MQTT Topics for HeishaMon

Availability Topic:

ID Topic Response
LWT Online/Offline (automatically returns to Offline if connection with the HeishaMon lost)

Log Topic:

ID Topic Response
LOG1 log response from headpump (level switchable)

Sensor Topics:

ID Topic Response/Description
TOP0 main/Heatpump_State Heatpump state (0=off, 1=on)
TOP1 main/Pump_Flow Pump flow (l/min)
TOP2 main/Force_DHW_State DHW status (0=off, 1=on)
TOP3 main/Quiet_Mode_Schedule Quiet mode schedule (0=inactive, 1=active)
TOP4 main/Operating_Mode_State Operating mode (0=Heat only, 1=Cool only, 2=Auto(Heat), 3=DHW only, 4=Heat+DHW, 5=Cool+DHW, 6=Auto(Heat)+DHW, 7=Auto(Cool), 8=Auto(Cool)+DHW)
TOP5 main/Main_Inlet_Temp Main inlet water temperature (°C)
TOP6 main/Main_Outlet_Temp Main outlet water temperature (°C)
TOP7 main/Main_Target_Temp Main outlet water target temperature (°C)
TOP8 main/Compressor_Freq Compressor frequency (Hz)
TOP9 main/DHW_Target_Temp DHW target temperature (°C)
TOP10 main/DHW_Temp Actual DHW temperature (°C)
TOP11 main/Operations_Hours Heatpump operating time (Hour)
TOP12 main/Operations_Counter Heatpump starts (counter)
TOP13 main/Main_Schedule_State Main thermostat schedule state (inactive - active)
TOP14 main/Outside_Temp Outside ambient temperature (°C)
TOP15 main/Heat_Power_Production Thermal heat power production (Watt)
TOP16 main/Heat_Power_Consumption Elektrical heat power consumption at heat mode (Watt)
TOP17 main/Powerful_Mode_Time Powerful state in minutes (0, 1, 2 or 3 x 30min)
TOP18 main/Quiet_Mode_Level Quiet mode level (0, 1, 2, 3)
TOP19 main/Holiday_Mode_State Holiday mode (0=off, 1=scheduled, 2=active)
TOP20 main/ThreeWay_Valve_State 3-way valve mode (0=Room, 1=DHW)
TOP21 main/Outside_Pipe_Temp Outside pipe temperature (°C)
TOP22 main/DHW_Heat_Delta DHW heating delta (-12 to -2) (K)
TOP23 main/Heat_Delta Heat delta (K)
TOP24 main/Cool_Delta Cool delta (K)
TOP25 main/DHW_Holiday_Shift_Temp DHW Holiday shift temperature (-15 to +15)
TOP26 main/Defrosting_State Defrost state (0=off, 1=on)
TOP27 main/Z1_Heat_Request_Temp Zone 1 Heat Requested shift temp (-5 to 5) or direct heat temp (20 to max)
TOP28 main/Z1_Cool_Request_Temp Zone 1 Cool Requested shift temp (-5 to 5) or direct cool temp (5 to 20)
TOP29 main/Z1_Heat_Curve_Target_High_Temp Target temperature at lowest point on the heating curve (°C)
TOP30 main/Z1_Heat_Curve_Target_Low_Temp Target temperature at highest point on the heating curve (°C)
TOP31 main/Z1_Heat_Curve_Outside_High_Temp Lowest outside temperature on the heating curve (°C)
TOP32 main/Z1_Heat_Curve_Outside_Low_Temp Highest outside temperature on the heating curve (°C)
TOP33 main/Room_Thermostat_Temp Remote control thermostat temp (°C)
TOP34 main/Z2_Heat_Request_Temp Zone 2 Heat Requested shift temp (-5 to 5) or direct heat temp (20 to max)
TOP35 main/Z2_Cool_Request_Temp Zone 2 Cool Requested shift temp (-5 to 5) or direct cool temp (5 to 20)
TOP36 main/Z1_Water_Temp Zone 1 Water outlet temperature (°C)
TOP37 main/Z2_Water_Temp Zone 2 Water outlet temperature (°C)
TOP38 main/Cool_Power_Production Thermal cooling power production (Watt)
TOP39 main/Cool_Power_Consumption Elektrical cooling power consumption (Watt)
TOP40 main/DHW_Power_Production Thermal DHW power production (Watt)
TOP41 main/DHW_Power_Consumption Elektrical DHW power consumption (Watt)
TOP42 main/Z1_Water_Target_Temp Zone 1 water target temperature (°C)
TOP43 main/Z2_Water_Target_Temp Zone 2 water target temperature (°C)
TOP44 main/Error Last active Error from Heat Pump
TOP45 main/Room_Holiday_Shift_Temp Room heating Holiday shift temperature (-15 to 15)
TOP46 main/Buffer_Temp Actual Buffer temperature (°C)
TOP47 main/Solar_Temp Actual Solar temperature (°C)
TOP48 main/Pool_Temp Actual Pool temperature (°C)
TOP49 main/Main_Hex_Outlet_Temp Outlet 2, after heat exchanger water temperature (°C)
TOP50 main/Discharge_Temp Discharge Temperature (°C)
TOP51 main/Inside_Pipe_Temp Inside pipe temperature (°C)
TOP52 main/Defrost_Temp Defrost temperature (°C)
TOP53 main/Eva_Outlet_Temp Eva Outlet temperature (°C)
TOP54 main/Bypass_Outlet_Temp Bypass Outlet temperature (°C)
TOP55 main/Ipm_Temp Ipm temperature (°C)
TOP56 main/Z1_Temp Zone1: Actual Temperature (°C)
TOP57 main/Z2_Temp Zone2: Actual Temperature (°C)
TOP58 main/DHW_Heater_State When enabled, backup/booster heater can be used for DHW heating (disabled - enabled)
TOP59 main/Room_Heater_State When enabled, backup heater can be used for room heating (disabled - enabled)
