You signed in with another tab or window. Reload to refresh your session.You signed out in another tab or window. Reload to refresh your session.You switched accounts on another tab or window. Reload to refresh your session.Dismiss alert
In our former data model, only large conventional power plants > 50MW were able to dispatch reactive power for voltage stability (control = 'PV'), all renewable and smaller conventional power plants had control = 'PQ'.
But technical requirements for all power plants have changed in the last years. According to 'Technische Anschlussbedingungen Mittelspannung, Westnetz, 2019' all power plants with an installed capacity > 475kW(p) have to be able to dispatch reactive power for voltage stability.
So I would like to update our assumption for control strategies.
I suggest to set control = 'PV' for all wind parks, conventional generators, pumped hydro storage units and solar ground mounted because the are most likely > 475kW(p). Assuming that most pv rooftop plants are smaller than 475kWp, I would set control = 'PQ' for all solar rooftop plants.
The text was updated successfully, but these errors were encountered:
In our former data model, only large conventional power plants > 50MW were able to dispatch reactive power for voltage stability (
control = 'PV'
), all renewable and smaller conventional power plants hadcontrol = 'PQ'
.But technical requirements for all power plants have changed in the last years. According to 'Technische Anschlussbedingungen Mittelspannung, Westnetz, 2019' all power plants with an installed capacity > 475kW(p) have to be able to dispatch reactive power for voltage stability.
So I would like to update our assumption for control strategies.
I suggest to set control = 'PV' for all wind parks, conventional generators, pumped hydro storage units and solar ground mounted because the are most likely > 475kW(p). Assuming that most pv rooftop plants are smaller than 475kWp, I would set control = 'PQ' for all solar rooftop plants.
The text was updated successfully, but these errors were encountered: