Correct crash with DOAS VS DX coils and fix system name in Coil Sizing tables #10334

Merged
merged 7 commits into from Feb 16, 2024

Conversation

rraustad
Copy link
Contributor

@rraustad rraustad commented Dec 15, 2023

Pull request overview

Reporting corrections:

  • HVAC Type and HVAC Name are reported for DOAS system
  • DOAS coil air flow is reported
  • System Sizing Method Concurrence method added Combination for when air loops used different sizing methods
  • TU heating coil air flow rate

NOTE: ENHANCEMENTS MUST FOLLOW A SUBMISSION PROCESS INCLUDING A FEATURE PROPOSAL AND DESIGN DOCUMENT PRIOR TO SUBMITTING CODE

Pull Request Author

Add to this list or remove from it as applicable. This is a simple templated set of guidelines.

  • Title of PR should be user-synopsis style (clearly understandable in a standalone changelog context)
  • Label the PR with at least one of: Defect, Refactoring, NewFeature, Performance, and/or DoNoPublish
  • Pull requests that impact EnergyPlus code must also include unit tests to cover enhancement or defect repair
  • Author should provide a "walkthrough" of relevant code changes using a GitHub code review comment process
  • If any diffs are expected, author must demonstrate they are justified using plots and descriptions
  • If changes fix a defect, the fix should be demonstrated in plots and descriptions
  • If any defect files are updated to a more recent version, upload new versions here or on DevSupport
  • If IDD requires transition, transition source, rules, ExpandObjects, and IDFs must be updated, and add IDDChange label
  • If structural output changes, add to output rules file and add OutputChange label
  • If adding/removing any LaTeX docs or figures, update that document's CMakeLists file dependencies

Reviewer

This will not be exhaustively relevant to every PR.

  • Perform a Code Review on GitHub
  • If branch is behind develop, merge develop and build locally to check for side effects of the merge
  • If defect, verify by running develop branch and reproducing defect, then running PR and reproducing fix
  • If feature, test running new feature, try creative ways to break it
  • CI status: all green or justified
  • Check that performance is not impacted (CI Linux results include performance check)
  • Run Unit Test(s) locally
  • Check any new function arguments for performance impacts
  • Verify IDF naming conventions and styles, memos and notes and defaults
  • If new idf included, locally check the err file and other outputs

@rraustad rraustad added the Defect Includes code to repair a defect in EnergyPlus label Dec 15, 2023
Copy link
Contributor Author

@rraustad rraustad left a comment

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Walk-thru

@@ -853,7 +853,6 @@ namespace AirLoopHVACDOAS {
if (state.dataGlobal->BeginEnvrnFlag && this->MyEnvrnFlag) {
bool ErrorsFound = false;
Real64 rho;
state.dataSize->CurSysNum = this->m_OASystemNum;
Copy link
Contributor Author

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Underlying problem with the table reporting issues. This line reset CurSysNum to CurOASysNum which confused table reports. The component variables CurSysNum and CurOASysNum are set in SizingAirLoopDOAS as:

state.dataSize->CurSysNum = state.dataHVACGlobal->NumPrimaryAirSys + this->m_AirLoopDOASNum + 1;
state.dataSize->CurOASysNum = this->m_OASystemNum;

Whether these initializations should be moved to SimAirLoopHVACDOAS to emulate SimAirLoops is another question. I'm not sure these variables are used in anything other than sizing.

@@ -451,7 +451,7 @@ Real64 HeatingCapacitySizer::size(EnergyPlusData &state, Real64 _originalValue,

this->selectSizerOutput(state, errorsFound);

if (this->isCoilReportObject && this->curSysNum <= state.dataHVACGlobal->NumPrimaryAirSys) {
if (this->isCoilReportObject) {
Copy link
Contributor Author

@rraustad rraustad Dec 15, 2023

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Many of these issues. The DOAS indexes are currently appended to the number of air loops (i.e., CurSysNum = 6 for a DOAS with 5 AirLoopHVAC objects). When code uses CurSysNum to access air loop arrays there is an access violation when DOAS components are sized. These subtle changes were made to get this defect file to run.

Copy link
Member

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Interesting. Should we actually use a separate counter for DOAS systems rather than keeping them magically in line with the other air loops? That's something for later, but just curious how you'd like to proceed in the future.

Copy link
Contributor Author

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

We have CurZoneEqNum, CurSysNum, and CurOASysNum. I think we do need a CurDOASNum. While making this change I was also wondering what the long term fix was. Still not sure if if (this->isCoilReportObject && this->curDOASNum == 0) is any better than what is here now.

c->airloopNum > 0 ? state.dataAirSystemsData->PrimaryAirSystems(c->airloopNum).Name : "N/A");
c->airloopNum > 0 && c->airloopNum <= state.dataHVACGlobal->NumPrimaryAirSys
? state.dataAirSystemsData->PrimaryAirSystems(c->airloopNum).Name
: "N/A");
Copy link
Contributor Author

@rraustad rraustad Dec 15, 2023

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

DOAS index violation. The thing I don't like about the if (airloopNum < NumPrimaryAirSys) is that DOAS information is not reported. This is of course fixable.

