ArSee v3.6.15 — Visible IEC-101/104 Scaling in Signal List

Release candidate notes. Not published until the immutable exact-source Package workflow succeeds. The current published stable release is v3.6.14. The new v3.6.15 assets/URLs must not be advertised until verified.

What changed

The Signal List Editor previously placed Engineering scaling mode after CA, IOA, Type, Name, Group, Type/Role and Unit within one long scrolling Selected signal panel. On a normal 1360×820 Windows window, a selected TI9 TRAFO SOGI TM POAQ could show only Bay / Description near the end of the panel while all scaling controls were off-screen, despite the scaling engine being correct. This was unusable for routine FAT/SAT calibration.

PR #245 changes the actual WPF editor:

  • Engineering Scaling and Mapping & Commands are separate, compact tabs in the fixed right inspector, not one endless form. A measured analog TI9/10/11/12/13/14/21/34/35/36 opens Scaling automatically; a digital or command row opens Mapping/Commands.
  • Scaling offers Unit, mutually exclusive Factor / TwoPoint mode, and X0, X100, Y0, Y100 in a compact two-column layout. The full four-input TwoPoint range is directly visible in the default 1360×820 WPF viewport without dragging the scrollbar.
  • Factor mode retains Scale/Offset/Ratio primary/secondary and normalized full-scale, independent from the TwoPoint formula. Changing mode never compounds the two calibration mechanisms.
  • CA, IOA, TI and Name remain frozen at the left side of the large signal DataGrid while the user scrolls horizontally. Mapping/Commands retains BAY TYPE, business TYPE, MNEMO, state map, class/COT, feedback and command policy.
  • Type-aware guidance reminds engineers that TI9 normalized X is decoded per-unit, TI11 scaled X is signed I16 counts (not automatically MVar), and TI13 IEEE short float is already in the upstream unit unless project mapping specifies otherwise.

Why this does not change field scaling accuracy

The prior v3.6.14 Factor and TwoPoint implementations remain unchanged. The document-backed 31-point I/O mapping still uses CA=105 and exact IOA/TI identity. The PDF does not provide an approved gateway signed integer-to-MVar factor for FEEDER, KOPEL or TRAFO reactive power TI11 points; these remain raw counts until field engineering data is supplied. Track physical bipolar Q calibration in #243.

The editor continues to preserve existing profile JSON, user-owned calibration, original HEX and IEC quality, timestamps, GI/SBO/control identity and all IEC-101/103/104 engine behavior. The new UI does not silently overwrite old profiles; Sync 31 I/O still requires explicit review and Save As.

Real-WPF acceptance

The exact self-contained Windows executable runs a UI acceptance probe as part of the existing --passive-gui-smoke flow. It opens the actual Signal List Editor at 1360×820, selects TI9 POAQ, and asserts each X0/X100/Y0/Y100 editable field falls within the visible scaling viewport, not merely within the full scrollable content. It also checks TI11 warnings, a digital row's Mapping default, frozen identity columns, and unchanged persisted row data. A first PR candidate failed the above-fold test and was redesigned; the corrected version passed PR software CI.

Publication acceptance remains a separate gate: native installed-update FAT on the exact merged commit, Windows/WPF tests, CodeQL, release executable probe, verified Setup/ZIP, checksums, SPDX SBOM, provenance, immutable GitHub tag and Pages documentation update. This release is not an IEC conformance certificate or field SAT.

See engineering scaling guide, 31-point source analysis and Release Packaging.