46 changes: 41 additions & 5 deletions ontology/yaml/resources/METERS/entity_types/ABSTRACT.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -75,9 +75,10 @@ PVCM:
- phase2_neutral_line_voltage_sensor
- phase3_neutral_line_voltage_sensor

# TODO: rename to make this more intuitive
PWMRDM:
guid: "4bfb27f6-0a27-48d9-8830-81c84d95c8ab"
description: "Energy monitoring from Electrical Grid and Generator with run hours monitoring."
description: "Energy monitoring from electrical grid and generator with run hours monitoring."
is_abstract: true
uses:
- generator_energy_accumulator
Expand All @@ -87,16 +88,51 @@ PWMRDM:

TPWM:
guid: "141dc3bf-85dd-4fce-9342-9a5462b3c274"
description: "Thermal power and thermal energy monitoring."
description: "Thermal power and thermal energy monitoring (typically used for heat meters)."
is_abstract: true
uses:
- thermal_energy_accumulator
- thermal_power_sensor
- thermal_energy_accumulator
- thermal_power_sensor

VCM:
guid: "dc4d2839-c00d-4935-bc67-013f7721535f"
description: "Current and voltage monitoring"
description: "Current and voltage monitoring."
is_abstract: true
uses:
- current_sensor
- voltage_sensor

VAM:
guid: "8f73213c-b12d-45e3-954d-6c876ddb12fc"
description: "Volume accumulator monitoring."
is_abstract: true
opt_uses:
- flowrate_sensor
uses:
- volume_accumulator

WVAM:
guid: "a9b16412-be29-4dd8-815f-544bf72a8fae"
description: "Water volume accumulator monitoring."
is_abstract: true
opt_uses:
- water_flowrate_sensor
- water_linearvelocity_sensor
uses:
- water_volume_accumulator

GVAM:
guid: "c7761aab-7560-4c62-9095-e9931b0f4c81"
description: "Gas volume accumulator monitoring."
is_abstract: true
opt_uses:
- gas_flowrate_sensor
uses:
- gas_volume_accumulator

GTM:
guid: "011225da-4eb3-4875-a1df-0f3cc3a2a7a0"
description: "Gas temperature monitoring."
is_abstract: true
uses:
- gas_temperature_sensor
5 changes: 2 additions & 3 deletions ontology/yaml/resources/METERS/entity_types/EM.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -53,9 +53,6 @@ EM_PWM_PVCM:
- EM
- PWM
- PVCM
opt_uses:
- reactive_energy_accumulator
- apparent_energy_accumulator

EM_PWM_AVCM:
guid: "441a3b57-05e7-426d-bed9-061f28f21b3a"
Expand Down Expand Up @@ -127,6 +124,7 @@ EM_ION:
- EM_PWM_AVCM_PLPM_PVCM
- DEPRECATED

# TODO: fully delete this type (duplicate of EM_PWM_NONCANONICAL_2 and not implemented by any entities)
EM_PWM_NONCANONICAL_1:
guid: "5063ee14-dd44-4d34-a17c-9b0d4f5cff43"
description: "Non-standard type."
Expand Down Expand Up @@ -154,6 +152,7 @@ EM_PWM_NONCANONICAL_2:
- average_line_current_sensor
- average_inter_line_voltage_sensor

# TODO: fully delete this type (not implemented by any entities)
EM_PWM_PLPM_PVCM_NONCANONICAL_2:
guid: "867a7be3-2023-49c2-a1da-4805abfaf9a0"
description: "SE PM5100 Meter"
Expand Down
13 changes: 4 additions & 9 deletions ontology/yaml/resources/METERS/entity_types/FM.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -12,15 +12,10 @@
# See the License for the specific language governing permissions and
# limitations under the License.

FM_STANDARD:
FM_VAM:
guid: "05f00511-9d04-4c98-ac9f-6aba9f0c9fe7"
description: "Standard flow meter typically for liquid."
description: "Standard closed-loop flow meter, typically for liquid."
is_canonical: true
implements:
- FM
is_canonical: true
uses:
- volume_accumulator
- flowrate_sensor
opt_uses:
- failed_alarm

- VAM
20 changes: 16 additions & 4 deletions ontology/yaml/resources/METERS/entity_types/GENERALTYPES.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -19,38 +19,50 @@ MTR:
is_abstract: true
implements:
- EQUIPMENT
opt_uses:
- failed_alarm

EM:
guid: "cba37f53-9e19-4498-80d1-6053d993f4ac"
description: "Tag for all the electrical meter types."
is_abstract: true
implements:
- MTR
is_abstract: true
opt_uses:
- failed_alarm

GM:
guid: "919ece3f-2f6f-4c9d-adcf-2a77eed49185"
description: "Tag for all gas meters."
is_abstract: true
implements:
- MTR
is_abstract: true
opt_uses:
- failed_alarm

FM:
guid: "e89d919e-ecfb-4852-aeab-c087b0fabf6d"
description: "Tag for all closed-loop system flow meters. Distinct from water meters which are open-loop systems."
is_abstract: true
implements:
- MTR
- MTR
opt_uses:
- failed_alarm

WM:
guid: "c1df623f-c71b-45a1-89eb-2bc7c82f291a"
description: "Tag for all water meters (open-loop), such as the main building water consumption meter."
is_abstract: true
implements:
- MTR
is_abstract: true
opt_uses:
- failed_alarm

HM:
guid: "9496631b-c154-4d86-857d-c2ffff88ffe4"
description: "Tag for all heat meters (cooling or heating), commonly referred to as BTU meters."
is_abstract: true
implements:
- MTR
opt_uses:
- failed_alarm
24 changes: 10 additions & 14 deletions ontology/yaml/resources/METERS/entity_types/GM.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -12,26 +12,22 @@
# See the License for the specific language governing permissions and
# limitations under the License.

