339
meta-ibm/meta-witherspoon/recipes-phosphor/dbus/fan-policy/mihawk/air-cooled.yaml
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Original file line number | Diff line number | Diff line change |
---|---|---|
@@ -0,0 +1,339 @@ | ||
# Air cooled mihawk fan policy for PDM. | ||
# | ||
# An air cooled mihawk requires a minimum of three functional fans | ||
# enclosures or six functional fan rotors across all enclosures. | ||
# If the number of functional fan enclosures is below three, soft poweroff | ||
# the system, whereas if the number of fan rotors drop below six, an | ||
# immediate hard poweroff of the system occurs. | ||
|
||
- name: fan enclosures | ||
description: > | ||
'An air cooled mihawk has 6 fan enclosures to monitor.' | ||
class: group | ||
group: path | ||
members: | ||
- meta: FAN | ||
path: /xyz/openbmc_project/inventory/system/chassis/motherboard/fan0 | ||
- meta: FAN | ||
path: /xyz/openbmc_project/inventory/system/chassis/motherboard/fan1 | ||
- meta: FAN | ||
path: /xyz/openbmc_project/inventory/system/chassis/motherboard/fan2 | ||
- meta: FAN | ||
path: /xyz/openbmc_project/inventory/system/chassis/motherboard/fan3 | ||
- meta: FAN | ||
path: /xyz/openbmc_project/inventory/system/chassis/motherboard/fan4 | ||
- meta: FAN | ||
path: /xyz/openbmc_project/inventory/system/chassis/motherboard/fan5 | ||
|
||
- name: fan rotors | ||
description: > | ||
'An air cooled Witherspoon has eight fan rotors to monitor.' | ||
class: group | ||
group: path | ||
members: | ||
- meta: FAN | ||
path: /xyz/openbmc_project/inventory/system/chassis/motherboard/fan0/fan0_0 | ||
- meta: FAN | ||
path: /xyz/openbmc_project/inventory/system/chassis/motherboard/fan0/fan0_1 | ||
- meta: FAN | ||
path: /xyz/openbmc_project/inventory/system/chassis/motherboard/fan1/fan1_0 | ||
- meta: FAN | ||
path: /xyz/openbmc_project/inventory/system/chassis/motherboard/fan1/fan1_1 | ||
- meta: FAN | ||
path: /xyz/openbmc_project/inventory/system/chassis/motherboard/fan2/fan2_0 | ||
- meta: FAN | ||
path: /xyz/openbmc_project/inventory/system/chassis/motherboard/fan2/fan2_1 | ||
- meta: FAN | ||
path: /xyz/openbmc_project/inventory/system/chassis/motherboard/fan3/fan3_0 | ||
- meta: FAN | ||
path: /xyz/openbmc_project/inventory/system/chassis/motherboard/fan3/fan3_1 | ||
- meta: FAN | ||
path: /xyz/openbmc_project/inventory/system/chassis/motherboard/fan4/fan4_0 | ||
- meta: FAN | ||
path: /xyz/openbmc_project/inventory/system/chassis/motherboard/fan4/fan4_1 | ||
- meta: FAN | ||
path: /xyz/openbmc_project/inventory/system/chassis/motherboard/fan5/fan5_0 | ||
- meta: FAN | ||
path: /xyz/openbmc_project/inventory/system/chassis/motherboard/fan5/fan5_1 | ||
|
||
- name: chassis state | ||
description: > | ||
'Witherspoon has a single chassis to monitor.' | ||
class: group | ||
group: path | ||
members: | ||
- meta: CHASSISSTATE | ||
path: /xyz/openbmc_project/state/chassis0 | ||
|
||
- name: chassis | ||
description: > | ||
'Witherspoon has a single chassis to monitor.' | ||
class: group | ||
group: path | ||
members: | ||
- meta: CHASSIS | ||
path: /xyz/openbmc_project/inventory/system/chassis | ||
|
||
- name: fan present | ||
description: > | ||
'Monitor the presence state of each fan.' | ||
class: group | ||
group: property | ||
type: boolean | ||
members: | ||
- interface: xyz.openbmc_project.Inventory.Item | ||
meta: PRESENT | ||
property: Present | ||
|
||
- name: fan functional | ||
description: > | ||
'Monitor the functional state of each fan.' | ||
class: group | ||
group: property | ||
type: boolean | ||
