UPS Agent

The UPS Agent is an OCS Agent which monitors various UPS models via SNMP.

Configuration File Examples

Below are configuration examples for the ocs config file and for running the Agent in a docker container.

OCS Site Config

To configure the UPS Agent we need to add a UPSAgent block to our ocs configuration file. Here is an example configuration block using all of the available arguments:

{'agent-class': 'UPSAgent',
 'instance-id': 'ups',
 'arguments': [['--address', '10.10.10.50'],
               ['--port', 161],
               ['--mode', 'acq'],
               ['--snmp-version', 1],
               ['--restart-time', 60]]},

Note

The --address argument should be the address of the UPS on the network. The --restart-time argument should be set to number of minutes before exiting the agent. Setting to 0 (default) will not exit the agent.

Docker Compose

The UPS Agent should be configured to run in a Docker container. An example docker-compose service configuration is shown here:

ocs-ups:
  image: simonsobs/socs:latest
  hostname: ocs-docker
  network_mode: "host"
  volumes:
    - ${OCS_CONFIG_DIR}:/config:ro
  environment:
    - INSTANCE_ID=ups
    - SITE_HUB=ws://127.0.0.1:8001/ws
    - SITE_HTTP=http://127.0.0.1:8001/call
    - LOGLEVEL=info

The LOGLEVEL environment variable can be used to set the log level for debugging. The default level is "info". If not using HostManager, we must set restart: unless-stopped to automatically restart the docker container.

Description

Various UPS models will be used to power various components on the SO site. The UPS Agent allows the monitoring of a UPS model. It provides information on the manufacturer and model of the UPS. It monitors the state of each output, as well as several stats of the battery. The UPS has an Simple Network Management Protocol (SNMP) interface. The agent has been tested on the following Falcon models: SSG3K-2T, SSG3KRM-2. These models require a SNMP interface add-on card to be installed.

The UPS Agent actively issues SNMP GET commands to request the status from several Object Identifiers (OIDs) specified by the provided Management Information Base (MIB). We sample only a subset of the OIDs defined by the MIB. The MIB has been converted from the original .mib format to a .py format that is consumable via pysnmp and is provided by socs.

Agent Fields

The fields returned by the Agent are built from the SNMP GET responses from the UPS. The field names consist of the OID name and the last value of the OID, which often serves as an index for duplicate pieces of hardware that share a OID string, i.e. outputs on the OID "upsOutputVoltage". This results in field names such as "upsOutputVoltage_0" and "upsOutputVoltage_1".

These queries mostly return integers which map to some state. These integers get decoded into their corresponding string representations and stored in the OCS Agent Process' session.data object. For more details on this structure, see the Agent API below. For information about the states corresponding to these values, refer to the MIB file.

Agent API

socs.agents.ups.agent.UPSAgent

Supporting APIs

socs.agents.ups.agent.update_cache