Nagios/Icinga2 check for Vertiv aka Liebert DataCenter Air Condition controllers:

$ ./check_liebert_aircondition --help
check_liebert_aircondition [-CHt] [long options...] <some-arg>
    --host STR (or -H)       Hostname
    --community STR (or -C)  SNMP community
    --timeout INT (or -t)    Timeout
    --waterflow              Water Flow Loss
    --debug                  Debug
    --listflexentries        List flexible entries
    --perf STR...            Performance metrics

    --help                   print usage message and exit

User --waterflow to monitor the waterflow alarm entry.

./check_liebert_aircondition \
        --host 172.30.128.18 \
        --waterflow \
        --community public \
        --perf "Ext Air Sensor B Temperature|deg C" \
        --perf "Supply Air Temperature|deg C" \
        --perf "Chilled Water Inlet Temperature|deg C" \
        --perf "Chilled Water Outlet Temperature|deg C" \
        --perf "Ext Air Sensor B Humidity" \
        --perf "Fan Speed" \
        --perf "Return Air Temperature|deg C"

LIEBERT_AIRCONDITION OK - system state: normalOperation(1) conditions present: 0 controlOperation: On(1) | 'Ext Air Sensor B Temperature'=14.3C;; 'Supply Air Temperature'=19.9C;; 'Chilled Water Inlet Temperature'=14.3C;; 'Chilled Water Outlet Temperature'=UnavailableC;; 'Ext Air Sensor B Humidity'=23.3%;; 'Fan Speed'=53%;; 'Return Air Temperature'=27.4C;;

To get the available sensor entries use the -flexentries command line option. Example output for a Liebert PDX-PCW:

