-
Notifications
You must be signed in to change notification settings - Fork 0
New issue
Have a question about this project? Sign up for a free GitHub account to open an issue and contact its maintainers and the community.
By clicking “Sign up for GitHub”, you agree to our terms of service and privacy statement. We’ll occasionally send you account related emails.
Already on GitHub? Sign in to your account
Verifications for Section 5.16.2 of ASHRAE Guideline 36 #3
Changes from 13 commits
7ed198d
0af5f43
f46aed4
91d65a7
dbec9ba
91f25da
2d548ce
bc62021
da752f0
f302a52
253d72f
6da99d3
3156f08
a1b54cc
File filter
Filter by extension
Conversations
Jump to
Diff view
Diff view
There are no files selected for viewing
Original file line number | Diff line number | Diff line change |
---|---|---|
@@ -1,6 +1,6 @@ | ||
on: | ||
push: | ||
branches: [ develop ] | ||
branches: [ '*' ] | ||
There was a problem hiding this comment. Choose a reason for hiding this commentThe reason will be displayed to describe this comment to others. Learn more. Changed the workflow so we run the tests on all pushes. |
||
pull_request: | ||
branches: [ '*' ] | ||
|
||
|
Original file line number | Diff line number | Diff line change |
---|---|---|
|
@@ -532,5 +532,291 @@ | |
], | ||
"description_verification_type": "rule-based", | ||
"assertions_type": "pass" | ||
} | ||
}, | ||
"G36_SupplyAirTemperatureSetpoint": { | ||
There was a problem hiding this comment. Choose a reason for hiding this commentThe reason will be displayed to describe this comment to others. Learn more. @leijerry888 FYI, Jeremy and I discussed that the names should match the class names. Also, as of There was a problem hiding this comment. Choose a reason for hiding this commentThe reason will be displayed to describe this comment to others. Learn more. Fixed in the latest commit! |
||
"library_item_id": 30, | ||
"description_brief": "Supply air temperature operation following the Guideline 36 recommendations", | ||
"description_detail": "Verify that the supply air temperature setpoint of a system follows the Guideline 36 recommendations", | ||
"description_index": ["Section 5.16.2.2 in ASHRAE Guideline 36-2021"], | ||
"description_datapoints": { | ||
"operation_mode": "System operation mode", | ||
"oa_t": "Outdoor air temperature", | ||
"t_max": "Maximum supply air temperature setpoint based on requests", | ||
"sa_t_sp_ac": "Actual supply air temperature setpoint", | ||
"oa_t_min": "Minimum outdoor air temperature for linear SAT reset", | ||
"oa_t_max": "Maximum outdoor air temperature for linear SAT reset", | ||
"min_clg_sa_t_sp": "Minimum cooling supply air temperature setpoint", | ||
"max_clg_sa_t_sp": "Maximum cooling supply air temperature setpoint", | ||
"sa_sp_tol": "supply air temperature tolerance" | ||
}, | ||
"description_verification_type": "procedure-based", | ||
"assertions_type": "pass", | ||
"description_assertions": [ | ||
"if t_max > max_clg_sa_t_sp", | ||
" fail", | ||
"end", | ||
"", | ||
"switch operation_mode", | ||
"case 'cooldown'", | ||
" sa_t_sp = min_clg_sa_t_sp", | ||
"case 'warmup', 'setback", | ||
" sa_t_sp = 35 # 95 F", | ||
"case 'occupied', 'setup'", | ||
" if oa_t <= oa_t_min", | ||
" sa_t_sp = t_max", | ||
" else if oa_t >= oa_t_max", | ||
" sa_t_sp = min_clg_sa_t_sp", | ||
" else", | ||
" sa_t_sp = (oa_t - oa_t_min) * (t_max - min_clg_sa_t_sp) / (oa_t_min - oa_t_max) + t_max ","# linear interpolation", | ||
" end", | ||
"end", | ||
"", | ||
"if abs(sa_t_sp - sa_t_s_ac) < sa_sp_tol", | ||
" pass", | ||
"else", | ||
" fail", | ||
"end" | ||
] | ||
}, | ||
"G36_SimultaneousHeatingCooling": { | ||
"library_item_id": 31, | ||
"description_brief": "Verifiy that both the heating and cooling coil are not operating at the same time", | ||
"description_index": ["Section 5.16.2.3 in ASHRAE Guideline 36-2021"], | ||
"description_datapoints": { | ||
"heating_output": "AHU heating coil output", | ||
"cooling_output": "AHU cooling coil output" | ||
}, | ||
"description_verification_type": "procedure-based", | ||
"assertions_type": "pass", | ||
"description_assertions": [ | ||
"if heating_output > 0 and cooling_output > 0", | ||
" fail", | ||
"else", | ||
" pass", | ||
"end" | ||
] | ||
}, | ||
"G36_ReturnAirDamperWithReturnPathNoAirFlowTracking": { | ||
"library_item_id": 32, | ||
