Multi-Bit Binary Input Record (mbbi)

The normal use for the multi-bit binary input record is to read contiguous, multiple bit inputs from hardware. The binary value represents a state from a range of up to 16 states. The multi-bit input record interfaces with devices that use more than one bit.

Most device support modules obtain values from hardware and place the value in RVAL. For these device support modules record processing uses RVAL to determine the current state (VAL is given a value between 0 and 15). Device support modules may optionally read a value directly into VAL.

Soft device modules are provided to obtain input via database or channel access links or via dbPutField or dbPutLink requests. Two soft device support modules are provided: Soft Channel allows VAL to be an arbitrary unsigned short integer. Raw Soft Channel reads the value into RVAL just like normal device support modules.

Parameter Fields

The record-specific fields are described below, grouped by functionality.

Scan Parameters

The multi-bit binary input record has the standard fields for specifying under what circumstances it will be processed. These fields are listed in Scan Fields.

Read and Convert Parameters

The device support routines obtain the record's input from the device or link specified in the INP field. For records that obtain their input from devices, the INP field must contain the address of the I/O card, and the DTYP field must specify the proper device support module. Be aware that the address format differs according to the I/O bus used.

Two soft device support modules can be specified in DTYP Soft Channel and Raw Soft Channel.

Raw Soft Channel reads the value into RVAL, upon which the normal conversion process is undergone. Soft Channel reads any unsigned integer directly into VAL. For a soft mbbi record, the INP field can be a constant, a database, or a channel access link. If INP is a constant, then the VAL is initialized to the constant value but can be changed at run-time via dbPutField or dbPutLink.

MASK is used by the raw soft channel read routine, and by typical device support read routines, to select only the desired bits when reading the hardware register. It is initialized to ((1 << NOBT) - 1) by record initialization. The user can configure the NOBT field, but the device support routines may set it, in which case the value given to it by the user is simply overridden. The device support routines may also override MASK or shift it left by SHFT bits. If MASK is non-zero, only the bits specified by MASK will appear in RVAL.

Unless the device support routine specifies no conversion, RVAL is used to determine VAL as follows:

  1. RVAL is assigned to a temporary variable -- rval = RVAL
  2. rval is shifted right SHFT number of bits.
  3. A match is sought between rval and one of the state value fields, ZRVL-FFVL.

Each of the fields, ZRVL-FFVL, represents one of the possible sixteen states (not all sixteen have to be used).

Alternatively, the input value can be read as a string, in which case, a match is sought with one of the strings specified in the ZRST-FFST fields. Then RVAL is set equal to the corresponding value for that string, and the conversion process occurs.

Field Summary Type DCT Default Read Write CA PP
VAL Current Value ENUM Yes Yes Yes Yes
INP Input Specification INLINK Yes Yes Yes No
MASK Hardware Mask ULONG No Yes No No
NOBT Number of Bits USHORT Yes Yes No No
RVAL Raw Value ULONG No Yes Yes Yes
SHFT Shift USHORT Yes Yes Yes No
ZRVL Zero Value ULONG Yes Yes Yes Yes
ONVL One Value ULONG Yes Yes Yes Yes
TWVL Two Value ULONG Yes Yes Yes Yes
THVL Three Value ULONG Yes Yes Yes Yes
FRVL Four Value ULONG Yes Yes Yes Yes
FVVL Five Value ULONG Yes Yes Yes Yes
SXVL Six Value ULONG Yes Yes Yes Yes
SVVL Seven Value ULONG Yes Yes Yes Yes
EIVL Eight Value ULONG Yes Yes Yes Yes
NIVL Nine Value ULONG Yes Yes Yes Yes
TEVL Ten Value ULONG Yes Yes Yes Yes
ELVL Eleven Value ULONG Yes Yes Yes Yes
TVVL Twelve Value ULONG Yes Yes Yes Yes
TTVL Thirteen Value ULONG Yes Yes Yes Yes
FTVL Fourteen Value ULONG Yes Yes Yes Yes
FFVL Fifteen Value ULONG Yes Yes Yes Yes

Operator Display Parameters

These parameters are used to present meaningful data to the operator. They display the value and other parameters of the mbbi record either textually or graphically. The ZRST-FFST fields contain strings describing one of the possible states of the record. The get_enum_str and get_enum_strs record routines retrieve these strings for the operator. Get_enum_str gets the string corresponding to the value set in VAL, and get_enum_strs retrieves all the strings.

