preliminary equations #428

Merged
merged 13 commits into from
Nov 24, 2023
152 changes: 141 additions & 11 deletions docs/user_manual/components.md
Original file line number Diff line number Diff line change
Expand Up @@ -133,6 +133,17 @@ if any of the faults in any of the scenarios within a batch are not three-phase
(i.e. `fault_type` is not `FaultType.three_phase`).
```

#### Electric Model

`line` is described by a π model, where

$$
\begin{eqnarray}
Z_\mathrm{series} & = & r + \mathrm{j}x \\
Y_\mathrm{shunt} & = & 2 \pi fc/(tan \sigma +\mathrm{j})
\end{eqnarray}
$$

### Link

* type name: `link`
Expand All @@ -142,6 +153,15 @@ two busbars inside a substation. It has a very high admittance (small impedance)
(equivalent to 10e6 siemens for 10kV network). Therefore, it is chosen by design that no sensors can be coupled to a `link`.
There is no additional attribute for `link`.

#### Electric Model:
`link` is modeled by a constant reactance $Y_\mathrm{series}$, where

$$
\begin{eqnarray}
Y_\mathrm{series} & = & 1 & \times 10^6 * ( 1+ \mathrm{j} ) p.u. &.
\end{eqnarray}
$$

### Transformer

`transformer` is a {hoverxreftooltip}`user_manual/components:branch` which connects two nodes with possibly different voltage
Expand Down Expand Up @@ -181,6 +201,29 @@ It can happen that `tap_min > tap_max`. In this case the winding voltage is decr
increased.
```

#### Electric Model
`transformer` is described by a π model, where $Z_\mathrm{series}$ can be computed as

$$
\begin{eqnarray}
& |Z_\mathrm{series}| = uk / z_\mathrm{base}\\
&\mathrm{Re}(Z_\mathrm{series}) = (pk/sn) / z_\mathrm{base}\\
&\mathrm{Im}(Z_\mathrm{series}) = \sqrt{|Z_\mathrm{series}|^2-\mathrm{Re}(Z_\mathrm{series})^2} \\
\end{eqnarray}
$$

and $Y_\mathrm{shunt}$ can be computed as

$$
\begin{eqnarray}
&|Y_\mathrm{shunt}| = i0 / y_\mathrm{base} \\
&\mathrm{Re}(Y_\mathrm{shunt}) = (sn/p0) / y_\mathrm{base} \\
&\mathrm{Im}(Y_\mathrm{shunt}) = -\sqrt{|Y_\mathrm{shunt}|^2-\mathrm{Re}(Y_\mathrm{shunt})^2} \\
\end{eqnarray}
$$

where $z_\mathrm{base} = 1/ y_\mathrm{base}= sn/(u2^2)$.

## Branch3

* type name: `branch3`
Expand Down Expand Up @@ -287,6 +330,7 @@ It can happen that `tap_min > tap_max`. In this case the winding voltage is decr
increased.
```


## Appliance

* type name: `appliance`
Expand Down Expand Up @@ -339,6 +383,32 @@ with an internal impedance. The impedance is specified by convention as short ci
| `rx_ratio` | `double` | - | R to X ratio | ❌ default 0.1 | ❌ | `>= 0` |
| `z01_ratio` | `double` | - | zero sequence to positive sequence impedance ratio | ❌ default 1.0 | ❌ | `> 0` |

#### Electric Model
`source` is modeled by an internal constant impedance $r+\mathrm{j}x$ with positive sequence and zero sequence.
Its value can be computed using following equations:

- for positive sequence,

$$
\begin{eqnarray}
& z_\mathrm{source} = s_\mathrm{base} / sk \\
& x_1 = z_\mathrm{source} \times \sqrt{1+ rx\_ ratio^2}\\
& r_1= x_1 \times rx\_ ratio
\end{eqnarray}
$$

where $s_\mathrm{base}$ is a constant value $1 \times 10^6$.

- for zero sequence,

$$
\begin{eqnarray}
&z_\mathrm{source,0} = z_\mathrm{source} \times z01\_ ratio\\
&x_0 = z_\mathrm{source,0} \times \sqrt{1+ rx\_ ratio^2}\\
&r_0= x_0 \times rx\_ ratio
\end{eqnarray}
$$

### Generic Load and Generator

* type name: `generic_load_gen`
Expand Down Expand Up @@ -369,6 +439,39 @@ However, the reference direction and meaning of `RealValueInput` is different, a
| `p_specified` | `RealValueInput` | watt (W) | specified active power | ✨ only for power flow | ✔ |
| `q_specified` | `RealValueInput` | volt-ampere-reactive (var) | specified reactive power | ✨ only for power flow | ✔ |

##### Electric model

`generic_load_gen` are modelled by using the so-called ZIP load model in power-grid-model,
where a load/generator is represented as a composition of constant power (P), constant current (I) and constant impedance (Z).

The injection of each ZIP model type can be computed as follows:

- for a constant impedance (Z) load/generator,

$$
\begin{eqnarray}
S = S_\mathrm{specified} \times \bar{u}^2
\end{eqnarray}
$$

- for a constant current (I) load/generator,

$$
\begin{eqnarray}
S = S_\mathrm{specified} \times \bar{u}
\end{eqnarray}
$$

- for a constant power (P) load/generator:,

$$
\begin{eqnarray}
S = S_\mathrm{specified}
\end{eqnarray}
$$

where $\bar{u}$ is the calculated node voltage.

### Shunt

* type name: `shunt`
Expand All @@ -392,6 +495,9 @@ if any of the faults in any of the scenarios within a batch are not three-phase
(i.e. `fault_type` is not `FaultType.three_phase`).
```