"description_brief": "Verify that the return air damper operation follows Guideline 36 recommendations for systems with relief damper/fan", | ||
"description_detail": "Verify that the return air damper operation follows the Guideline 36 recommendations for supply air temperature setpoint operations", | ||
"description_index": ["Section 5.16.2.3 in ASHRAE Guideline 36-2021"], | ||
"description_datapoints": { | ||
"max_ra_p": "Maximum return air damper position", | ||
"ra_p_tol": "Return air damper position tolerance", | ||
"ra_p": "Return air damper position", | ||
"oa_p": "Outdoor air damper position", | ||
"max_oa_p": "Maximum outdoor air damper position" | ||
}, | ||
"description_verification_type": "procedure-based", | ||
"assertions_type": "pass", | ||
"description_assertions": [ | ||
"if heating_output > 0", | ||
" if abs(ra_p - max_ra_p) < ra_p_tol", | ||
" pass", | ||
" else", | ||
" fail", | ||
" end", | ||
"else if cooling_output > 0", | ||
" if abs(ra_p - 0) < ra_p_tol", | ||
" pass", | ||
" else", | ||
" fail", | ||
" end", | ||
"else if oa_p < max_oa_p", | ||
" if abs(ra_p - max_ra_p) < ra_p_tol", | ||
" pass", | ||
" else", | ||
" fail", | ||
" end", | ||
"else if abs(oa - max_oa_p) < oa_p_tol", | ||
" if ra_p < max_ra_p", | ||
" pass", | ||
" else", | ||
" fail", | ||
" end", | ||
"end" | ||
] | ||
|
||
}, | ||
"G36_OutdoorAirDamperWithReturnPathNoAirFlowTracking": { | ||
"library_item_id": 33, | ||
"description_brief": "Verify that the outdoor air damper operation follows Guideline 36 recommendations for systems with relief damper/fan", | ||
"description_detail": "Verify that the outdoor air damper operation follows the Guideline 36 recommendations for supply air temperature setpoint operations", | ||
"description_index": ["Section 5.16.2.3 in ASHRAE Guideline 36-2021"], | ||
"description_datapoints": { | ||
"heating_output": "AHU heating coil output", | ||
"cooling_output": "AHU cooling coil output", | ||
"economizer_high_limit_reached": "Economizer high limit flag", | ||
"oa_p": "Outdoor air damper position", | ||
"min_oa_p": "Minimum outdoor air damper position", | ||
"max_oa_p": "Maximum outdoor air damper position", | ||
"oa_p_tol": "Outdoor air damper position tolerance", | ||
"ra_p_tol": "Return air damper position tolerance", | ||
"ra_p": "Return air damper position", | ||
"max_ra_p": "Maximum return air damper position" | ||
}, | ||
"description_verification_type": "procedure-based", | ||
"assertions_type": "pass", | ||
"description_assertions": [ | ||
"if heating_output > 0", | ||
" if abs(oa_p - min_oa_p) < oa_p_tol", | ||
" pass", | ||
" else", | ||
" fail", | ||
" end", | ||
"else if cooling_output > 0", | ||
" if economizer_high_limit_reached", | ||
" if abs(oa_p - min_oa_p) < oa_p_tol", | ||
" pass", | ||
" else", | ||
" fail", | ||
" end", | ||
" else", | ||
" if abs(oa_p - max_oa_p) < oa_p_tol", | ||
" pass", | ||
" else", | ||
" fail", | ||
" end", | ||
" end", | ||
"else if ra_p < max_ra_p", | ||
" if abs(oa_p - max_oa_p) < oa_p_tol", | ||
" pass", | ||
" else", | ||
" fail", | ||
" end", | ||
"else if abs(ra_p - max_ra_p) < ra_p_tol", | ||
" if min_oa_p < oa_p < max_oa_p", | ||
" pass", | ||
" else", | ||
" fail", | ||
" end", | ||
"end" | ||
] | ||
}, | ||
"G36_ReturnAirDamperWithReturnPathWithAirFlowTracking": { | ||
"library_item_id": 34, | ||
"description_brief": "Verify that the return air damper operation follows Guideline 36 recommendations for systems with return fan with airflow tracking", | ||
"description_detail": "Verify that the return air damper operation follows the Guideline 36 recommendations for supply air temperature setpoint operations", | ||
"description_index": ["Section 5.16.2.3 in ASHRAE Guideline 36-2021"], | ||
"description_datapoints": { | ||
"heating_output": "AHU heating coil output", | ||
"cooling_output": "AHU cooling coil output", | ||
"max_ra_p": "Maximum return air damper position", | ||
"ra_p_tol": "Return air damper position tolerance", | ||
"ra_p": "Return air damper position", | ||
"rea_p": "Relief air damper position" | ||
}, | ||
"description_verification_type": "procedure-based", | ||
"assertions_type": "pass" | ||
}, | ||
"G36_OutdoorAirDamperWithReturnPathWithAirFlowTracking": { | ||
"library_item_id": 35, | ||
"description_brief": "Verify that the outdoor air damper operation follows Guideline 36 recommendations for systems with return fan with airflow tracking", | ||