See Fields Common to All Record Types for more on the record name (NAME) and description (DESC) fields.

Field Summary Type DCT Default Read Write CA PP
NAME Record Name STRING [61] No Yes No No
DESC Descriptor STRING [41] Yes Yes Yes No
ZRST Zero String STRING [26] Yes Yes Yes Yes
ONST One String STRING [26] Yes Yes Yes Yes
TWST Two String STRING [26] Yes Yes Yes Yes
THST Three String STRING [26] Yes Yes Yes Yes
FRST Four String STRING [26] Yes Yes Yes Yes
FVST Five String STRING [26] Yes Yes Yes Yes
SXST Six String STRING [26] Yes Yes Yes Yes
SVST Seven String STRING [26] Yes Yes Yes Yes
EIST Eight String STRING [26] Yes Yes Yes Yes
NIST Nine String STRING [26] Yes Yes Yes Yes
TEST Ten String STRING [26] Yes Yes Yes Yes
ELST Eleven String STRING [26] Yes Yes Yes Yes
TVST Twelve String STRING [26] Yes Yes Yes Yes
TTST Thirteen String STRING [26] Yes Yes Yes Yes
FTST Fourteen String STRING [26] Yes Yes Yes Yes
FFST Fifteen String STRING [26] Yes Yes Yes Yes

Alarm Parameters

The possible alarm conditions for multi-bit binary inputs are the SCAN, READ, and state alarms. The state alarms are configured in the below severity fields. These fields have the usual possible values for severity fields: NO_ALARM, MINOR, and MAJOR.

The unknown state severity (UNSV) field, if set to MINOR or MAJOR, triggers an alarm when the record support routine cannot find a matching value in the state value fields for rval.

The change of state severity (COSV) field triggers an alarm when any change of state occurs, if set to MAJOR or MINOR.

The other fields, when set to MAJOR or MINOR, trigger an alarm when VAL equals the corresponding state.

See Alarm Specification for a complete explanation of record alarms and of the standard fields. Alarm Fields lists other fields related to alarms that are common to all record types.

Field Summary Type DCT Default Read Write CA PP
UNSV Unknown State Severity MENU menuAlarmSevr Yes Yes Yes Yes
COSV Change of State Svr MENU menuAlarmSevr Yes Yes Yes Yes
ZRSV State Zero Severity MENU menuAlarmSevr Yes Yes Yes Yes
ONSV State One Severity MENU menuAlarmSevr Yes Yes Yes Yes
TWSV State Two Severity MENU menuAlarmSevr Yes Yes Yes Yes
THSV State Three Severity MENU menuAlarmSevr Yes Yes Yes Yes
FRSV State Four Severity MENU menuAlarmSevr Yes Yes Yes Yes
FVSV State Five Severity MENU menuAlarmSevr Yes Yes Yes Yes
SXSV State Six Severity MENU menuAlarmSevr Yes Yes Yes Yes
SVSV State Seven Severity MENU menuAlarmSevr Yes Yes Yes Yes
EISV State Eight Severity MENU menuAlarmSevr Yes Yes Yes Yes
NISV State Nine Severity MENU menuAlarmSevr Yes Yes Yes Yes
TESV State Ten Severity MENU menuAlarmSevr Yes Yes Yes Yes
ELSV State Eleven Severity MENU menuAlarmSevr Yes Yes Yes Yes
TVSV State Twelve Severity MENU menuAlarmSevr Yes Yes Yes Yes
TTSV State Thirteen Sevr MENU menuAlarmSevr Yes Yes Yes Yes
FTSV State Fourteen Sevr MENU menuAlarmSevr Yes Yes Yes Yes
FFSV State Fifteen Severity MENU menuAlarmSevr Yes Yes Yes Yes

Run-time Parameters

These parameters are used by the run-time code for processing the multi-bit binary input.

