Data for ECU-R-PRO not matching native interface #99

Closed
dewi-ny-je opened this issue Apr 1, 2022 · 4 comments
Closed

Data for ECU-R-PRO not matching native interface #99

dewi-ny-je opened this issue Apr 1, 2022 · 4 comments

Comments

@dewi-ny-je
Copy link

The values reported

  1. don't match the values from the native web interface
  2. the values for both solar panels of each inverter are always the same, even if the native interface offers independent readings.

See screenshots

image

image

(the ones from 3 to 6 are not posted for conciseness)

Original interface

image

@jeroenkl
Copy link

jeroenkl commented Jun 1, 2022

same issue, waiting for support

@MartijnVdS
Copy link

MartijnVdS commented Nov 24, 2022

ECU-R exposes the data of the inverters, not the separate panels on its RS-485/modbus interface.

However, it does expose the inverters twice, once with integer data + scale factors in model 101/102/103 (single/split/multi phase), once as floats (Sunspec models 111/112/113).

I only have one inverter, so I don't know if each inverter shows up separately, or if it's all added up by the ECU-R into one big "model" object.

@SenH
Copy link

SenH commented Nov 24, 2022

You need to assign each inverter a different Modbus address on the ECU-R but there is no separate panel data indeed.
Screenshot 2022-11-24 at 21 38 28

@dewi-ny-je
Copy link
Author

Thanks