below is a table showing the protection codes and corresponding situations.

prot_code Description
0 not in protection mode
1 overcurrent protection
2 overvoltage protection
3 AC power failure or power interuption
5 over temperature protection
7 IOC communication error

When the PMX enters the protection mode, the cause must be removed and the protection mode must be deactivated in order to resume output. After removing the cause of the protection, output can be resumed by executing the following API tasks via the HWP PMX Agent:

pmx.clear_alarm()
pmx.set_on()