TOP60 main/Internal_Heater_State Internal backup heater state (inactive - active)
TOP61 main/External_Heater_State External backup/booster heater state (inactive - active)
TOP62 main/Fan1_Motor_Speed Fan 1 Motor rotation speed (R/Min)
TOP63 main/Fan2_Motor_Speed Fan 2 Motor rotation speed (R/Min)
TOP64 main/High_Pressure High Pressure (Kgf/Cm2)
TOP65 main/Pump_Speed Pump Rotation Speed (R/Min)
TOP66 main/Low_Pressure Low Pressure (Kgf/Cm2)
TOP67 main/Compressor_Current Compressor/Outdoor unit Current (Ampere)
TOP68 main/Force_Heater_State Force heater status (0=inactive, 1=active)
TOP69 main/Sterilization_State Sterilisation State (0=inactive, 1=active)
TOP70 main/Sterilization_Temp Sterilisation Temperature (°C)
TOP71 main/Sterilization_Max_Time Sterilisation maximum time (minutes)
TOP72 main/Z1_Cool_Curve_Target_High_Temp Target temperature at highest point on the cooling curve (°C)
TOP73 main/Z1_Cool_Curve_Target_Low_Temp Target temperature at lowest point on the cooling curve (°C)
TOP74 main/Z1_Cool_Curve_Outside_High_Temp Highest outside temperature on the cooling curve (°C)
TOP75 main/Z1_Cool_Curve_Outside_Low_Temp Lowest outside temperature on the cooling curve (°C)
TOP76 main/Heating_Mode Compensation / Direct mode for heat (0 = compensation curve, 1 = direct)
TOP77 main/Heating_Off_Outdoor_Temp Above this outdoor temperature all heating is turned off(5 to 35 °C)
TOP78 main/Heater_On_Outdoor_Temp Below this temperature the backup heater is allowed to be used by heatpump heating logic(-15 to 20 °C)
TOP79 main/Heat_To_Cool_Temp Outdoor temperature to switch from heat to cool mode when in auto setting(°C)
TOP80 main/Cool_To_Heat_Temp Outdoor temperature to switch from cool to heat mode when in auto setting (°C)
TOP81 main/Cooling_Mode Compensation / Direct mode for cool (0 = compensation curve, 1 = direct)
TOP82 main/Z2_Heat_Curve_Target_High_Temp Target temperature at lowest point on the heating curve (°C)
TOP83 main/Z2_Heat_Curve_Target_Low_Temp Target temperature at highest point on the heating curve (°C)
TOP84 main/Z2_Heat_Curve_Outside_High_Temp Lowest outside temperature on the heating curve (°C)
TOP85 main/Z2_Heat_Curve_Outside_Low_Temp Highest outside temperature on the heating curve (°C)
TOP86 main/Z2_Cool_Curve_Target_High_Temp Target temperature at highest point on the cooling curve (°C)
TOP87 main/Z2_Cool_Curve_Target_Low_Temp Target temperature at lowest point on the cooling curve (°C)
TOP88 main/Z2_Cool_Curve_Outside_High_Temp Highest outside temperature on the cooling curve (°C)
TOP89 main/Z2_Cool_Curve_Outside_Low_Temp Lowest outside temperature on the cooling curve (°C)
TOP90 main/Room_Heater_Operations_Hours Electric heater operating time for Room (Hour)
TOP91 main/DHW_Heater_Operations_Hours Electric heater operating time for DHW (Hour)
TOP92 main/Heat_Pump_Model Heat pump model, all values in HeatPumpType.md
TOP93 main/Pump_Duty Pump duty
TOP94 main/Zones_State Zones state (0 = zone1 active, 1 = zone2 active, 2 = zone1 and zone2 active)
TOP95 main/Max_Pump_Duty Max pump duty configured
TOP96 main/Heater_Delay_Time Heater delay time (J-series only)
TOP97 main/Heater_Start_Delta Heater start delta (J-series only)
TOP98 main/Heater_Stop_Delta Heater stop delta (J-series only)
TOP99 main/Buffer_Installed Buffer tank installed
TOP100 main/DHW_Installed DHW tank installed
TOP101 main/Solar_Mode Solar mode (disabled, to buffer, to DHW)
TOP102 main/Solar_On_Delta Solar heating delta on
TOP103 main/Solar_Off_Delta solar heating delta off
TOP104 main/Solar_Frost_Protection Solar frost protection temp
TOP105 main/Solar_High_Limit Solar max temp limit
TOP106 main/Pump_Flowrate_Mode Settings for pump flow rate (0=DeltaT, 1=Maximum flow, J-series only)
TOP107 main/Liquid_Type Type of liquid in settings (Water / Glycol)
TOP108 main/Alt_External_Sensor If external outdoor sensor is selected
TOP109 main/Anti_Freeze_Mode Is anti freeze mode enabled or disabled
TOP110 main/Optional_PCB If the optional PCB is enabled (if installed)
TOP111 main/Z2_Sensor_Settings Setting of the sensor for zone 2 (water, ext thermostat, int. thermostat or thermistor)
TOP112 main/Z1_Sensor_Settings Setting of the sensor for zone 1 (water, ext thermostat, int. thermostat or thermistor)
TOP113 main/Buffer_Tank_Delta Delta of buffer tank setting in Kelvin
TOP114 main/External_Pad_Heater If the external pad heater is enabled (if installed)

All Topics realated with state can have also value -1 - unknown - but only in abnormal situations.

Option PCB Topics:

The following topics are actions from the heatpump to the optional pcb (for example, start pump on zone 2). This is only available if you have enable optional pcb emulation. These values are not visible if you have the real optional pcb installed.

ID Topic Response/Description
OPT0 optional/Z1_Water_Pump Z1 water pump action request (0=off, 1=on)
OPT1 optional/Z1_Mixing_Valve Z1 mixing valve action request (0=off, 1=decrease, 2=increase)
OPT2 optional/Z2_Water_Pump Z2 water pump action request (0=off, 1=on)
OPT3 optional/Z2_Mixing_Valve Z2 mixing valve action request (0=off, 1=decrease, 2=increase)
OPT4 optional/Pool_Water_Pump Pool water pump action request (0=off, 1=on)
OPT5 optional/Solar_Water_Pump Solar water pump action request (0=off, 1=on)
OPT6 optional/Alarm_State Alarm state (0=off, 1=on)

Command Topics:

These topics are commands through heishamon to set modes and values on the heatpump and they can be set by either using:

MQTT: send mqtt message to base_topic/commands/SetTopic (e.g.: panasonic_heat_pump/commands/SetHeatpump)

HTTP REST API: http://x.x.x.x/command?[topic]=[value]&[topic]=[value] (e.g.: http://x.x.x.x/command?SetQuietMode=3&SetZ1HeatRequestTemperature=21_

ID Topic Description Value/Range
SET1 SetHeatpump Set heatpump on or off 0=off, 1=on
SET2 SetHolidayMode Set holiday mode on or off 0=off, 1=on
SET3 SetQuietMode Set quiet mode level 0, 1, 2 or 3
SET4 SetPowerfulMode Set powerful mode run time in minutes 0=off, 1=30, 2=60 or 3=90
SET5 SetZ1HeatRequestTemperature Set Z1 heat shift or direct heat temperature -5 to 5 or 20 to max
SET6 SetZ1CoolRequestTemperature Set Z1 cool shift or direct cool temperature -5 to 5 or 20 to max
SET7 SetZ2HeatRequestTemperature Set Z2 heat shift or direct heat temperature -5 to 5 or 20 to max
SET8 SetZ2CoolRequestTemperature Set Z2 cool shift or direct cool temperature -5 to 5 or 20 to max
SET9 SetOperationMode Sets operating mode 0=Heat only, 1=Cool only, 2=Auto, 3=DHW only, 4=Heat+DHW, 5=Cool+DHW, 6=Auto+DHW
SET10 SetForceDHW Forces DHW (Operating mode should be set first to inlcude DWH mode (operation mode 3,4,5 or 6) to be effective. Please look at SET9 ) 0, 1
SET11 SetDHWTemp Set DHW target temperature 40 - 75
SET12 SetForceDefrost Forces defrost routine 0, 1
SET13 SetForceSterilization Forces DHW sterilization routine 0, 1
SET14 SetPump Set Water Pump to service mode, max speed 0, 1
SET15 SetMaxPumpDuty Set max Water Pump duty in service menu decimal value translate to hexadecimal in service menu
64 to 254
SET16 SetCurves Set zones heat/cool curves JSON document (see below)
SET17 SetZones Set zones to active 0 = zone 1 active, 1 = zone2 active, 2 = zone1 and zone2 active
SET18 SetFloorHeatDelta Set floor heating delta in Kelvin 1-15
SET19 SetFloorCoolDelta Set floor cooling delta in Kelvin 1-15
SET20 SetDHWHeatDelta Set DHW heating delta in Kelvin -12 to -2 (negative value)
SET21 SetHeaterDelayTime Set heater start delay time (only J-series) in minutes
SET22 SetHeaterStartDelta Set heater start delta T (only J-series) in kelvin
SET23 SetHeaterStopDelta Set heater stop delta T (only J-series) in kelvin
SET24 SetMainSchedule Set weekly schedule 0=off, 1=on
SET25 SetAltExternalSensor Set the alternative external outdoor sensor 0=disabled, 1=enabled
SET26 SetExternalPadHeater Set the external pad heater 0=disabled, 1=type-A, 2=type-B
SET27 SetBufferDelta Set buffer tank delta 0 - 10
SET28 SetBuffer Set buffer installed 0=not installed, 1=installed
SET29 SetHeatingOffOutdoorTemp Set Outdoor Temperature to stop heating 5 to 35

If you operate your heatpump in water mode with direct temperature setup: topics ending xxxRequestTemperature will set the absolute target temperature.

But if you operature your heatpump in internal/external thermostat or thermistor mode with direct temperature, you can not use these SET15 and other topics to set the direct temperature. The direct temperature in that modes is stored in the high target compenstation curve value. So to change the requested direct temperature in those modes, use the SET16 to set this value. Maybe this weird behaviour is different for newer heatpump types. So if your heatpump works different, please feel free to updates this note in github.

To send Heating/Cooling Curves on topic SET16 you need to send a flattened JSON document. For example:

{"zone1":{"heat":{"target":{"high":35,"low":25},"outside":{"high":15,"low":-15}},"cool":{"target":{"high":35,"low":25},"outside":{"high":15,"low":-15}}},"zone2":{"heat":{"target":{"high":35,"low":25},"outside":{"high":15,"low":-15}},"cool":{"target":{"high":35,"low":25},"outside":{"high":15,"low":-15}}}}

The structure of the JSON document:

{
	"zone1": {
		"heat": {
			"target": {
				"high": 35,
				"low": 25
			},
			"outside": {
				"high": 15,
				"low": -15
			}
		},
		"cool": {
			"target": {
				"high": 35,
				"low": 25
			},
			"outside": {
				"high": 15,
				"low": -15
			}
		}
	},
	"zone2": {
		"heat": {
			"target": {
				"high": 35,
				"low": 25
			},
			"outside": {
				"high": 15,
				"low": -15
			}
		},
		"cool": {
			"target": {
				"high": 35,
				"low": 25
			},
			"outside": {
				"high": 15,
				"low": -15
			}
		}
	}
}

But you are free to set only the value you need, for example:

{
  "zone1": {
    "heat": {
      "outside": {
        "low": -15
      }
    }
  }
}