Holdings

Chris Elsworth edited this page Aug 18, 2023 · 7 revisions

WIP

This is a list of holding registers on the inverter. All these registers are read-write. Register numbers are in decimal.

As with input, each register is 16 bits. They seem to be arranged in banks of 40 (so 80 bytes per bank), with read or write requests that cross the boundary being rejected by the inverter. Five banks of 40 (so 240 registers, 480 bytes) are available on at least one inverter, although most of the tail values are zeroes.

Also see https://github.com/celsworth/lxp-bridge/blob/master/doc/LXP_REGISTERS.txt

Also see https://eg4electronics.com/wp-content/uploads/2023/06/EG4-18KPV-12LV-Modbus-Protocol.pdf

Register Register Unit Description
0 - 1 HOLD_MODEL
2 - 6 HOLD_SERIAL_NUM
7 HOLD_FW_CODE
8 Unknown/Reserved
9 Unknown/Reserved
10 Unknown/Reserved
11 Unknown/Reserved
12 HOLD_TIME / year & month
13 HOLD_TIME / hour & day
14 HOLD_TIME / second & minute
15 COM_ADDR
16 LANGUAGE
19 DEVICE_TYPE
20 PV_INPUT_MODE
21 FUNCTIONS(?) Bitmask (see Register 21, below)
22 START_PV_VOLT
23 CONNECT_TIME
24 RECONNECT_TIME
25 GRID_VOLT_CONN_LOW
26 GRID_VOLT_CONN_HIGH
27 GRID_FREQ_CONN_LOW
28 GRID_FREQ_CONN_HIGH
29 GRID_VOLT_LIMIT1_LOW
30 GRID_VOLT_LIMIT1_HIGH
31 GRID_VOLT_LIMIT1_LOW_TIME
32 GRID_VOLT_LIMIT1_HIGH_TIME
33 GRID_VOLT_LIMIT2_LOW
34 GRID_VOLT_LIMIT2_HIGH
35 GRID_VOLT_LIMIT2_LOW_TIME
36 GRID_VOLT_LIMIT2_HIGH_TIME
37 GRID_VOLT_LIMIT3_LOW
38 GRID_VOLT_LIMIT3_HIGH
39 GRID_VOLT_LIMIT3_LOW_TIME
40 GRID_VOLT_LIMIT3_HIGH_TIME
41 GRID_VOLT_MOV_AVG_HIGH
42 GRID_FREQ_LIMIT1_LOW
43 GRID_FREQ_LIMIT1_HIGH
44 GRID_FREQ_LIMIT1_LOW_TIME
45 GRID_FREQ_LIMIT1_HIGH_TIME
46 GRID_FREQ_LIMIT2_LOW
47 GRID_FREQ_LIMIT2_HIGH
48 GRID_FREQ_LIMIT2_LOW_TIME
49 GRID_FREQ_LIMIT2_HIGH_TIME
50 GRID_FREQ_LIMIT3_LOW
51 GRID_FREQ_LIMIT3_HIGH
52 GRID_FREQ_LIMIT3_LOW_TIME
53 GRID_FREQ_LIMIT3_HIGH_TIME
54 MAX_Q_PERCENT_FOR_QV
55 V1L
56 V2L
57 V1H
58 V2H
59 REACTIVE_POWER_CMD_TYPE
60 ACTIVE_POWER_PERCENT_CMD
61 REACTIVE_POWER_PERCENT_CMD
62 PF_CMD
63 POWER_SOFT_START_SLOPE
64 CHARGE_POWER_PERCENT_CMD
65 DISCHG_POWER_PERCENT_CMD
66 AC_CHARGE_POWER_CMD
67 AC_CHARGE_SOC_LIMIT
68 AC_CHARGE_START_HOUR / AC_CHARGE_START_MINUTE
69 AC_CHARGE_END_HOUR / AC_CHARGE_END_MINUTE
70 AC_CHARGE_START_HOUR_1 / AC_CHARGE_START_MINUTE_1
71 AC_CHARGE_END_HOUR_1 / AC_CHARGE_END_MINUTE_1
72 AC_CHARGE_START_HOUR_2 / AC_CHARGE_START_MINUTE_2
73 AC_CHARGE_END_HOUR_2 / AC_CHARGE_END_MINUTE_2
74 FORCED_CHG_POWER_CMD
75 FORCED_CHG_SOC_LIMIT
76 FORCED_CHARGE_START_HOUR / FORCED_CHARGE_START_MINUTE
77 FORCED_CHARGE_END_HOUR/ FORCED_CHARGE_END_MINUTE
78 FORCED_CHARGE_START_HOUR_1 / FORCED_CHARGE_START_MINUTE_1
79 FORCED_CHARGE_END_HOUR_1 / FORCED_CHARGE_END_MINUTE_1
80 FORCED_CHARGE_START_HOUR_2 / FORCED_CHARGE_START_MINUTE_2
81 FORCED_CHARGE_END_HOUR_2 / FORCED_CHARGE_END_MINUTE_2
82 FORCED_DISCHG_POWER_CMD
83 FORCED_DISCHG_SOC_LIMIT
84 FORCED_DISCHARGE_START_HOUR / FORCED_DISCHARGE_START_MINUTE
85 FORCED_DISCHARGE_END_HOUR / FORCED_DISCHARGE_END_MINUTE
86 FORCED_DISCHARGE_START_HOUR_1 / FORCED_DISCHARGE_START_MINUTE_1
87 FORCED_DISCHARGE_END_HOUR_1 / FORCED_DISCHARGE_END_MINUTE_1
88 FORCED_DISCHARGE_START_HOUR_2 / FORCED_DISCHARGE_START_MINUTE_2
89 FORCED_DISCHARGE_END_HOUR_2 / FORCED_DISCHARGE_END_MINUTE_2
90 EPS_VOLT_SET
91 EPS_FREQ_SET
99 LEAD_ACID_CHARGE_VOLT_REF
100 LEAD_ACID_DISCHARGE_CUT_OFF_VOLT
101 LEAD_ACID_CHARGE_RATE
102 LEAD_ACID_DISCHARGE_RATE
103 FEED_IN_GRID_POWER_PERCENT
105 DISCHG_CUT_OFF_SOC_EOD
106 LEAD_ACID_TEMPR_LOWER_LIMIT_DISCHG
107 LEAD_ACID_TEMPR_UPPER_LIMIT_DISCHG
108 LEAD_ACID_TEMPR_LOWER_LIMIT_CHG
109 LEAD_ACID_TEMPR_UPPER_LIMIT_CHG
110 FUNCTIONS_GRID(?) Bitmask (see Register 110)
112 SET_MASTER_OR_SLAVE
113 SET_COMPOSED_PHASE
116 P_TO_USER_START_DISCHG
118 VBAT_START_DERATING
119 This seems to be some sort of grid ct calibration offset to achieve true zero import/export. only seems to work in recent firmwares
120 ST_SYS_ENABLE Bitmask (see Register 120)
122 MAINTENANCE_COUNT
125 SOC_LOW_LIMIT_EPS_DISCHG
137 SPEC_LOAD_COMPENSATE
144 FLOATING_VOLTAGE
145 OUTPUT_CONFIGURATION
146 LINE_MODE_INPUT
147 BATTERY_CAPACITY
148 NOMINAL_BATTERY_VOLTAGE
149 EQUALIZATION_VOLTAGE
150 EQUALIZATION_PERIOD
151 EQUALIZATION_TIME
152 AC_FIRST_START_HOUR / AC_FIRST_START_MINUTE
153 AC_FIRST_END_HOUR / AC_FIRST_END_MINUTE
154 AC_FIRST_START_HOUR_1 / AC_FIRST_START_MINUTE_1
155 AC_FIRST_END_HOUR_1 / AC_FIRST_END_MINUTE_1
156 AC_FIRST_START_HOUR_2 / AC_FIRST_START_MINUTE_2
157 AC_FIRST_END_HOUR_2 / AC_FIRST_END_MINUTE_2
158 AC_CHARGE_START_BATTERY_VOLTAGE
159 AC_CHARGE_END_BATTERY_VOLTAGE
160 AC_CHARGE_START_BATTERY_SOC
161 AC_CHARGE_END_BATTERY_SOC
162 BATTERY_WARNING_VOLTAGE
163 BATTERY_WARNING_RECOVERY_VOLTAGE
164 BATTERY_WARNING_SOC
165 BATTERY_WARNING_RECOVERY_SOC
166 BATTERY_LOW_TO_UTILITY_VOLTAGE
167 BATTERY_LOW_TO_UTILITY_SOC
168 AC_CHARGE_BATTERY_CURRENT
169 ON_GRID_EOD_VOLTAGE
177 MAX_GENERATOR_INPUT_POWER

