Added typical values for Abs and Ech + references
Browse files Browse the repository at this point in the history
  • Loading branch information
samuelduchesne committed Apr 19, 2018
1 parent c8d6427 commit 7b395e4
Showing 1 changed file with 41 additions and 0 deletions.
41 changes: 41 additions & 0 deletions docs/plugins/district-energy.rst
Original file line number Diff line number Diff line change
Expand Up @@ -85,6 +85,24 @@ Input Parameters
| Cooling coefficient of performance | Average annual ratio of useful cooling delivered to natural gas consumed | 0.90 |
+----------------------------------------------+------------------------------------------------------------------------------------+---------------+

Typical Values
''''''''''''''

Table :numref:`typicalAbs` summarizes typical chiller efficiency ranges for different chiller technologies.

.. table:: Typical chiller efficiency ranges with different prime drivers
:name: typicalAbs

+----------------------------------------------------------------+--------------------+----------------+
| Chiller type | Typical efficiency | Capacity (KW) |
+================================================================+====================+================+
| Steam driven centrifugal HW absorption chiller (single effect) | COP 0.55–0.70 | <200 to >11500 |
+----------------------------------------------------------------+--------------------+----------------+
| Steam absorption chiller (single effect) | COP 0.60–0.8 | <200 to >11500 |
+----------------------------------------------------------------+--------------------+----------------+
| Direct fired (double effect) absorption chiller | COP 0.85–1.30 | <350 to >11500 |
+----------------------------------------------------------------+--------------------+----------------+

Electric chillers
`````````````````

Expand Down Expand Up @@ -120,6 +138,24 @@ Input Parameters
| Cooling coefficient of performance | Average annual ratio of useful cooling delivered to electricity consumed | 4.40 |
+------------------------------------+--------------------------------------------------------------------------+---------------+

Typical Values
''''''''''''''

Table :numref:`typicalEch` summarizes typical chiller efficiency ranges for different chiller technologies.

.. table:: Typical chiller efficiency ranges with different prime drivers [#]_
:name: typicalEch

+---------------------------------------------------------------------+--------------------+-----------------+
| Chiller type | Typical efficiency | Capacity (KW) |
+=====================================================================+====================+=================+
| Electric centrifugal (standard single compressor) | COP 4.7–6.75 | 1750 to > 5275 |
+---------------------------------------------------------------------+--------------------+-----------------+
| Electric centrifugal (standard dual compressor) | COP 4.7–6.75 | 5275 to >14000 |
+---------------------------------------------------------------------+--------------------+-----------------+
| Electric centrifugal (single compressor industrial – field erected) | COP 4.7–6.75 | 8800 to > 20000 |
+---------------------------------------------------------------------+--------------------+-----------------+

Solar thermal collectors
````````````````````````

Expand Down Expand Up @@ -425,3 +461,8 @@ The module can also be assigned to track electricity instead of the thermal load
+-----------------------------------------------+---------------------------------------------------------------------------------+---------------+
| Waste heat recovery effectiveness (%) | Average annual ratio of usable heat recovered from generator to fuel consumed | 29 |
+-----------------------------------------------+---------------------------------------------------------------------------------+---------------+

References
----------

.. [#] S. Tredinnick and G. Phetteplace, 8 - District cooling, current status and future trends, In Woodhead Publishing Series in Energy, edited by Robin Wiltshire,, Woodhead Publishing, Oxford, 2016, Pages 167-188, Advanced District Heating and Cooling (DHC) Systems, ISBN 9781782423744, `<https://doi.org/10.1016/B978-1-78242-374-4.00008-2>`_. (`<https://www.sciencedirect.com/science/article/pii/B9781782423744000082>`_)