#### Electric Model
`shunt` is modelled by a fixed admittance which equals to $g + \mathrm{j}b$.

## Sensor

* type name: `sensor`
Expand Down Expand Up @@ -421,6 +527,7 @@ a `node`.
| --------- | --------- | -------- | --------------------------------------------------------------------------------------------------------------- | :--------------------------------: | :------: | :----------: |
| `u_sigma` | `double` | volt (V) | standard deviation of the measurement error. Usually this is the absolute measurement error range divided by 3. | ✨ only for state estimation | ✔ | `> 0` |


#### Voltage Sensor Concrete Types

There are two concrete types of voltage sensor. They share similar attributes:
Expand All @@ -446,6 +553,16 @@ voltage is a line-to-line voltage. In a `asym_voltage_sensor` the measured volta
| `u_residual` | `RealValueOutput` | volt (V) | residual value between measured voltage magnitude and calculated voltage magnitude |
| `u_angle_residual` | `RealValueOutput` | rad | residual value between measured voltage angle and calculated voltage angle (only possible with phasor measurement units) |

#### Electric Model
`generic_voltage_sensor` is modeled by following equations:

$$
\begin{eqnarray}
&& u\_ residual = u\_ measured - u\_ state \\
&& u\_ angle\_ residual = u\_ angle\_ measured - u\_ angle\_ state
\end{eqnarray}
$$

### Generic Power Sensor

* type name: `generic_power_sensor`
Expand Down Expand Up @@ -508,6 +625,16 @@ See the documentation on [state estimation calculation methods](calculations.md#
| `p_residual` | `RealValueOutput` | watt (W) | residual value between measured active power and calculated active power |
| `q_residual` | `RealValueOutput` | volt-ampere-reactive (var) | residual value between measured reactive power and calculated reactive power |

#### Electric Model
`Generic Power Sensor` is modeled by following equations:

$$
\begin{eqnarray}
p\_ residual = p\_ measured - p\_ state \\
q\_ residual = q\_ measured - q\_ state
\end{eqnarray}
$$

## Fault

* type name: `fault`
Expand Down Expand Up @@ -537,17 +664,6 @@ If any of the faults in any of the scenarios within a batch are not `three_phase
the calculation is treated as asymmetric.
```

##### Default values for `fault_phase`

In case the `fault_phase` is not specified or is equal to `FaultPhase.default_value`, the power-grid-model assumes the following fault phases for different values of `fault_type`.

| `fault_type` | `fault_phase` |
| ---------------------------------- | ---------------- |
| `FaultType.three_phase` | `FaultPhase.abc` |
| `FaultType.single_phase_to_ground` | `FaultPhase.a` |
| `FaultType.two_phase` | `FaultPhase.bc` |
| `FaultType.two_phase_to_ground` | `FaultPhase.bc` |

#### Steady state output

A `fault` has no steady state output.
Expand All @@ -558,3 +674,17 @@ A `fault` has no steady state output.
| ----------- | ----------------- | ---------- | ------------- |
| `i_f` | `RealValueOutput` | ampere (A) | current |
| `i_f_angle` | `RealValueOutput` | rad | current angle |

#### Electric Model
Four types of short circuit fault are included in power-grid-model.

| `fault_type` | `fault_phase` | description |
| ---------------------------------- | ---------------- |-------------------------------------------------------------------------|
| `FaultType.three_phase` | `FaultPhase.abc` | Three phases are connected with impedance z_f. |
| `FaultType.single_phase_to_ground` | `FaultPhase.a` | One phase is grounded with impedance z_f, and other phases are open. |
| `FaultType.two_phase` | `FaultPhase.bc` | Two phases are connected with impedance z_f. |
| `FaultType.two_phase_to_ground` | `FaultPhase.bc` | Two phases are connected with impedance z_f then grounded. |

In case the `fault_phase` is not specified or is equal to `FaultPhase.default_value`, the power-grid-model assumes the following fault phases for different values of `fault_type`.