members: | ||
- interface: xyz.openbmc_project.State.Decorator.OperationalStatus | ||
meta: FUNCTIONAL | ||
property: Functional | ||
|
||
- name: chassis powered | ||
description: > | ||
'Monitor the chassis power state.' | ||
class: group | ||
group: property | ||
type: string | ||
members: | ||
- interface: xyz.openbmc_project.State.Chassis | ||
meta: CHASSIS_STATE | ||
property: CurrentPowerState | ||
|
||
- name: chassis air cooled | ||
description: > | ||
'Monitor the chassis cooling type.' | ||
class: group | ||
group: property | ||
type: boolean | ||
members: | ||
- interface: xyz.openbmc_project.Inventory.Decorator.CoolingType | ||
meta: COOLING_TYPE | ||
property: WaterCooled | ||
|
||
- name: watch fan present | ||
description: > | ||
'Trigger logic on fan enclosure presence state changes.' | ||
class: watch | ||
watch: property | ||
paths: fan enclosures | ||
properties: fan present | ||
callback: check cooling type | ||
|
||
- name: watch fan functional | ||
description: > | ||
'Trigger logic on fan enclosure functional state changes.' | ||
class: watch | ||
watch: property | ||
paths: fan enclosures | ||
properties: fan functional | ||
callback: check cooling type | ||
|
||
- name: watch fan rotor functional | ||
description: > | ||
'Trigger logic on fan rotor functional state changes.' | ||
class: watch | ||
watch: property | ||
paths: fan rotors | ||
properties: fan functional | ||
callback: check cooling type | ||
|
||
- name: watch chassis state | ||
description: > | ||
'Trigger logic on chassis power state changes.' | ||
class: watch | ||
watch: property | ||
paths: chassis state | ||
properties: chassis powered | ||
callback: check cooling type | ||
|
||
- name: watch cooling type | ||
description: > | ||
'Maintain a cache of the chassis cooling type.' | ||
class: watch | ||
watch: property | ||
paths: chassis | ||
properties: chassis air cooled | ||
|
||
- name: check cooling type | ||
description: > | ||
'If this condition passes the chassis is air cooled.' | ||
class: condition | ||
condition: count | ||
paths: chassis | ||
properties: chassis air cooled | ||
callback: check power | ||
countop: '==' | ||
countbound: 0 | ||
op: '==' | ||
bound: true | ||
|
||
- name: check power | ||
description: > | ||
'If the chassis has power, check fans.' | ||
class: condition | ||
condition: count | ||
paths: chassis state | ||
properties: chassis powered | ||
callback: check fans | ||
countop: '>' | ||
countbound: 0 | ||
op: '==' | ||
bound: xyz.openbmc_project.State.Chassis.PowerState.On | ||
|
||
- name: check fans | ||
description: > | ||
'Verify there are at least three functional fan enclosures and at least | ||
six functional fan rotors, power off if not.' | ||
class: callback | ||
callback: group | ||
members: | ||
- check group presence | ||
- check group functional enclosures | ||
- check group functional rotors | ||
|
||
- name: check group presence | ||
description: > | ||
'If this condition passes more than one fan has been unplugged | ||
for more than 25 seconds. Shut the system down. Count present | ||
fans rather than non-present fans since the latter would pass | ||
if the fan has not been created for some reason. | ||
For a more detailed definition of unplugged, consult the documentation | ||
of xyz.openbmc_project.Inventory.Item and/or the documentation | ||
of the fan inventory object implementation.' | ||
class: condition | ||
condition: count | ||
paths: fan enclosures | ||
properties: fan present | ||
defer: 25000000us | ||
callback: log and shutdown | ||
countop: '<' | ||