Register 21

This is a writable register controlling a range of functions, listed below. For instance, to enable AC charge, you need to retrieve the current value of the register, bitwise-or it with 0x80, and write that value back to the register.

Bit ([MSB, LSB]) Name / Description
0x8000 Feed in grid
0x4000 DCI
0x2000 GFCI
0x1000 ? - can't see any effect, normally on?
0x0800 Charge priority (charge before supplying load)
0x0400 Forced discharge
0x0200 Normal / standby (doesn't seem to save any power anyway)
0x0100 Seamless EPS switching
0x0080 AC Charge
0x0040 Grid on power SS
0x0020 Neutral detect
0x0010 Anti island
0x0008 ? Can't see any effect. Normally off.
0x0004 drms
0x0002 ovf load derate
0x0001 eps - setting fails with error code 3? (134 in dataframe second byte)

Register 110

Just like register 21, this is a set of functionality that can be individually switched on or off.

Bit ([MSB, LSB]) Name / description
0x0004 Micro grid enable
0x0002 Fast zero export
0x0001 PV without grid? (setting fails with error 3 (134 in dataframe second byte)

Register 120

Bit sparse on details here, this is just copied from the EG4 18kPV modbus protocol document. May only apply in newer inverters/firmwares.

Details about bits 1-3 are summarised nicely in this discussion post.

Bit Values Description
0 0, 1 HalfHourACChrStartEn
1 - 3 0 - 3 ACChargeType : 0- disable; 1- according to time; 2- according to voltage; 3- according to SOC
4 - 5 0 - 2 DischgCtrlType : 0- according to voltage; 1- according to SOC; 2- according to both
6 0, 1 OnGridEODType : 0- according to voltage; 1- according to SOC
7 0, 1 GenChargeType : 0- According to Battery voltage; 1- According to Battery SOC