"description_detail": "Verify that the outdoor air damper operation follows the Guideline 36 recommendations for supply air temperature setpoint operations", | ||
"description_index": ["Section 5.16.2.3 in ASHRAE Guideline 36-2021"], | ||
"description_datapoints": { | ||
"oa_p": "Outdoor air damper position", | ||
"max_oa_p": "Maximum outdoor air damper position", | ||
"oa_p_tol": "Outdoor air damper position tolerance" | ||
}, | ||
"description_verification_type": "procedure-based", | ||
"assertions_type": "pass", | ||
"description_assertions": [ | ||
"if abs(oa_p - max_oa_p) < oa_p_tol", | ||
" pass", | ||
"else", | ||
" fail", | ||
"end" | ||
] | ||
}, | ||
"G36_ReliefAirDamperWithReturnPathWithAirFlowTracking": { | ||
"library_item_id": 36, | ||
"description_brief": "Verify that the outdoor air damper operation follows Guideline 36 recommendations for systems with return fan with airflow tracking", | ||
"description_detail": "Verify that the outdoor air damper operation follows the Guideline 36 recommendations for supply air temperature setpoint operations", | ||
"description_index": ["Section 5.16.2.3 in ASHRAE Guideline 36-2021"], | ||
"description_datapoints": { | ||
"heating_output": "AHU heating coil output", | ||
"cooling_output": "AHU cooling coil output", | ||
"max_rea_p": "Maximum return air damper position", | ||
"rea_p_tol": "Return air damper position tolerance", | ||
"rea_p": "Return air damper position", | ||
"ra_p": "Relief air damper position" | ||
}, | ||
"description_verification_type": "procedure-based", | ||
"assertions_type": "pass", | ||
"description_assertions": [ | ||
"if heating_output > 0", | ||
" if abs(rea_p - 0) < rea_p_tol", | ||
" pass", | ||
" else", | ||
" fail", | ||
" end", | ||
"else if cooling_output > 0", | ||
" if abs(rea_p - max_rea_p) < rea_p_tol", | ||
" pass", | ||
" else", | ||
" fail", | ||
" end", | ||
"else if abs(rea_p - (1 - ra_p) * max_rea_p) < rea_p_tol", | ||
" pass", | ||
"else", | ||
" fail", | ||
"end" | ||
] | ||
}, | ||
"G36_ReturnAirDamperWithReturnWithBuildingPressureControl": { | ||
"library_item_id": 37, | ||
"description_brief": "Verify that the return air damper operation follows Guideline 36 recommendations for systems with return fan with direct building pressure control", | ||
"description_detail": "Verify that the return air damper operation follows the Guideline 36 recommendations for supply air temperature setpoint operations", | ||
"description_index": ["Section 5.16.2.3 in ASHRAE Guideline 36-2021"], | ||
"description_datapoints": { | ||
"heating_output": "AHU heating coil output", | ||
"cooling_output": "AHU cooling coil output", | ||
"max_ra_p": "Maximum return air damper position", | ||
"ra_p_tol": "Return air damper position tolerance", | ||
"ra_p": "Return air damper position" | ||
}, | ||
"description_verification_type": "procedure-based", | ||
"assertions_type": "pass", | ||
"description_assertions": [ | ||
"if heating_output > 0", | ||
" if abs(ra_p - max_ra_p) < ra_p_tol", | ||
" pass", | ||
" else", | ||
" fail", | ||
" end", | ||
"else if cooling_output > 0", | ||
" if abs(ra_p - 0) < ra_p_tol", | ||
" pass", | ||
" else", | ||
" fail", | ||
" end", | ||
"else if abs(ra_p - (1 - rea_p) * max_ra_p) < ra_p_tol", | ||
" pass", | ||
"else", | ||
" fail", | ||
"end" | ||
] | ||
}, | ||
"G36_OutdoorAirDamperWithReturnWithBuildingPressureControl": { | ||
"library_item_id": 38, | ||
"description_brief": "Verify that the outdoor air damper operation follows Guideline 36 recommendations for systems with return fan with direct building pressure control", | ||
"description_detail": "Verify that the outdoor air damper operation follows the Guideline 36 recommendations for supply air temperature setpoint operations", | ||
"description_index": ["Section 5.16.2.3 in ASHRAE Guideline 36-2021"], | ||
"description_datapoints": { | ||
"oa_p": "Outdoor air damper position", | ||
"max_oa_p": "Maximum outdoor air damper position", | ||
"oa_p_tol": "Outdoor air damper position tolerance" | ||
}, | ||
"description_verification_type": "procedure-based", | ||
"assertions_type": "pass", | ||
"description_assertions": [ | ||
"if abs(oa_p - max_oa_p) < oa_p_tol", | ||
" pass", | ||
"else", | ||
" fail", | ||
"end" | ||
] | ||
} | ||
} |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Changed the workflow so we only build the doc when we push on develop and/or we create a PR.