countbound: 6 | ||
op: '==' | ||
bound: true | ||
|
||
- name: check group functional enclosures | ||
description: > | ||
'If this condition passes more than one fan enclosure in the group has been | ||
marked as nonfunctional for 25 seconds. Shut the system down. | ||
For a more detailed definition of nonfunctional, consult the documentation | ||
of xyz.openbmc_project.State.Decorator.OperationalStatus and/or the | ||
documentation of the fan inventory object implementation.' | ||
class: condition | ||
condition: count | ||
paths: fan enclosures | ||
properties: fan functional | ||
defer: 25000000us | ||
callback: log and shutdown | ||
countop: '>' | ||
countbound: 1 | ||
op: '==' | ||
bound: false | ||
|
||
- name: check group functional rotors | ||
description: > | ||
'If this condition passes more than two fan rotors in the group have been | ||
marked as nonfunctional for 25 seconds. Immediately power off. | ||
For a more detailed definition of nonfunctional, consult the documentation | ||
of xyz.openbmc_project.State.Decorator.OperationalStatus and/or the | ||
documentation of the fan inventory object implementation.' | ||
class: condition | ||
condition: count | ||
paths: fan rotors | ||
properties: fan functional | ||
defer: 25000000us | ||
callback: log and poweroff | ||
countop: '>' | ||
countbound: 1 | ||
op: '==' | ||
bound: false | ||
|
||
- name: log and poweroff | ||
description: > | ||
'Immediately poweroff, log an event in the journal, and create an | ||
error log.' | ||
class: callback | ||
callback: group | ||
members: | ||
- hard poweroff | ||
- log hard poweroff | ||
- create shutdown error | ||
|
||
- name: log and shutdown | ||
description: > | ||
'Shut the system down, log an event in the journal, and create an | ||
error log.' | ||
class: callback | ||
callback: group | ||
members: | ||
- shutdown | ||
- log shutdown | ||
- create shutdown error | ||
|
||
- name: hard poweroff | ||
description: > | ||
'Immediately power off the system.' | ||
class: callback | ||
callback: method | ||
service: org.freedesktop.systemd1 | ||
path: /org/freedesktop/systemd1 | ||
interface: org.freedesktop.systemd1.Manager | ||
method: StartUnit | ||
args: | ||
- value: obmc-chassis-hard-poweroff@0.target | ||
type: string | ||
- value: replace | ||
type: string | ||
|
||
- name: shutdown | ||
description: > | ||
'Shut down the system.' | ||
class: callback | ||
callback: method | ||
service: org.freedesktop.systemd1 | ||
path: /org/freedesktop/systemd1 | ||
interface: org.freedesktop.systemd1.Manager | ||
method: StartUnit | ||
args: | ||
- value: obmc-host-shutdown@0.target | ||
type: string | ||
- value: replace | ||
type: string | ||
|
||
- name: log hard poweroff | ||
description: > | ||
'Log a hard poweroff event to the systemd journal.' | ||
class: callback | ||
callback: journal | ||
paths: chassis state | ||
properties: chassis powered | ||
severity: ERR | ||
message: Immediate poweroff of system. There are not enough functional fans. | ||
|
||
- name: log shutdown | ||
description: > | ||
'Log a shutdown event to the systemd journal.' | ||
class: callback | ||
callback: journal | ||
paths: chassis state | ||
properties: chassis powered | ||
severity: ERR | ||
message: Request shutdown of system. There are not enough functional fans. | ||
|
||
- name: create shutdown error | ||
description: > | ||
'Create a Fan Shutdown Error log.' | ||
class: callback | ||
callback: elog | ||
paths: chassis state | ||
properties: chassis powered | ||
error: xyz::openbmc_project::State::Shutdown::Inventory::Error::Fan |