Example using TcHmi on IPC with multiple screens (or multiple clients accessing different screens)

Disclaimer

This is a personal guide not a peer reviewed journal or a sponsored publication. We make no representations as to accuracy, completeness, correctness, suitability, or validity of any information and will not be liable for any errors, omissions, or delays in this information or any losses injuries, or damages arising from its display or use. All information is provided on an as is basis. It is the reader’s responsibility to verify their own facts.

The views and opinions expressed in this guide are those of the authors and do not necessarily reflect the official policy or position of any other agency, organization, employer or company. Assumptions made in the analysis are not reflective of the position of any entity other than the author(s) and, since we are critically thinking human beings, these views are always subject to change, revision, and rethinking at any time. Please do not hold us to them in perpetuity.

Overview

Typically an IPC will have a single screen which will be used as a HMI. This will require, starting a browser in kiosk mode, then directing it to TcHmi (typically using a shortcut).

There are applications which will require more than one screen with each screen showing a different view of TcHMI. This project shows you one method to achieve this.

  1. Add a code behind javascript which will allow the current view to be selected via a query string passed in the URL.
  2. Create two shortcuts to control chrome's startup location.
  3. Change the default url in the shortcuts to include the new query string.

This example code can also be used when more than one client needs to access different pages from the server.

Getting Started

1. Additions to your TcHMI project

The code we will add will allow us to replace

http://127.0.0.1:1010/

with

http://127.0.0.1:1010?view=Desktop

In this example we have a second view called ExtendedDesktop which can now be accessed by the following,

http://127.0.0.1:1010?view=ExtendedDesktop

You will need to add the code below, to a "CodeBehind" JavaScript file to your project. Either copy the "ViewSelector.js" from the included project or create a new code behind file and paste in the following code, shown in the steps below.

a. The code snippet which does the work

const urlParams = new URLSearchParams(window.location.search);
const view = urlParams.get("view");

if (!view) return;
TcHmi.View.load(view + ".view");

b. Creating the code behind file

screen layout

c. The complete code once added to the code behind file.

screen layout

At this point you project is now able to accept queries passed in via the location bar.

2. Create two shortcuts

Shortcut 1 (Main screen)

"C:\Program Files (x86)\Google\Chrome\Application\chrome.exe" --new-window "http://localhost:1010" --window-size="1024,768" --window-position="0,0" --kiosk --user-data-dir="C:/temp/Profiles/1"

Shortcut 2 (Second screen)

"C:\Program Files (x86)\Google\Chrome\Application\chrome.exe" --new-window "http://localhost:1010" --window-size="1024,768" --window-position="-1024,0" --kiosk --user-data-dir="C:/temp/Profiles/2"

Please note that you will need to set the second window-position so that it correctly sits on your second screen.

--window-position="-1024,0"

This may require setting a positive or negative position depending on which side the second screen is placed.

screen layout

It is also important to set the two profiles to different values as the window position is stored here.

3. Change the default url

Shortcut 1 (Main screen)

"C:\Program Files (x86)\Google\Chrome\Application\chrome.exe" --new-window "http://localhost:1010?view=Desktop" --window-size="1024,768" --window-position="0,0" --kiosk --user-data-dir="C:/temp/Profiles/1"

Shortcut 2 (Second screen)

"C:\Program Files (x86)\Google\Chrome\Application\chrome.exe" --new-window "http://localhost:1010?view=ExtendedDesktop" --window-size="1024,768" --window-position="-1024,0" --kiosk --user-data-dir="C:/temp/Profiles/2"

You can request any view simply by changing the value. It must match the name of a view in your TcHmi Project.