./check_liebert_aircondition --host 172.30.128.18 --community public --listflexentries
Actual Cold Aisle Humidity                              Unavailable          % RH      
Actual Cold Aisle Temperature                           Unavailable          deg C     
Actual Cold Aisle Temperature                           Unavailable          deg F     
Actual Compressor 1 Suction Pressure                    -32768               bar       
Actual Compressor 2 Suction Pressure                    -32768               bar       
Actual Return Air Temperature Set Point                 25.0                 deg C     
Actual Return Air Temperature Set Point                 77.0                 deg F     
Actual Return Humidity Set Point                        Unavailable          % RH      
Adjusted Humidity                                       30.4                 % RH      
Air Filter Differential Pressure                        -131.55              inWC      
Air Filter Differential Pressure                        -32768               Pa        
Air Temperature Control Integration Time                0                    min       
Air Temperature Control Type                            Proportional                   
Air Temperature Dead Band                               0.0                  deg C     
Air Temperature Dead Band                               0.0                  deg F     
Air Temperature Proportional Band                       14.4                 deg F     
Air Temperature Proportional Band                       8.0                  deg C     
Air Temperature Set Point                               25.0                 deg C     
Air Temperature Set Point                               77.0                 deg F     
Analog Input Reading                                    0.00                           
Analog Input Reading                                    0.00                           
Analog Input Reading                                    0.00                           
Analog Input Reading                                    0.00                           
Auto Restart Delay                                      5                    sec       
Automatic Transfer Switch - Active Power Supply         Power Supply 1                 
Automatic Transfer Switch - Power Supply 1 Status       OK                             
Automatic Transfer Switch - Power Supply 2 Status       OK                             
BMS Timeout Period                                      0                    min       
Back Draft Control Fan Speed                            20                   %         
CW Valve Control                                        0                              
Calculated Next Maintenance Month                       65409                          
Calculated Next Maintenance Year                        Unavailable                    
Chilled Water Flow Loss Status                          Flow OK                        
Chilled Water Flow Loss Status                          Flow OK                        
Chilled Water Inlet Temperature                         14.3                 deg C     
Chilled Water Inlet Temperature                         Unavailable          deg C     
Chilled Water Outlet Temperature                        23.3                 deg C     
Chilled Water Outlet Temperature                        Unavailable          deg C     
Chilled Water Valve Hours                               0                    hr        
Chilled Water Valve Hours                               8494                 hr        
Chilled Water Valve Reset Enable                        disabled                       
Clogged Air Filter - Event Control                      enabled                        
Clogged Air Filter - Event Type                         Warning                        
Cold Aisle Cascade Fan Speed Max Set Point              40                   %         
Cold Aisle Control Enable                               disabled                       
Cold Aisle Fan Speed Max Set Point                      80                   %         
Cold Aisle Fan Speed Min Set Point                      30                   %         
Cold Aisle Force Max Fan/Cooling - Ext Control          disabled                       
Cold Aisle Humidity Calculation Method                  Highest                        
Cold Aisle Sensor Air Temperature                       Unavailable          deg C     
Cold Aisle Sensor Air Temperature                       Unavailable          deg C     
Cold Aisle Sensor Air Temperature                       Unavailable          deg C     
Cold Aisle Sensor Air Temperature                       Unavailable          deg F     
Cold Aisle Sensor Air Temperature                       Unavailable          deg F     
Cold Aisle Sensor Air Temperature                       Unavailable          deg F     
Cold Aisle Sensor Humidity                              Unavailable          % RH      
Cold Aisle Sensor Humidity                              Unavailable          % RH      
Cold Aisle Sensor Humidity                              Unavailable          % RH      
Cold Aisle Temperature Calculation Method               Highest                        
Compressor Capacity Control State                       off                            
Compressor Capacity Control State                       off                            
Compressor Discharge Pressure                           Unavailable          bar       
Compressor Discharge Pressure                           Unavailable          bar       
Compressor High Head Pressure - Event Control           enabled                        
Compressor High Head Pressure - Event Control           enabled                        
Compressor High Head Pressure - Event Type              Alarm                          
Compressor High Head Pressure - Event Type              Alarm                          
Compressor Hours                                        0                    hr        
Compressor Hours                                        0                    hr        
Compressor Hours                                        0                    hr        
Compressor Hours                                        0                    hr        
Compressor Hours Threshold                              0                    hr        
Compressor Hours Threshold                              0                    hr        
Compressor Hours Threshold                              0                    hr        
Compressor Hours Threshold                              0                    hr        
Compressor Low Suction Pressure - Event Control         enabled                        
Compressor Low Suction Pressure - Event Control         enabled                        
Compressor Low Suction Pressure - Event Type            Alarm                          
Compressor Low Suction Pressure - Event Type            Alarm                          
Compressor Short Cycle - Event Control                  enabled                        
Compressor Short Cycle - Event Control                  enabled                        
Compressor Short Cycle - Event Type                     Warning                        
Compressor Short Cycle - Event Type                     Warning                        
Compressor State                                        off                            
Compressor State                                        off                            
Compressor Thermal Overload - Event Control             enabled                        
Compressor Thermal Overload - Event Control             enabled                        
Compressor Thermal Overload - Event Type                Alarm                          
Compressor Thermal Overload - Event Type                Alarm                          
Compressor Utilization                                  57                   %         
Condenser Issue - Event Control                         enabled                        
Condenser Issue - Event Control                         enabled                        
Condenser Issue - Event Type                            Warning                        
Condenser Issue - Event Type                            Warning                        
Cooling Capacity                                        0.0                  kW        
Cooling Capacity                                        0.0                  kW        
Cooling State                                           on                             
Customer Configurable Analog Output Value               0                    %         
Customer Configurable Analog Output Value               0                    %         
Customer Configurable Analog Output Value               53                   %         
Customer Configurable Analog Output Value               57                   %         
Customer Input 1                                        Inactive Event                 
Customer Input 1 - Event Control                        enabled                        
Customer Input 1 - Event Type                           Alarm                          
Customer Input 2                                        Inactive Event                 
Customer Input 2 - Event Control                        enabled                        
Customer Input 2 - Event Type                           Alarm                          
Customer Input 3 - Event Control                        enabled                        
Customer Input 3 - Event Type                           Alarm                          
Customer Input 4 - Event Control                        enabled                        
Customer Input 4 - Event Type                           Alarm                          
Dehumidification Fan Speed Min Set Point                40                   %         
Dehumidifier Hours                                      0                    hr        
Dehumidifier Hours Threshold                            0                    hr        
Dehumidifier State                                      off                            
Dehumidifier Utilization                                0                    %         
Dew Point Dead Band                                     2.2                  deg C     
Dew Point Dead Band                                     4.0                  deg F     
Dew Point Over Temp Threshold                           15.0                 deg C     
Dew Point Proportional Band                             4.4                  deg C     
Dew Point Proportional Band                             7.9                  deg F     
Dew Point Set Point                                     48.0                 deg F     
Dew Point Set Point                                     8.9                  deg C     
Dew Point Under Temp Threshold                          3.9                  deg C     
Dig Scroll Comp Discharge Over Temp - Event Ctrl        enabled                        
Dig Scroll Comp Discharge Over Temp - Event Ctrl        enabled                        
Dig Scroll Comp Discharge Over Temp - Event Type        Alarm                          
Dig Scroll Comp Discharge Over Temp - Event Type        Alarm                          
Dig Scroll Comp Discharge Temp                          Unavailable          deg C     
Dig Scroll Comp Discharge Temp                          Unavailable          deg C     
Dig Scroll Comp Discharge Temp                          Unavailable          deg F     
Dig Scroll Comp Discharge Temp                          Unavailable          deg F     
Electric Reheat State                                   off                            
Electric Reheater Hours                                 0                    hr        
Electric Reheater Hours                                 0                    hr        
Electric Reheater Hours                                 0                    hr        
Electric Reheater Hours Threshold                       0                    hr        
Electric Reheater Hours Threshold                       0                    hr        
Electric Reheater Hours Threshold                       0                    hr        
Energy Consumption                                      Unavailable          kWH       
Ext Air Sensor A Event Control                          disabled                       
Ext Air Sensor A High Humidity - Event Control          disabled                       
Ext Air Sensor A High Humidity - Event Type             Warning                        
Ext Air Sensor A Humidity                               Unavailable          % RH      
Ext Air Sensor A Low Humidity - Event Control           disabled                       
Ext Air Sensor A Low Humidity - Event Type              Alarm                          
Ext Air Sensor A Over Temp - Event Control              disabled                       
Ext Air Sensor A Over Temp - Event Type                 Warning                        
Ext Air Sensor A Temperature                            Unavailable          deg C     
Ext Air Sensor A Temperature                            Unavailable          deg F     
Ext Air Sensor A Under Temp - Event Control             disabled                       
Ext Air Sensor A Under Temp - Event Type                Alarm                          
Ext Air Sensor B Humidity                               23.3                 % RH      
Ext Air Sensor B Temperature                            14.3                 deg C     
Ext Air Sensor B Temperature                            57.7                 deg F     
Ext Air Sensor C Humidity                               Unavailable          % RH      
Ext Air Sensor C Temperature                            Unavailable          deg C     
Ext Air Sensor C Temperature                            Unavailable          deg F     
Ext Compressor Lockout - Event Control                  enabled                        
Ext Compressor Lockout - Event Type                     Warning                        
Ext Condenser Pump High Water - Event Control           enabled                        
Ext Condenser Pump High Water - Event Type              Warning                        
Ext Free Cooling Lockout - Event Control                enabled                        
Ext Free Cooling Lockout - Event Type                   Warning                        
Ext Humidifier Lockout - Event Control                  enabled                        
Ext Humidifier Lockout - Event Type                     Warning                        
Ext Loss of Flow - Event Control                        enabled                        
Ext Loss of Flow - Event Type                           Alarm                          
Ext Over Temperature - Event Control                    enabled                        
Ext Over Temperature - Event Type                       Alarm                          
Ext Reheat Lockout - Event Control                      enabled                        
Ext Reheat Lockout - Event Type                         Warning                        
Fan Control Mode                                        Auto                           
Fan Hours                                               8498                 hr        
Fan Hours Exceeded - Event Control                      enabled                        
Fan Hours Exceeded - Event Type                         Warning                        
Fan Hours Threshold                                     0                    hr        
Fan Issue - Event Control                               enabled                        
Fan Speed                                               53                   %         
Fan Speed Delta Control                                 0                              
Fan Speed Maximum Set Point                             80                   %         
Fan State                                               on                             
Fluid Flow Rate                                         -32768               m3/h      
Fluid Flow Rate                                         -32768               m3/h      
Free Cooling Fluid Temperature                          Unavailable          deg C     
Free Cooling Fluid Temperature                          Unavailable          deg F     
Free Cooling Internal Control Mode                      Disabled                       
Free Cooling Internal Temperature Delta                 4.5                  deg C     
Free Cooling Internal Temperature Delta                 8.1                  deg F     
Free Cooling State                                      off                            
Free Cooling Status                                     No Support                     
Free Cooling Valve Hours                                0                    hr        
Free Cooling Valve Hours Threshold                      0                    hr        
Free Cooling Valve Open Position                        0                    %         
Heating Fan Speed Min Set Point                         50                   %         
High Power Shutdown - Event Control                     enabled                        
High Power Shutdown - Event Type                        Warning                        
High Return Air Temperature Threshold                   34.0                 deg C     
High Return Air Temperature Threshold                   93.2                 deg F     
High Return Humidity - Event Control                    enabled                        