ORAW is used by record processing to hold the prior RVAL for use in determining when to post a monitor event for the RVAL field.

The LALM field implements the change of state alarm severity by holding the value of VAL when the previous change of state alarm was issued.

MLST holds the value when the last monitor for value change was triggered.

SDEF is used by record support to save time if no states are defined.

Field Summary Type DCT Default Read Write CA PP
ORAW Prev Raw Value ULONG No Yes No No
LALM Last Value Alarmed USHORT No Yes No No
MLST Last Value Monitored USHORT No Yes No No
SDEF States Defined SHORT No Yes No No

Simulation Mode Parameters

The following fields are used to operate the record in simulation mode.

If SIMM (fetched through SIML) is YES or RAW, the record is put in SIMS severity and the value is fetched through SIOL (buffered in SVAL). If SIMM is YES, SVAL is written to VAL without conversion, if SIMM is RAW, SVAL is trancated to RVAL and converted. SSCN sets a different SCAN mechanism to use in simulation mode. SDLY sets a delay (in sec) that is used for asynchronous simulation processing.

See Input Simulation Fields for more information on simulation mode and its fields.

Field Summary Type DCT Default Read Write CA PP
SIML Simulation Mode Link INLINK Yes Yes Yes No
SIMM Simulation Mode MENU menuSimm No Yes Yes No
SIOL Simulation Input Link INLINK Yes Yes Yes No
SVAL Simulation Value ULONG No Yes Yes No
SIMS Simulation Mode Severity MENU menuAlarmSevr Yes Yes Yes No
SDLY Sim. Mode Async Delay DOUBLE Yes -1.0 Yes Yes No
SSCN Sim. Mode Scan MENU menuScan Yes 65535 Yes Yes No

Record Support

Record Support Routines

init_record

This routine initializes SIMM with the value of SIML if SIML type is CONSTANT link or creates a channel access link if SIML type is PV_LINK. SVAL is likewise initialized if SIOL is CONSTANT or PV_LINK.

This routine next checks to see that device support is available and a device support read routine is defined. If either does not exist, an error message is issued and processing is terminated.

Clears MASK and then sets the NOBT low order bits.

If device support includes init_record(), it is called.

init_common is then called to determine if any states are defined. If states are defined, SDEF is set to TRUE.

process

See next section.

special

Calls init_common to compute SDEF when any of the fields ZRVL, ... FFVL change value.

get_enum_str

Retrieves ASCII string corresponding to VAL.

get_enum_strs

Retrieves ASCII strings for ZRST,...FFST.

put_enum_str

Checks if string matches ZRST,...FFST and if it does, sets VAL.

Record Processing

Routine process implements the following algorithm:

  1. Check to see that the appropriate device support module exists. If it doesn't, an error message is issued and processing is terminated with the PACT field still set to TRUE. This ensures that processes will no longer be called for this record. Thus error storms will not occur.
  2. readValue is called. See "Input Records" for more information.
  3. If PACT has been changed to TRUE, the device support read routine has started but has not completed reading a new input value. In this case, the processing routine merely returns, leaving PACT TRUE.
  4. Convert:
    • status=read_mbbi
    • PACT = TRUE
    • recGblGetTimeStamp() is called.
    • If status is 0, then determine VAL
      • Set rval = RVAL
      • Shift rval right SHFT bits
    • If at least one state value is defined
      • Set UDF to TRUE
    • If RVAL is ZRVL,...,FFVL then set
      • VAL equals index of state
      • UDF set to FALSE
    • Else set VAL = undefined
      • Else set VAL = RVAL
    • Set UDF to FALSE
      • If status is 1, return 0
      • If status is 2, set status = 0
  5. Check alarms. This routine checks to see if the new VAL causes the alarm status and severity to change. If so, NSEV, NSTA and LALM are set.
  6. Check to see if monitors should be invoked.
    • Alarm monitors are invoked if the alarm status or severity has changed.
    • Archive and value change monitors are invoked if MLST is not equal to VAL.
    • Monitors for RVAL are checked whenever other monitors are invoked.
    • NSEV and NSTA are reset to 0.
  7. Scan forward link if necessary, set PACT FALSE, and return.