GM_STANDARD:
GM_GVAM_GTM:
guid: "96de90c9-fb62-4557-b29c-aa723e255a8f"
description: "The typical building gas meter."
description: "Gas meter that measures volume and temperature."
is_canonical: true
implements:
- GM
is_canonical: true
uses:
- gas_flowrate_sensor
- gas_volume_accumulator
- gas_temperature_sensor
- GVAM
- GTM

GM_PULSE:
GM_GVAM:
guid: "0b74bcd2-f3c6-42b2-9a91-88f34c5d472d"
description: "Gas meter that operates by counting pulses, interpreted into flow and accumulated volume."
description: "Gas meter that measures volume accumulated (e.g., pulse meter)."
is_canonical: true
implements:
- GM
is_canonical: true
uses:
- gas_flowrate_sensor
- gas_volume_accumulator
- GVAM

GM_TPWM:
guid: "223b81fb-9fcf-475b-a2f5-ad5d1364454c"
Expand All @@ -41,4 +37,4 @@ GM_TPWM:
- GM
- TPWM
opt_uses:
- gas_temperature_sensor
- gas_temperature_sensor # TODO: examine optional usage of this (remove and implement GTM, if possible)
42 changes: 19 additions & 23 deletions ontology/yaml/resources/METERS/entity_types/HM.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -12,55 +12,51 @@
# See the License for the specific language governing permissions and
# limitations under the License.


# TODO: rename this type
HM_STANDARD:
guid: "7f96b71e-3f47-4872-b770-71a4b8021677"
description: "General water-side thermal load heat meter."
is_canonical: true
implements:
- HM
- TPWM
- HVAC/WDT # inherits from HVAC namespace
uses:
- flowrate_sensor
- supply_water_temperature_sensor
- return_water_temperature_sensor
- thermal_power_sensor
- thermal_energy_accumulator
- flowrate_sensor # TODO: change to water_flowrate_sensor (for continuity) and implement WVAM
opt_uses:
- water_volume_accumulator
- water_volume_accumulator # TODO: determine if this can be promoted to `uses` (if so, implement WVAM)

HM_CHW:
guid: "4439f98a-c52b-4fff-8765-84e689862423"
description: "Cooling load heat meter."
is_canonical: true
implements:
- HM
is_canonical: true
- HVAC/CHWDT # inherits from HVAC namespace
- HVAC/CHWFRM # inherits from HVAC namespace
uses:
- chilled_water_flowrate_sensor
- chilled_supply_water_temperature_sensor
- chilled_return_water_temperature_sensor
- cooling_thermal_power_sensor
- cooling_thermal_energy_accumulator
- cooling_thermal_power_sensor # TODO: justify if `cooling` needs to be specified here, if not implement TPWM
- cooling_thermal_energy_accumulator # TODO: justify if `cooling` needs to be specified here, if not implement TPWM
opt_uses:
- differential_temperature_sensor
- failed_alarm

HM_CHW_WAC:
HM_CHW_WVAM:
guid: "441029f3-1324-42c5-aca2-74138500917a"
description: "Cooling load heat meter with total chilled water volume accumulator."
is_canonical: true
implements:
- HM_CHW
is_canonical: true
uses:
- water_volume_accumulator
- WVAM

HM_HW:
guid: "12427c9d-7d96-4551-b5de-e7d78a7d3674"
description: "Heating load heat meter."
is_canonical: true
implements:
- HM
is_canonical: true
- HVAC/HWDT # inherits from HVAC namespace
uses:
- heating_water_flowrate_sensor
- heating_supply_water_temperature_sensor
- heating_return_water_temperature_sensor
- heating_thermal_power_sensor
- heating_thermal_energy_accumulator
- heating_water_flowrate_sensor # TODO: justify if `heating` needs to be specified here
- heating_thermal_power_sensor # TODO: justify if `heating` needs to be specified here, if not implement TPWM
- heating_thermal_energy_accumulator # TODO: justify if `heating` needs to be specified here, if not implement TPWM
23 changes: 11 additions & 12 deletions ontology/yaml/resources/METERS/entity_types/WM.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -12,27 +12,26 @@
# See the License for the specific language governing permissions and
# limitations under the License.

WM_STANDARD:
WM_WVAM:
guid: "7cbdf4a9-82f0-4dd5-991f-14984cbce4cb"
description: "Standard building water meter."
description: "Standard building water meter with volume monitoring."
is_canonical: true
implements:
- WM
is_canonical: true
uses:
- water_volume_accumulator
- WVAM # TODO: we are creating tech debt to model it like this (in theory we should not need to specify `water` and could simply use the VAM type)
opt_uses:
- failed_alarm
- flowrate_sensor
- flowrate_sensor # TODO: remove this and rely on optional usage of `water_flowrate_sensor` in the WVAM type

# TODO: potentially deprecate this type (not currently implemented by any entities)
WM_WF:
guid: "df942136-4b98-4da7-9e68-acc210d6cf03"
description: "Water supply flow rate meter with counter."
is_canonical: true
implements:
- WM
is_canonical: true
uses:
- supply_water_flowrate_sensor
- supply_water_flowrate_sensor # TODO: examine why `supply` is needed
opt_uses:
- supply_water_volume_accumulator
- water_linearvelocity_sensor
- water_volume_accumulator
- supply_water_volume_accumulator # TODO: examine why `supply` is needed
- water_linearvelocity_sensor # TODO: remove and rely on optional usage in WVAM type
- water_volume_accumulator # TODO: remove and rely on optional usage in WVAM type