High Return Humidity - Event Type                       Warning                        
High Return Humidity Threshold                          99.0                 % RH      
Hot Water / Hot Gas State                               off                            
Hot Water / Hot Gas Valve Hours                         0                    hr        
Hot Water / Hot Gas Valve Hours Threshold               0                    hr        
Hot Water / Hot Gas Valve Open Position                 0                    %         
Humidification Fan Speed Min Set Point                  75                   %         
Humidifier Hours                                        0                    hr        
Humidifier Hours Threshold                              0                    hr        
Humidifier Issue - Event Control                        enabled                        
Humidifier Issue - Event Type                           Alarm                          
Humidifier State                                        off                            
Humidifier Utilization                                  0                    %         
Humidity Control Integration Time                       0                    min       
Humidity Control Type                                   Relative                       
Humidity Dead Band                                      0.0                  % RH      
Humidity Proportional Band                              10                   % RH      
Humidity Set Point                                      50                   % RH      
Infrared Humidifier Flush Rate                          150                  %         
Instantaneous Power                                     Unavailable          W         
Low Return Air Temperature Threshold                    14.0                 deg C     
Low Return Air Temperature Threshold                    57.2                 deg F     
Low Return Humidity - Event Control                     enabled                        
Low Return Humidity - Event Type                        Warning                        
Low Return Humidity Threshold                           1.0                  % RH      
MAN-OFF-AUTO Switch                                     2                              
Main Fan Overload - Event Control                       enabled                        
Main Fan Overload - Event Type                          Alarm                          
Main Valve                                              0                              
Maintenance Ramp                                        0                    %         
Maintenance Tracking State                              off                            
Master Unit Communication Lost - Event Control          enabled                        
Master Unit Communication Lost - Event Type             Warning                        
Minimum Chilled Water Temp Set Point                    44.6                 deg F     
Minimum Chilled Water Temp Set Point                    7.0                  deg C     
Minimum Chilled Water Temp Set Point Enable             disabled                       
Outside Air Temperature                                 Unavailable          deg C     
Outside Air Temperature                                 Unavailable          deg F     
Power Meter Status                                      0                              
Raw Auxiliary Air Temperature                           Unavailable          deg C     
Raw Auxiliary Air Temperature                           Unavailable          deg F     
Reheat Utilization                                      0                    %         
Return Air Over Temp - Event Control                    enabled                        
Return Air Over Temp - Event Type                       Warning                        
Return Air Sensor Event Control                         enabled                        
Return Air Temperature                                  27.4                 deg C     
Return Air Temperature                                  81.3                 deg F     
Return Air Under Temp - Event Control                   enabled                        
Return Air Under Temp - Event Type                      Warning                        
Return Damper Status                                    open                           
Return Dew Point                                        47.1                 deg F     
Return Dew Point                                        8.4                  deg C     
Return Humidity                                         30.4                 % RH      
Server Class                                            AIR                            
Shutdown - Loss Of Power - Event Control                disabled                       
Shutdown - Loss Of Power - Event Type                   Warning                        
Smoke Detected - Event Control                          enabled                        
Smoke Detected - Event Type                             Alarm                          
Static Pressure Set Point                               0.10                 inWC      
Static Pressure Set Point                               25                   Pa        
Super Saver Call For Cooling                            0                    %         
Supply Air Temperature                                  20.0                 deg C     
Supply Air Temperature                                  68.0                 deg F     
Supply Air Temperature Sensor Control                   Temp Only                      
Supply Air Temperature Set Point                        20.0                 deg C     
Supply Air Temperature Set Point                        68.0                 deg F     
System Date and Time                                    2024-02-22 21:17:47            
System Input RMS A-B                                    Unavailable          VAC       
System Input RMS A-N                                    Unavailable          VAC       
System Input RMS B-C                                    Unavailable          VAC       
System Input RMS B-N                                    Unavailable          VAC       
System Input RMS C-A                                    Unavailable          VAC       
System Input RMS C-N                                    Unavailable          VAC       
System Input RMS Current Phase A                        Unavailable          A AC      
System Input RMS Current Phase B                        Unavailable          A AC      
System Input RMS Current Phase C                        Unavailable          A AC      
System Model Number                                     PDX-PCW                        
System Name                                             UNIT                           
System On/Off Control                                   on                             
System Static Pressure                                  0                    Pa        
System Static Pressure                                  0.00                 inWC      
System Status                                           Normal Operation               
Today's High Air Temperature                            27.7                 deg C     
Today's High Air Temperature                            81.9                 deg F     
Today's High Air Temperature Time                       11:28:46                       
Today's High Humidity                                   30.6                 % RH      
Today's High Humidity Time                              12:58:05                       
Today's Low Air Temperature                             27.3                 deg C     
Today's Low Air Temperature                             81.1                 deg F     
Today's Low Air Temperature Time                        00:00:06                       
Today's Low Humidity                                    28.5                 % RH      
Today's Low Humidity Time                               06:45:24                       
Underfloor Static Pressure Control Enable               disabled                       
Unit Control Mode                                       Internal (Auto)                
Unit Off Reason                                         None                           
Unit Operating State                                    on                             
Water Under Floor - Event Control                       enabled                        
Water Under Floor - Event Type                          Alarm                          

About

Nagios/Icinga2 check for Liebert / Vertiv air conditioning controller

Topics

Resources

Stars

Watchers

Forks

Releases

No releases published

Packages