Permalink
Corrected wrong assignment and use of evaluate_etaPL
Browse files Browse the repository at this point in the history
For #1200
  • Loading branch information
mwetter committed Sep 12, 2019
1 parent 7648d71 commit 5c24d68
Showing 1 changed file with 11 additions and 4 deletions.
15 changes: 11 additions & 4 deletions IBPSA/Fluid/Chillers/BaseClasses/Carnot.mo
Original file line number Diff line number Diff line change
Expand Up @@ -124,8 +124,8 @@ partial model Carnot

Real etaPL(final unit = "1")=
if evaluate_etaPL
then 1
else IBPSA.Utilities.Math.Functions.polynomial(a=a, x=yPL)
then IBPSA.Utilities.Math.Functions.polynomial(a=a, x=yPL)
else 1
"Efficiency due to part load (etaPL(yPL=1)=1)";

Real COP(min=0, final unit="1") = etaCarnot_nominal_internal * COPCar * etaPL
Expand Down Expand Up @@ -157,8 +157,8 @@ protected

// For Carnot_y, computing etaPL = f(yPL) introduces a nonlinear equation.
// The parameter below avoids this if a = {1}.
final parameter Boolean evaluate_etaPL=
(size(a, 1) == 1 and abs(a[1] - 1) < Modelica.Constants.eps)
final parameter Boolean evaluate_etaPL =
not ((size(a, 1) == 1 and abs(a[1] - 1) < Modelica.Constants.eps))
"Flag, true if etaPL should be computed as it depends on yPL"
annotation(Evaluate=true);

Expand Down Expand Up @@ -382,6 +382,13 @@ and the part load ratio are set up.
</html>", revisions="<html>
<ul>
<li>
September 12, 2019, by Michael Wetter:<br/>
Corrected value of <code>evaluate_etaPL</code> and how it is used.
This correction only affects protected variables and does not affect the results.<br/>
This is for <a href=\"https://github.com/ibpsa/modelica-ibpsa/issues/1200\">
#1200</a>.
</li>
<li>
June 16, 2017, by Michael Wetter:<br/>
Added temperature difference between fluids in condenser and evaporator
for computation of nominal COP and effectiveness.<br/>
Expand Down