@@ -543,7 +548,7 @@ void ReportCoilSelection::doAirLoopSetup(EnergyPlusData &state, int const coilVe
{
// this routine sets up some things for central air systems, needs to follow setting of an airloop num
auto &c(coilSelectionDataObjs[coilVecIndex]);
if (c->airloopNum > 0 && allocated(state.dataAirSystemsData->PrimaryAirSystems)) {
if (c->airloopNum > 0 && c->airloopNum <= state.dataAirSystemsData->PrimaryAirSystems.size()) {
Copy link
Contributor Author

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

DOAS index violation within this block.

c->typeHVACname = "AirLoopHVAC:DedicatedOutdoorAirSystem";
int DOASSysNum = state.dataAirLoop->OutsideAirSys(c->oASysNum).AirLoopDOASNum;
c->userNameforHVACsystem = state.dataAirLoopHVACDOAS->airloopDOAS[DOASSysNum].Name;
} else if (c->airloopNum > 0 && c->zoneEqNum == 0) {
Copy link
Contributor Author

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Correct Coil Sizing tables to report DOAS type and name correctly.

@@ -1276,7 +1286,8 @@ void ReportCoilSelection::setCoilCoolingCapacity(
// if ( c->zoneEqNum > 0 ) doZoneEqSetup( index );
c->oASysNum = curOASysNum;

if (curSysNum > 0 && c->zoneEqNum == 0 && allocated(state.dataSize->FinalSysSizing) && allocated(SysSizPeakDDNum)) {
if (curSysNum > 0 && c->zoneEqNum == 0 && allocated(state.dataSize->FinalSysSizing) && allocated(SysSizPeakDDNum) &&
curSysNum <= state.dataHVACGlobal->NumPrimaryAirSys) {
Copy link
Contributor Author

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

DOAS index violation within this if block.

state.dataAirLoop->AirLoopControlInfo(state.dataSize->CurSysNum).UnitarySysSimulating = false;
if (state.dataSize->CurSysNum <= state.dataHVACGlobal->NumPrimaryAirSys) {
state.dataAirLoop->AirLoopControlInfo(state.dataSize->CurSysNum).UnitarySysSimulating = false;
}
Copy link
Contributor Author

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Protect access array violation when CoilSystem is used in DOAS systems.

RatedAirVolFlowRateDes = state.dataSize->FinalSysSizing(state.dataSize->CurSysNum).DesMainVolFlow;
} else {
RatedAirVolFlowRateDes = 0.0;
}
Copy link
Contributor Author

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Add to VS DX coil sizing for coils in a DOAS. I did not update this code to use the sizing classes. Probably should have but was trying to get this file to run.

@rraustad
Copy link
Contributor Author

Defect file results:

image

@@ -120,6 +120,7 @@ namespace DataSizing {
// parameters for sizing
constexpr int NonCoincident(1);
constexpr int Coincident(2);
constexpr int Combination(3);
Copy link
Contributor Author

@rraustad rraustad Dec 17, 2023

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

If 1 airloop on a DOAS system sizes coincident and others size noncoincident then reporting for System Sizing Method Concurrence needs an alternate notation.

@@ -5014,6 +5043,8 @@ namespace VariableSpeedCoils {
state.dataRptCoilSelection->coilSelectionReportObj->setCoilLvgAirTemp(state, varSpeedCoil.Name, varSpeedCoil.VarSpeedCoilType, SupTemp);
state.dataRptCoilSelection->coilSelectionReportObj->setCoilLvgAirHumRat(
state, varSpeedCoil.Name, varSpeedCoil.VarSpeedCoilType, SupHumRat);
state.dataRptCoilSelection->coilSelectionReportObj->setCoilAirFlow(
state, varSpeedCoil.Name, varSpeedCoil.VarSpeedCoilType, varSpeedCoil.RatedAirVolFlowRate, RatedAirFlowAutoSized);
Copy link
Contributor Author

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Heating coils in OA systems were not reporting air flow in Coil Sizing tables. Or maybe it's just DOAS system, but there are times when air flow = -999 and this corrects that.

@rraustad
Copy link
Contributor Author

rraustad commented Dec 17, 2023

5Zone_Unitary_HXAssistedCoil table diffs. Both develop and this branch used TermUnitSizing(this->curTermUnitSizingNum).AirVolFlow = 0.129526 to size the zone heating coil, but develop reported the FinalZoneSizing heating volume flow = 0.15108.

image

@rraustad rraustad added this to the EnergyPlus 24.1 milestone Jan 4, 2024
@EnergyArchmage
Copy link
Contributor

I have reviewed the code changes here and they look good.

@nrel-bot
Copy link

@rraustad @Myoldmopar it has been 28 days since this pull request was last updated.

Copy link
Member

@Myoldmopar Myoldmopar left a comment

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

These look good to me, I'll double check locally with other develop changes, but expect this to merge soon if clean.

@Myoldmopar
Copy link
Member

Table diffs are quite expected and reasonable. Otherwise this is happy and ready to merge. Thanks @rraustad

@Myoldmopar Myoldmopar merged commit 19484de into develop Feb 16, 2024
15 checks passed
@Myoldmopar Myoldmopar deleted the 10332-DOAS-incorrect-system-name-in-CoilDetails branch February 16, 2024 20:49
Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment