The model Buildings.Examples.VAVReheat.BaseClasses.Controls.FreezeStat has no hysteresis set.
This causes Guideline36 to stall as reported in #2693 (comment)
To correct this, a hysteresis needs to be set.
The text was updated successfully, but these errors were encountered:
The model
Buildings.Examples.VAVReheat.BaseClasses.Controls.FreezeStat
has no hysteresis set.This causes
Guideline36
to stall as reported in #2693 (comment)To correct this, a hysteresis needs to be set.