Is your feature request related to a problem? Please describe.
As an 61850 test engineer
I would like to see an overview of important 61850 configuration settings
So I can spot error pretty quickly.
Parameters per IED (instantiated values and data templates sections):
IEDname
IP adress (only 1 port available)
Subnetmask (only 1 port available)
Template (IED description)
Current related TCTR (IL1 and RES):
Path:
IED name / LD0 / server / LD0 / TCTR
/ ARtg / setMag = Primary rated current
ARtgNom / setMag = Network Nominal Current
ARtgSec / setVal = Secondary rated current
VRtgSec / VRtgSec = Rated Secondary Value
Voltage related:
IED name / LD0 / server / LD0 / TVTR
VRtgScy = secondary rated voltage
VRtg = Primary rated voltage
Rat = Devision ratio / Ratio between the primary and secondary value of an instrument transformer.
LPHD / PhyNam / vendor = Vendor
LPHD / PhyNam / model = Model
Background
With template engineering, some parameters need to be adjusted when apply an template.
Describe the solution you'd like
The parameters can change over time, It would be nice if relevant parameters are configured in an configuration file (or equal).
Additional information
For further reading including e.g parts of IEC 61850, Tissues or other sources that triggered your feature wish
Open Questions
Where can the SNTP IP address (primary/secondary) settings be found in the ABB SCL files? This can be build in a later version (once found). (seperate issue)
For later improvement:
Where to show the exact location?
Display the full path/query?
Technical: @JakobVogelsang "Have an menu type plugin that opens a dialog that can be designed as one like. Web component libraries grow bigger and bigger, and there are plenty with containing table views. For this purpose we might not even need that as it is read-only but use pure CSS and HTML."
The text was updated successfully, but these errors were encountered:
Is your feature request related to a problem? Please describe.
As an 61850 test engineer
I would like to see an overview of important 61850 configuration settings
So I can spot error pretty quickly.
Parameters per IED (instantiated values and data templates sections):
IEDname
IP adress (only 1 port available)
Subnetmask (only 1 port available)
Template (IED description)
Current related TCTR (IL1 and RES):
Path:
IED name / LD0 / server / LD0 / TCTR
/ ARtg / setMag = Primary rated current
ARtgNom / setMag = Network Nominal Current
ARtgSec / setVal = Secondary rated current
VRtgSec / VRtgSec = Rated Secondary Value
Voltage related:
IED name / LD0 / server / LD0 / TVTR
VRtgScy = secondary rated voltage
VRtg = Primary rated voltage
Rat = Devision ratio / Ratio between the primary and secondary value of an instrument transformer.
LPHD / PhyNam / vendor = Vendor
LPHD / PhyNam / model = Model
Background
With template engineering, some parameters need to be adjusted when apply an template.
Describe the solution you'd like
The parameters can change over time, It would be nice if relevant parameters are configured in an configuration file (or equal).
Suggestions for a specific user interaction
Export in a format that excel can read (e.g. CSV):
https://excalidraw.com/#json=cDNz1-4xVKzTOquYzmaat,CCts1udoBdSY9DwU3jADdQ
Additional information
For further reading including e.g parts of IEC 61850, Tissues or other sources that triggered your feature wish
Open Questions
Where can the SNTP IP address (primary/secondary) settings be found in the ABB SCL files? This can be build in a later version (once found). (seperate issue)
For later improvement:
Where to show the exact location?
Display the full path/query?
Technical:
@JakobVogelsang "Have an menu type plugin that opens a dialog that can be designed as one like. Web component libraries grow bigger and bigger, and there are plenty with containing table views. For this purpose we might not even need that as it is read-only but use pure CSS and HTML."
The text was updated successfully, but these errors were encountered: