Describe the Evoblock and the conditional row in 2.1.2b2
Correct what the shorter pump block does here
Note the shorter pump block seen on a WSB 8
Describe the 2.1.2 log levels and migration cleanup
Note when the write counters start over in 2.1.1
Narrow the entity tables Names and titles share a cell in German and English, and the web interface's values get a table per page, so the tables fit the page.
Fix line breaks left by the source marks
Drop the source marks from the text Where a fact was observed or comes from Weishaupt's documents, the sentence says so; the rest describes the integration.
Document the integration Pages for setup, every entity, how data updates, the web interface, troubleshooting and migration, beside the register reference.
Note the cooling release for the system modes
Identify register 31106 as a copy of the operating mode
Name the flow sensors and B7's refresh interval 33104 is B4 at the condenser, 33105 is B9; 33111 (B7) is refreshed only every three minutes.
Document the input function codes and DHW setpoint 45101-45108 report the function currently set (checked by switching DE1); the codes come from the selection lists of the local web interface. 32101 is the DHW setpoint in force, not the flow setpoint of a DHW charge.
Identify register 33126 as the electrical power
Add the Modbus register reference in English and German
Initial Home page