Device Support

Fields Of Interest To Device Support

Each input record must have an associated set of device support routines.

The primary responsibility of the device support routines is to obtain a new raw input value whenever read_mbbi is called. The device support routines are primarily interested in the following fields:

Field Summary Type DCT Default Read Write CA PP
PACT Record active UCHAR No Yes No No
DPVT Device Private NOACCESS No No No No
UDF Undefined UCHAR Yes 1 Yes Yes Yes
NSEV New Alarm Severity MENU menuAlarmSevr No Yes No No
NSTA New Alarm Status MENU menuAlarmStat No Yes No No
NOBT Number of Bits USHORT Yes Yes No No
VAL Current Value ENUM Yes Yes Yes Yes
INP Input Specification INLINK Yes Yes Yes No
RVAL Raw Value ULONG No Yes Yes Yes
MASK Hardware Mask ULONG No Yes No No
SHFT Shift USHORT Yes Yes Yes No

Device Support Routines

Device support consists of the following routines:

long report(int level)

This optional routine is called by the IOC command dbior and is passed the report level that was requested by the user. It should print a report on the state of the device support to stdout. The level parameter may be used to output increasingly more detailed information at higher levels, or to select different types of information with different levels. Level zero should print no more than a small summary.

long init(int after)

This optional routine is called twice at IOC initialization time. The first call happens before any of the init_record() calls are made, with the integer parameter after set to 0. The second call happens after all of the init_record() calls have been made, with after set to 1.

init_record

init_record(precord)

This routine is optional. If provided, it is called by the record support init_record() routine. If it uses MASK, it should shift it as necessary and also give SHFT a value.

get_ioint_info

get_ioint_info(int cmd,struct dbCommon *precord,IOSCANPVT *ppvt)

This routine is called by the ioEventScan system each time the record is added or deleted from an I/O event scan list. cmd has the value (0,1) if the record is being (added to, deleted from) an I/O event list. It must be provided for any device type that can use the I/O Event scanner.

read_mbbi

read_mbbi(precord)

This routine must provide a new input value. It returns the following values:

  • 0: Success. A new raw value is placed in RVAL. The record support module determines VAL from RVAL, SHFT, and ZEVL ... FFVL.
  • 2: Success, but don't modify VAL.
  • Other: Error.

Device Support For Soft Records

Two soft device support modules Soft Channel and Raw Soft Channel are provided for multi-bit binary input records not related to actual hardware devices. The INP link type must be either CONSTANT, DB_LINK, or CA_LINK.

Soft Channel

read_mbbi always returns a value of 2, which means that no conversion is performed.

If the INP link type is constant, then the constant value is stored into VAL by init_record(), and UDF is set to FALSE. VAL can be changed via dbPut requests. If the INP link type is PV_LINK, then dbCaAddInlink is called by init_record().

read_mbbi calls recGblGetLinkValue to read the current value of VAL. See Soft Input.

If the return status of recGblGetLinkValue is zero, then read_mbbi sets UDF to FALSE. The status of recGblGetLinkValue is returned.

Raw Soft Channel

This module is like the previous except that values are read into RVAL, VAL is computed from RVAL, and read_mbbi returns a value of 0. Thus the record processing routine will determine VAL in the normal way.